Delta AH08DA-5A

Delta AH08DA-5A – 8-Channel Voltage and Current Analog Output Module

The Delta AH08DA-5A is an 8-channel analog output module for the Delta AH500 PLC system. Each channel can be configured individually for voltage or current output. The module has 16-bit hardware resolution and a 150 µs conversion time per channel. In the Delta AH analog module range, this model suits panels that need a mix of analog reference signals.

The module can send a speed or position reference calculated by the PLC to a variable frequency drive or a proportional valve driver. Match the module’s analog signal range to the receiving device’s analog input setting.

Output ranges and field wiring

Voltage output ranges are −10 to +10 V, 0–10 V, −5 to +5 V, 0–5 V and 1–5 V. Current output ranges are 0–20 mA and 4–20 mA. Delta specifies a 1 kΩ–2 MΩ load impedance for the 0–10 V and ±10 V ranges, and a 550 Ω maximum total load for current output. See 0–10 V and 4–20 mA for signal selection.

The module has a removable terminal block. Use the channel’s VO and AG terminals for voltage output or IO and AG for current output. The UP/ZP auxiliary supply is nominally 24 VDC, with a specified range of 20.4–28.8 VDC. Route shielded signal cables separately from power cables. See AH power supplies and grounding for panel design.

ISPSoft configuration and addressing

Use HWCONFIG in ISPSoft to set the module slot, channel mode and scaling limits. Each channel’s floating-point output value occupies two 16-bit registers. The eight output values use 16 registers in total. Check the project’s I/O mapping for the actual start address.

For a 4–20 mA channel scaled from 0 to 100, a command of 50 produces 12 mA. Output retention when the module stops can be configured by channel. Check this behavior during commissioning. Use COMMGR for the PC-to-PLC connection and see Delta PLC software for engineering tools and versions.

Related models

The AH04DA-5A provides four channels with selectable voltage and current output. The eight-channel AH08DA-5B is designed for voltage output, and the AH08DA-5C is designed for current output. See the AH06XA-5A for mixed analog input and output, or the AH08AD-5A for eight analog input channels.

Manuals and wiring PDFs

Delta AH500 Module Manual (PDF, English). In Chapter 3, see PDF pages 62–63 (printed 3-2–3-3) for output specifications, page 66 (3-6) for the terminal layout, and pages 78–79 (3-18–3-19) for HWCONFIG and register mapping.

Delta AH500 Hardware and Operation Manual (PDF, English). The AH08DA-5A wiring diagram is on PDF page 240 (printed 4-70). See the Delta AH PLC PDF files archive for other manuals in the series.

Editor’s Note

Check the side label for the complete AH08DA-5A part number when buying a spare.

For a used module, confirm that the removable terminal block is included and inspect the VO, IO and AG terminals.

If an output is missing, check the UP/ZP supply first, then the channel mode selected in HWCONFIG.

Test a current channel at 4, 12 and 20 mA with a suitable test load. If the readings differ, check the scaling and total load first.

Before replacing the module, back up the project and record the channel ranges and output retention settings.