Delta AH10EN-5A
Delta AH10EN-5A Ethernet Communication Module
The Delta AH10EN-5A is an Ethernet communication module installed on the main backplane of a Delta AH500 PLC. It exchanges data between the Delta AH PLC and devices on the network. Its two RJ45 ports, X1 and X2, support 10/100 Mbps auto-detection and Auto MDI/MDIX.
The module can operate as a Modbus TCP client and server simultaneously. EtherNet/IP is supported on AH10EN-5A modules running firmware V2.00 or later. As a Scanner, the module initiates I/O connections to network adapters. As an Adapter, it exchanges data over a connection initiated by another Scanner.
Ports, IP Addressing and Connection Capacity
In single-IP mode, the two ports act as a built-in switch on the same network. In dual-IP mode, disable the switch function in HWCONFIG and assign a separate IP address and subnet mask to each port. Delta specifies CAT 5e cabling with a maximum link length of 100 metres.
For Modbus TCP, Delta lists limits of 64 client connections and 128 server connections. For EtherNet/IP I/O, the limits are 64 TCP connections and 64 CIP connections. The EtherNet/IP RPI range is 1–1,000 ms, and the maximum data length per transfer is 500 bytes. In a ring topology, the module is used as a DLR Ring Node.
Commissioning with ISPSoft
In HWCONFIG within ISPSoft, add the AH10EN-5A to the slot it occupies on the main backplane, then set the port mode and IP parameters. Use EIP Builder to check EtherNet/IP connections and their mapping to PLC data addresses. See Delta COMMGR for the PC-to-PLC connection setup.
When adding the module to an existing installation, check the rack layout for the AH expansion modules and the load on the AH power supply. Also check the CPU’s own Ethernet functions. Models such as the AHCPU521-EN and AHCPU560-EN2 have EtherNet/IP capabilities that depend on the CPU version.
AH15EN and Remote I/O Adapter Comparison
The AH15EN-5A has a similar two-port layout and supports Modbus TCP and IEC 60870-5-104. The distinguishing protocol on the AH10EN-5A is EtherNet/IP. The AHRTU-ETHN-5A serves as the Ethernet adapter for the field-side remote I/O rack.
Manuals and PDF Downloads
Delta AH500 Module Manual (PDF, English) · December 25, 2020. Chapter 9 covers the ports, single- and dual-IP modes, connection limits and registers.
Delta EtherNet/IP Operation Manual (PDF, English) · May 13, 2019. Section 3.2.2 covers AH10EN-5A EtherNet/IP specifications. Chapter 4 covers EIP Builder setup.
Editor’s Note
When buying used, read the full AH10EN-5A code on the label. If the job calls for EtherNet/IP, check the installed firmware version as well.
Test X1 and X2 separately on the bench. Inspect the RJ45 latches and the backplane connector.
Before removing the old module, record its slot, port mode, IP addresses and subnet masks. You will need those settings when fitting the replacement.
If the link lights are on but data is missing, check the port mode and possible IP conflicts first. Then verify the Scanner/Adapter role and I/O mapping.
Before connecting to the production network, read a known data address on the bench. Verify both that the connection opens and that the expected value reaches the intended address.
Related Topics
See the AH10SCM-5A for serial communication and the AH10DNET-5A for DeviceNet. For PROFIBUS DP, the AH10PFBM-5A is the master module and the AH10PFBS-5A is the slave module.
Delta Navigation
Delta PLC series · Delta PLC accessories · Delta PLC and HMI manuals · Second-hand Delta Automation
External References
Delta EtherNet/IP Operation Manual · Delta AH Series Catalogue