6ES5 457-4UA12
Siemens 6ES5 457-4UA12 — 16-Channel Digital Output Module
Siemens 6ES5 457-4UA12 is a 16-channel, galvanically isolated digital output module for SIMATIC S5-135U/155U systems. This member of the S5 digital output family has a 24–60 V DC rated load supply and a permitted supply range of 20–72 V DC. The outputs are diode-decoupled and short-circuit protected.
Switching current for resistive and inductive loads is 5 mA–0.5 A per channel. Lamp loads have a separate limit of 0.22 A, maximum 5 W. Check operating and inrush current when selecting a relay or other load, and assess the power supply against loads switched on simultaneously.
Output connections and enable input
The manufacturer’s wiring diagram shows a separate +/− terminal pair for each output. Check the front connector and wiring against the exact module diagram. Record the existing rack arrangement and terminal numbers before transferring wiring from another module.
The module has an F+/F− enable input. With jumper X20 inserted, the input is active; this is the factory setting. With the jumper open, the enable input is inactive. If outputs do not operate, check the F input and existing jumper position together with commands in the PLC program.
Short-circuit indication and fuses
Green LEDs indicate output status, while a common red LED indicates a short circuit. The H+/H− common signaling output reports a short circuit and has a maximum switching current of 10 mA. Assess its connection to a suitable digital input against the manufacturer’s diagram. The specification lists 16 × 1 A slow-blow fuses.
Cooling and interference control
Total load capability depends on ventilation. Siemens specifies a 100% coincidence factor with ventilation and 50% without ventilation, or 100% up to 35 °C. Check the individual channel current together with the conditions governing simultaneous operation of all outputs.
The manual’s CE notes require shielded signal cable for this exact part number. They also specify a SIFI C or equivalent filter in the 24 V DC load supply. Assess the electromagnetic filter, cable shield and grounding together when investigating electromagnetic interference.
Replacement and troubleshooting
6ES5 457-7LA11, 6ES5 453-4UA12, 6ES5 456-4UA12 and 6ES5 458-4UA12 are other output models for comparison. Verify voltage, output type, current and terminal arrangement before considering interchangeability. Match the complete order number against the installed module.
During troubleshooting, establish whether one channel or all outputs are affected. If analog modules and interface modules in the same rack are also affected, inspect their common supply and connection path. For a single affected output, check its load, wiring and associated fuse.
Editor’s note
With an older Siemens S5 module, start with the label. Photograph the 457-4UA12 code and front connector wiring. Similar-looking modules may have different terminal arrangements, and a clear record makes removal and replacement much easier.
Do not rely solely on a voltage reading with no load connected. Check how the output behaves with its actual load. Pay particular attention to lamps and coils; a faulty load can put the replacement module under the same strain.
If every output is silent, remember the F input and X20 position. Do not remove the jumper simply to make the system run. First establish the purpose of the enable circuit in the existing installation, then follow the wiring diagram.
Back up the program and record the RAM/EPROM memory arrangement, slot address and cable markings before removal. Isolate the supply and verify that the equipment is de-energized. A clear record made before dismantling is one of the most useful tools in an old cabinet.
For used Siemens equipment, ask how operation was verified. Where possible, test all 16 channels individually with a suitable load, and inspect heating, short-circuit indication and connector condition. A few working channels do not establish that the whole module is serviceable.
OtomasyonAVM resources and PDFs
+ S5 digital output modules · S5 cables and connectors
Related topics
+ 6ES5 457-7LA11 — another construction in the 457 family
+ 6ES5 453-4UA12 — output type and current comparison
+ 6ES5 456-4UA12 — load voltage comparison
+ 6ES5 458-4UA12 — different output design
Browse SIMATIC S5
Siemens and external references
+ Same Siemens manual, p. 1-5 — shielded cable and 24 V DC load-supply filter notes for 457-4UA12