Delta AH08AD-5C 8-channel analog current input module

The Delta AH08AD-5C is an 8-channel, 16-bit analog input module for the Delta AH500 PLC. Its input ranges are 0–20 mA, 4–20 mA and −20 to +20 mA. It brings current signals from pressure, level or flow transmitters into the PLC. Delta specifies a conversion time of 150 µs per channel and a current input impedance of 250 Ω.

Model selection. The AH08AD-5A accepts voltage and current, the AH08AD-5B accepts voltage, and the AH08AD-5C accepts current. The AH08DA-5C is a current output module. Check the AD / DA designation when ordering or replacing a unit.

I+ / I− terminals and the current loop

The removable terminal block has eight channel pairs, from I0+ / I0− through I7+ / I7−. The Delta diagram shows separate connections for two-, three- and four-wire transmitters. With a two-wire transmitter, the supply and input channel are part of the same current loop. At 20 mA, the 250 Ω input drops 5 V. Include that drop and the transmitter’s minimum operating voltage when sizing the loop supply.

Route shielded signal cable away from power wiring. Connect the SLD shield terminal as shown in the manual’s grounding diagram. See Delta AH power supplies for panel supply options.

ISPSoft channel setup and D registers

Set each channel’s input mode in HWCONFIG within Delta ISPSoft. Mode 0 disables the channel. Mode 1 selects 0–20 mA, mode 2 selects 4–20 mA and mode 3 selects −20 to +20 mA. Set the scale endpoints to match the transmitter. Each floating-point channel value uses two 16-bit D registers. All eight channels occupy 16 D registers.

Wiring and setup PDFs

AH500 Hardware and Operation Manual · AH08AD-5C wiring · English PDF · page 239, section 4.9.3. AH500 Module Manual · ISPSoft channel settings · English PDF · page 54. See the Delta AH PLC PDF archive for other documents.

Editor’s Note

When buying a used unit, check the AH08AD-5C nameplate and make sure the removable terminal block is included.
On the bench, select 4–20 mA mode and use a current calibrator to apply 4, 12 and 20 mA.
Test all eight channels individually.
If the reading stays flat, check loop continuity, polarity and the configured input mode first.
Before replacing the module, record the starting D address, channel modes and scaling settings.