6ES5 458-4UC11
Siemens 6ES5 458-4UC11 – 16-Channel Relay Digital Output Module
6ES5 458-4UC11 is a digital output module with 16 normally open relay outputs in the Siemens SIMATIC S5 family. This S5 digital output board arranges its outputs in two isolated groups of eight. Each contact can switch 5 A at 250 V AC with a resistive load; the total current per group is limited to 8 A.
Documented in the SIMATIC S5 S5-135U/155U system manual, this model switches loads through mechanical relay contacts. Contact ratings depend on AC/DC voltage and whether the load is resistive or inductive.
Contact ratings by load type
Resistive loads: 250 V AC → 5 A; 30 V DC → 5 A; 115 V DC → 0.3 A. These ratings apply to individual contacts; the eight-channel group limit also applies.
Inductive loads: 250 V AC → 1.5 A; 30 V DC → 1 A; 115 V DC → 0.08 A. When driving a contactor or external control relay coil, compare its voltage and switching load against these ratings.
Each P0 and P1 group is limited to 8 A total. When selecting fuses and circuit protection, consider more than individual channel current. Include simultaneously energised outputs in the load and protection-current calculation.
24 V relay supply and contact circuits
The relay operating supply is 24 V DC, with a permissible range of 20–30 V DC. The front connection identifies L+ as pin 22 and L− as pin 23. This power supply operates the relays; the load circuits switched by their contacts are connected separately.
The common load connection for the first group is P0: pin 4; for the second group it is P1: pin 25. Compare S5 connection components and connectors against the actual diagram. The two groups are isolated from each other; the eight contacts within each group share a common group connection.
With all outputs active, typical consumption is 5 V / 120 mA from the system bus and 250 mA through L+/L−. Assess relay power and contact loads separately when sizing the PLC power supply. Rated power dissipation is 6.6 W.
Enable input and addressing
The enable connections are F+: pin 1 and F−: pin 2, with a nominal enable voltage of 24 V DC. Check the relay supply and enable state alongside the output command in the PLC program.
During troubleshooting, look beyond the green channel LED. The LED indicates output status; it does not prove that the contact is delivering power to the load. Check the CPU output bit, enable circuit, P0/P1 supply and actual contact conduction together.
Switching life and mechanical specifications
Maximum switching frequency is 10 Hz for resistive loads and 2 Hz for inductive loads. The manual specifies approximately 100,000 electrical operations at 230 V AC / 5 A and 10 million mechanical cycles. Mechanical life does not imply the same electrical life under every load.
Dimensions are 20 × 255 × 195 mm (W × H × D), with an approximate weight of 0.7 kg. Before installation in an S5 rack, check rack/slot suitability, board contacts and the front connection.
Related variants and used-module checks
6ES5 458-4UA11 and 6ES5 458-4UA12 are also S5 relay-output models, but the 4UC11 voltage, current and grouping specifications must not be transferred to them. Match the full order number and connection diagram when selecting a spare.
For used Siemens equipment, inspect the label, relays, heat damage and contact behaviour. After confirming the S5 system architecture, test all 16 outputs with suitable loads and check for welded or high-resistance contacts.
Editor’s note
Start by identifying the actual load. A heater and a contactor coil require different switching-current checks. Using the 5 A figure for every load can needlessly shorten the life of a sound contact.
Checking each output individually is not enough: the group total must stay within 8 A. Two 5 A loads in the same group add up to 10 A. Do the calculation first, before it becomes a heating problem.
Keep the 24 V supply on terminals 22–23 separate from the P0/P1 load circuits in your records. Photograph and label the existing wiring before removing the connector. A few minutes spent recording it makes reassembly much easier.
An illuminated LED and a clicking relay are a useful start, but verify conduction under an actual load. With a used board, its previous switching duty may be unknown. Watch for contact resistance that has quietly increased over time.
If one group stops working, check before condemning the whole board. Start with the relay supply, enable input and affected group supply. Isolate both the module supply and separately fed contact circuits before removal or insertion, then finish by checking every output.
OtomasyonAVM resources and PDFs
Start with About Siemens S5 PLC, S5 digital output modules and how relays work.
The OtomasyonAVM Siemens S5 PDF archive collects our available documents. This description is based on §8.4.18 of the English S5-135U/155U system manual below, which provides the contact ratings and full connection diagram.
Related topics
+ 6ES5 458-4UA11 and 6ES5 458-4UA12: different S5 relay-output variants.
+ Contactors and relays/sockets: selecting the controlled load.
+ Fuse rating and load relationship: channel and group current calculations.
Browse SIMATIC S5
S5 digital output modules · S5 racks · S5 cables and connectors · Used Siemens equipment
Siemens and external references
+ Siemens S5-135U/155U System Manual – C79000-G8576-C199-07, English: §8.4.18, printed 8-67 / PDF 381 for resistive/inductive ratings, group limits, supply, life and dimensions; printed 8-68 / PDF 382 for P0/P1, L+/L−, F+/F− and channel connections.