Delta DVP08XN211T adds 8 NPN transistor outputs to DVP-ES2 and DVP-EX2 systems. Its channel count is 0 inputs and 8 outputs. The host PLC program controls the outputs. See ES2/EX2 expansion modules for the product family and Delta DVP PLC files for wiring documents.
Output type and current limits
Y0–Y7 are NPN open collector outputs. When a channel turns on, it sinks load current to 0 V via ZP. Delta's model wiring section gives a load voltage range of 5–30 V DC and resistive-load limits of 0.3 A per channel and 1.2 A total per common. Add the currents of all loads that can be on at the same time because the eight outputs share a return.
Delta's general selection table and DIDO sheet also show 0.5 A per channel and 4 A per common. Size loads using the lower values in the exact model's wiring section 2.5.3 and the electrical specifications in section 2.1. Section 2.1 lists 50 µs turn-on, 200 µs turn-off and a 100 Hz switching limit. The CPU scan cycle also affects the actual switching rate.
24 V DC supply and UP/ZP wiring
The host powers the module electronics through the expansion bus. For the output circuit, connect +24 V DC to UP and 0 V to ZP. Delta specifies a tolerance of −15% to +20% and consumption of up to 10 mA for this auxiliary circuit. Include load current separately when sizing the 24 V DC supply.
For a 24 V DC load, wire one side of the load to +24 V and the other to the selected Y output. An active output carries current from the load to ZP. Verify sink/source compatibility, leave NC terminals unused and connect loads within the specified DC range. Use a suitable suppression diode for DC coils and size the fuse for the circuit.
The module weighs approximately 109 g. It has removable terminal blocks and supports 35 mm DIN rail or screw mounting. Delta specifies an operating temperature range of 0–55 °C.
Addressing, software and programming cable
Y0–Y7 are the local terminal labels. The host CPU and preceding modules determine the PLC addresses. For example, as the first digital expansion on a DVP32ES200R, the eight outputs use Y20–Y27. The module adds zero X input points.
Use WPLSoft or ISPSoft for supported ES2/EX2 CPUs. Check the CPU model and Y addresses in the ladder project. Set the COMMGR channel for an ISPSoft connection. Download the program to the host CPU.
Use UC-PRG020-12A for a USB connection to the CPU's COM1 RS-232 port. For a computer with a native RS-232 port, use UC-MS020-01A. After installing the USB cable driver, select the COM number shown in Windows Device Manager.
Related models
DVP08XN211R provides eight relay outputs with C0/C1 commons. DVP16XN211T provides 16 transistor outputs, DVP08XP211T has four inputs and four transistor outputs, and DVP08XM211N has eight digital inputs. When replacing an older DVP08XN11T, verify the exact ordering code against CPU support and the terminal diagram.
Editor's Note
Check the 211T suffix and the UP/ZP markings together. On a used module, verify that the removable blocks are present and inspect the connector pins and retaining clip for damage.
If every channel stays off, use a multimeter to check voltage and polarity between UP and ZP. A command visible in the host CPU still requires a complete field circuit.
Isolate the machine loads and use a small fused 24 V DC test load to check Y0 through Y7 one by one. Watch the load switch as well as the channel LED.
If a load stays active after the command clears, isolate the field wiring and check for a short circuit. Comparing the channel with a known good test load helps locate the fault in the load circuit or the output.
For a contactor or interposing relay coil, check inrush, suppression and the total current of simultaneously active channels. Save the CPU program and record the Y addresses before changing the module order.
Related topics
Delta PLC · Delta DVP series · DVP expansion modules · Delta DVP PLC PDF files · Second-hand Delta equipment
External references
Delta DVP Series Module Manual (6 January 2026, English, 913 pages. Model wiring on printed page 2-10 / PDF page 44). DVP-ES2 DIDO Instruction Sheet (21 February 2024, English and Chinese, 19 pages). Delta PLC/HMI Cable Selection Guide (15 August 2019, English, 175 pages. ES2/EX2 cables on printed page 1-3).