Delta AS08AD-C

Delta AS08AD-C 8-channel analog current input module

The Delta AS08AD-C is an 8-channel, 16-bit current input module in the Delta AS analog measurement range. Each channel supports 4–20 mA, 0–20 mA or −20 to +20 mA. It reads current signals from pressure, level and flow transmitters.

Supply, terminals and conversion time

The module uses a 24 V DC supply (20.4–28.8 V DC) and has a 250 Ω current input impedance. Terminal pairs I1+/I1− through I8+/I8− serve the eight channels. Check the 2-, 3- or 4-wire transmitter diagram and the 24 V DC supply. The analog section is isolated from the digital section. The channels share the same analog section.

Delta specifies 2 ms per channel, or 1 ms per channel with module firmware V1.02.00 or later. The AS08AD-B has eight voltage inputs. The AS04AD-A has four inputs selectable for voltage or current, the AS06XA-A combines analog inputs and outputs, and the AS04DA-A has four analog outputs.

ISPSoft channel setup and scaling

Verify the CPU model and module order in an AS200 or AS300 project. Select the current mode for each channel in HWCONFIG in ISPSoft and read the data address from the project mapping. Connect to the CPU using COMMGR and a PLC cable suited to its port.

The default integer scale in 4–20 mA mode is 0–32000. For a 0–10 bar transmitter, 4 mA = 0 bar, 12 mA = 5 bar and 20 mA = 10 bar. Verify channel diagnostics and filter settings during commissioning.

PDFs and wiring diagrams

The general AS manual is listed as D06 under OtomasyonAVM PLC accessories files. Chapter 3 of Delta’s module manual covers channel setup, conversion values and wiring. Instruction sheet 5014071702 includes English and Turkish.

Editor's Note

Look for -C on the side label. The front of the module is marked 08AD.

For a used module, ask for photos of the removable terminal block and expansion connector.

If the reading is low, check the loop supply, polarity and channel mode first.

Use a current calibrator at 4, 12 and 20 mA and check the raw value on each channel separately.

Check the engineering unit and scale on the HMI. Monitor channel diagnostics for low-current faults.

Related topics

AS expansion modules · RTD inputs · Thermocouple inputs · Load cell measurement · PLC software

Delta AS PLC series · Delta PLC main category · PLC and HMI manuals · Used Delta equipment

External references

Delta AS Module Manual (EN) · Delta AS Hardware and Operation Manual (EN) · AS08AD-B / AS08AD-C instruction sheet (EN and TR included)