Delta AHCPU520-RS2
Delta AHCPU520-RS2 128K-step PLC CPU module
The Delta AHCPU520-RS2 is a standard Delta AH500 CPU with 128K program steps and two DB9 serial ports. The two ports let you run an operator panel on one link and drives or meters on the other, for example.
Program memory, I/O and rack capacity
The CPU provides 65,536 data registers from D0 to D65535. Delta specifies a system limit of 2,304 physical I/O points, 36 modules and one main rack plus three extension racks. The installed I/O count depends on the selected digital and analog I/O modules. Plan the slot layout around the AH expansion modules and the main rack model.
Install the CPU next to the power supply on the main rack. Select the AH rack supply for the cabinet voltage. The AHPS05-5A accepts 100–240 V AC, and the AHPS15-5A accepts 24 V DC.
COM1, COM2 and the 520-EN variant
COM1 and COM2 can be configured for RS-232, RS-422 or RS-485. When replacing a serial device, record the interface mode, baud rate, parity, stop bits and station address.
The AHCPU520-EN offers the same 128K-step capacity with one serial port and built-in 10/100 Mbit/s Ethernet. The 520-RS2 front panel has two serial ports. See the AH communication modules for projects that need additional serial links. Check the serial interface and rack compatibility when selecting an AH10SCM-5A.
ISPSoft, COMMGR and programming cable
Select the exact CPU model in ISPSoft and use HWCONFIG to match the rack and slot layout to the cabinet. Connect the PC to the CPU’s Mini USB port using a data cable. Delta’s PLC cable guide lists UC-PRG015-01A and UC-PRG030-01A for this connection. Create the USB connection in COMMGR and select it in ISPSoft. If Windows does not detect the CPU, see Appendix A of the AH500 manual for USB driver installation. Find related utilities under Delta PLC software.
Manual and PDF files
AH500 Hardware and Operation Manual — English PDF. Section 2.2.1 covers CPU capacity and communications. Section 2.2.4.1 shows the front panel and ports. Find related documents in the Delta AH PLC PDF archive.
Editor’s Note
When buying used, verify the complete AHCPU520-RS2 label. Inspect both DB9 sockets, the Mini USB port and the rear backplane connector.
Before replacement, back up any program and CPU parameters you can access and record the module layout. Label both COM cables before disconnecting them.
On the bench, use a compatible rack and power supply. Connect through Mini USB first and confirm that you can read the CPU model and firmware version.
Test the ports separately. If a COM LED flashes but the field device returns no data, compare the baud rate, parity and station address.
If BUS FAULT lights, check the rack extension cable and the HWCONFIG slot order before replacing the CPU. On systems configured to restore from SD at startup, verify the card contents and DIP switch setting before applying power.
Related models
The AHCPU510-RS2 supports 64K steps and 1,280 I/O points. The AHCPU521-RS2 supports 192K steps and 2,304 I/O points. The AHCPU530-RS2 supports 256K steps and 4,352 I/O points.
Delta AH PLC series · Delta PLC · Second-hand Delta equipment
External references
Delta AH500 Hardware and Operation Manual · Delta PLC/HMI Cable Selection Guide