Delta AS02LC-A
Delta AS02LC-A Two-Channel Load Cell Module
Delta AS02LC-A is an AS measurement module for compatible Delta AS200 and Delta AS300 PLCs. It reads two four-wire or six-wire load cells and offers a 24-bit ADC with nine sampling intervals from 2.5 to 400 ms. It can send gross or net weight to the PLC in filling, dosing and hopper weighing applications.
Load cell wiring
The module uses a 24 V DC supply and provides 5 V DC load cell excitation. On each channel, EXC+/EXC− carry excitation and SIG+/SIG− carry the measurement signal. Connect the sense leads of a six-wire cell to SEN+/SEN−. For a four-wire cell, follow the sense jumper arrangement in the instruction sheet. Check the SLD shield terminal on the diagram and review the AS power supply and panel supply layout.
LC Wizard calibration and PLC addresses
Connect the PC with a suitable Delta PLC cable and manage the connection with COMMGR. In ISPSoft, select the AS02LC-A in HWCONFIG and open LC Wizard. Choose 1, 2, 4, 6, 20, 40 or 80 mV/V according to the load cell’s rated sensitivity. Perform a two-point calibration with the empty platform and a known test weight. Check gross, net and tare behavior in Monitor before the first fill cycle.
Delta’s local module example shows D28000–D28006 as the input range and D28007–D28019 as the output range. Check the assigned addresses in HWCONFIG before reading weight or status in the program. The order of the AS expansion modules can change the assignment.
Selecting a module by signal type
Connect a direct mV/V bridge signal to the AS02LC-A. If a separate load cell transmitter supplies 4–20 mA, consider a current input module such as the AS04AD-A or AS08AD-C. For DVP systems, see the DVP Slim load cell modules range, including the DVP01LC-SL, DVP02LC-SL and DVP202LC-SL.
Editor’s Note
When buying used, check the AS02LC-A label and make sure the removable terminal block is present.
If zero drifts with the scale empty, check whether the platform is rubbing against anything before increasing the filter setting.
If the reading moves in the wrong direction under load, isolate power and compare SIG+/SIG− with the load cell diagram.
After calibration, remove the weight and check the return to zero. Verify the reading with an intermediate test weight.
Save the channel settings and calibration record before replacing the module. Verify both channels on the replacement with a known load.