Delta AS04AD-A

Delta AS04AD-A four-channel analog input module

The Delta AS04AD-A is a four-channel, 16-bit analog input module in the Delta AS analog measurement range. It reads voltage and current analog signals, including a 4–20 mA signal from a pressure transmitter.

Input ranges and conversion time

Voltage ranges are 0–5 V, 1–5 V, ±5 V, 0–10 V and ±10 V. Current ranges are 0–20 mA, 4–20 mA and ±20 mA. Input impedance is 2 MΩ in voltage mode and 250 Ω in current mode. Conversion time is 2 ms per channel, or 1 ms per channel with module firmware V1.02.00 or later.

Supply and terminals

The module supply is 24 V DC (20.4–28.8 V DC). Wire a voltage signal between Vn+ and VIn−. For a current signal, jumper Vn+ to In+ on the same channel. Use VIn− as the return. n is the channel number (1–4). Follow Delta’s loop-power diagram for two-wire 4–20 mA transmitters. The analog inputs are not isolated from one another. Delta AS power supplies

ISPSoft channel setup and scaling

Use it as an AS expansion module in compatible AS200 and AS300 systems. Select the voltage or current range for each channel in ISPSoft HWCONFIG. Check the raw data address in the hardware configuration. In 4–20 mA mode, nominal raw integer values are 0 at 4 mA, 16,000 at 12 mA and 32,000 at 20 mA. See COMMGR for PC connectivity and Delta PLC software for version information.

Related modules

The AS08AD-B has eight voltage inputs and the AS08AD-C has eight current inputs. The AS06XA-A has four analog inputs and two analog outputs, and the AS04DA-A has four analog outputs. For direct temperature measurement, use the AS04RTD-A with RTDs such as Pt100 or the AS04TC-A with thermocouples.

Editor’s Note

When buying used, check the full label and removable terminal block. Obtain the correct block before testing if it is missing.

If the current reading is wrong, check the channel mode and the Vn+ / In+ jumper first.

If a two-wire transmitter gives no reading, check loop power and polarity.

On the bench, apply 4, 12 and 20 mA. Compare the raw count first, then the engineering value shown on the display.

If the reading fluctuates, check the analog cable route and the shield connection at FE against the diagram.

Related topics

Delta AS PLC series · Delta PLC · Used Delta equipment · Delta PLC and HMI manuals

External references

AS04AD-A instruction sheet (includes English) · Delta AS Module Manual (EN)