Delta DVP16SP11T – digital expansion module with 8 inputs and 8 NPN outputs
Delta DVP16SP11T adds eight 24 V DC digital inputs and eight NPN transistor outputs to compatible Delta DVP Slim CPUs. The CPU expansion connection powers the module. Field input circuits and output loads use their own wiring. Check the exact CPU’s right-side expansion connection and I/O capacity. See DVP Slim digital modules and DVP expansion modules.
S/S input common and C0 output common
The input terminals are S/S and X0–X7. Delta specifies 24 V DC and approximately 5 mA per input. For PNP sensors, connect S/S to 0 V. For NPN sensors, connect S/S to +24 V. Connect the signal wire to its X terminal. All eight inputs share S/S. Use a suitable interface if the application requires both sensor types in the same group.
The output terminals are C0 and Y0–Y7. When on, the NPN transistor sinks current to 0 V. Wire the load between the positive field supply and the Y terminal. Connect C0 to the load supply’s 0 V. The model wiring diagram specifies 5–30 V DC, 0.3 A per output and 1.2 A per C0. Delta’s temperature ratings are 0.3 A at 40 °C, 0.2 A at 45 °C, 0.15 A at 50 °C and 0.1 A at 55 °C per output.
Delta’s series summary also gives 2 A per common. For sizing the loads, use the 1.2 A limit in the model’s wiring diagram, section 7.5.15. Eight 0.20 A loads operating together draw 1.60 A and exceed that limit. Check each channel and the C0 total independently.
From sensor to output in the control panel
On a conveyor, an inductive sensor can detect a metal part, a photoelectric sensor can detect a box, and a limit switch can detect the end position of a mechanism. Check the NPN or PNP wiring for each sensor. The guide to PLC input and output modules explains how the PLC reads these signals and commands a Y output.
When a Y output drives a relay coil, include its current in the C0 calculation. A suitable diode or other suppressor limits the voltage spike from a DC coil as it turns off. Select fuse protection for the load circuit according to the wiring and load current.
Addressing, software and programming cable
X0–X7 and Y0–Y7 are the module’s local terminal markings. Program addresses depend on the CPU and expansion order. If the starting addresses are X20 and Y20, the eight inputs occupy X20–X27 and the eight outputs occupy Y20–Y27. DVP X/Y addresses use octal numbering.
Download the PLC program to the host CPU. For controllers such as DVP-SS2, DVP-SA2 and DVP-SX2, select the connection for the exact CPU model. Use a supported version of WPLSoft or ISPSoft for PLC programming. The UC-PRG020-12A USB-to-RS-232 cable is an option for a compatible COM1 RS-232 port. ISPSoft can manage the connection through COMMGR.
Related models
DVP16SP11TS offers eight PNP transistor outputs. DVP16SP11R offers eight relay outputs. See DVP08SP11T for four inputs and four transistor outputs, DVP16SM11N for input expansion, or DVP08SN11T for NPN output expansion. Compare exact model codes and terminal layouts before replacement.
Editor’s Note
When buying used, ask for photos of the full 16SP11T label, terminals and side expansion connector.
Test all eight inputs and all eight outputs individually. Compare the software X status with the actual terminal signal and LED.
If a Y LED lights but the load stays off, measure the positive load supply and C0 return with a multimeter. Then try a small load you know works.
If the whole group drops out, check the common return and the total current drawn by loads that run together.
For repeat failures with coils, inspect surge suppression and cable routing. Isolate machine power before fitting or removing the unit.