6ES5 458-4UA11

Siemens 6ES5 458-4UA11 — 16-Channel Relay Output Module

The Siemens 6ES5 458-4UA11 is a 16-channel digital output module with potential-free electromechanical relay contacts for SIMATIC S5 systems. It belongs to the S5 digital output range. Its module supply is 24 V DC, with a permitted range of 20–30 V DC.

For resistive loads, the contact voltage limit is 60 V DC / 48 V AC. The current rating is 0.5 A with contact suppression and 70 mA without it. Describing this board simply as “16 outputs, 0.5 A” leaves out an essential condition.

Relay outputs and load selection

A relay contact switches a separately supplied load circuit. Keep the module’s 24 V supply distinct from the voltage switched by its contacts. When selecting an interposing relay and socket or a contactor coil, check pickup current as well as steady operating current.

Contact suppression and fuses

The Siemens wiring diagram shows the 6ES5 498-1AB11 contact-suppression module. The 0.5 A inductive-load limit requires both contact suppression and an external suppression circuit at the load. Select protection suitable for the load’s AC or DC circuit.

The board uses 16 × 1 A slow-blow fuses. An intact fuse does not prove that a relay contact is sound: Siemens explicitly states that the fuse does not protect the contact. Investigate a blown fuse rather than increasing its rating.

Supply, enable input and fault checks

Check the F+/F− enable input against the wiring diagram. Do not apply the enable-jumper setting shown for the 458-4UA12 to the 4UA11. The manual’s jumper instruction applies only to the 4UA12.

If an output fails, check the command in the PLC program, the supply and the field circuit in sequence. During troubleshooting, verify cables and connections with measurements rather than relying solely on the LED. Include cabinet grounding in the inspection.

Replacement boards and related models

Match the full order code, front connection and S5 rack arrangement when selecting a spare. Siemens identifies the 4UA13 as the successor to the 4UA11/4UA12; however, it uses solid-state relays, integrated contact suppression and a changed role for the 24 V connection. Review the change notice for the application.

Do not treat the 458-4UC11, 458-7LA11, 458-7LB11 and 458-7LC11 as interchangeable merely because they share the 458 designation. Compare output technology, voltage and load limits using each model’s documentation.

A transistor-output option such as the 457-4UA12 also changes the circuit arrangement. The NPN/PNP distinction does not establish a direct substitute for a potential-free relay contact.

Editor’s note

Start by reading the final characters on the label carefully. Separating the 4UA11 from later versions at the outset makes both spare selection and wiring checks much easier.

Hearing a relay click is encouraging, but let us check a little further. Its contact may be worn or welded. Verify that every output opens and closes under a suitable load; this also avoids blaming a sound board.

If the same channel fails again, look beyond the board. Check coil current, wiring and suppression components. Finding the cause gives the replacement a better chance of lasting.

Before removal, photograph the label, front connection and protection components, and back up the program. Switch off power and follow the system instructions for replacement. A little preparation now saves a good deal of work later.

For a used board, ask which voltage and load were used to test all 16 channels. Checking LEDs and testing under load are different checks. Agree on the test conditions so everyone knows what to expect from the part.

OtomasyonAVM resources and PDFs

+ About Siemens S5 PLCs · Siemens S5 PDF files — our manual archive. Manufacturer documents for this model appear below.

Related topics

+ 498-1AB11 contact suppression · 458-4UA12 · 458-4UC11 · 458-7LA11