6ES5 498-1AB11

Siemens 6ES5 498-1AB11 SIMATIC S5 RC Contact Suppression Module

The Siemens 6ES5 498-1AB11 is a four-channel RC contact suppression module for the 458-4UA digital output family in SIMATIC S5-135U/155U systems. Siemens shows its connection on the 6ES5 458-4UA12 relay output module. Each output has a 47 Ω resistor in series with a 47 nF capacitor. The RC branch is wired across the relay contact.

De-energizing a relay or contactor coil can produce a voltage spike across the opening contact. The RC network slows the voltage rise, reducing arcing and switching interference. For inductive loads, Siemens shows an external suppressor across the load in addition to the RC module on the output card.

Which output card and channel group does it fit?

The connection diagram and load ratings in the Siemens manual are for the 16-output 458-4UA12 relay card. The 6ES5 458-4UA11 and 6ES5 458-4UC11 are separate order numbers. Check the applicable manual for their wiring and load limits.

The 458-4UA12 diagram shows RC modules for output groups 1–4, 5–8, 9–12 and 13–16. One 498-1AB11 protects one group of four outputs. Field wiring terminates at the card’s 42-pin front connector. The S5 front connector range includes the single-width 497-4UA12 crimp connector and 497-4UB31 screw-terminal connector.

What load can the relay output switch?

For a 60 V DC or 48 V AC resistive load, the general 458-4UA12 rating is 0.5 A with the RC module fitted and 70 mA without it. The UL footnote gives a maximum of 50 V / 0.5 A for resistive loads. These are contact ratings for the output card.

The 0.5 A maximum for inductive loads requires both the RC module and an external suppressor. At that current, Siemens specifies a maximum switching rate of 0.5 Hz. The manual shows diode suppression for DC loads and Zener diode suppression for AC loads. Assess the load against the relay contact ratings, independently of the output fuse.

How does 1AB11 differ from the 1AA range modules?

The 6ES5 498-1AA11, 6ES5 498-1AA31 and 6ES5 498-1AA51 set measuring ranges on S5 analog input cards. For cards such as the 460-4UA13 and 465-4UA13, use the card’s measuring-range table. The 1AB11 suffix identifies the RC contact suppressor for 458-4UA relay outputs.

Editor’s note

When buying a spare, check the labels on both the 498-1AB11 submodule and the 458-4UA12 output card.

Record the four protected outputs and their connected coils before removal. Bring the machine to a safe stop and isolate both the S5 rack and the separate load supplies.

After a coil change, check the new coil’s AC or DC type, current and external suppressor together. Compare the load-side wiring with the Siemens diagram.

If all outputs are down, start at the S5 power supply and check the 458 card’s 24 V supply. If jumper X35 enables the input, check the F+/F− circuit as well.

For a fault on one output, check its fuse, load wiring and relay contact separately. Siemens specifies replacement of the affected relay after an overload.

OtomasyonAVM resources and PDFs

+ 6ES5 458-4UA12 relay output card · Siemens SIMATIC S5 PLC overview

+ SIMATIC S5 manuals and PDF archive

Related topics

+ 6ES5 458-4UA11 · 6ES5 458-4UC11 · 497-4UB31 screw-terminal front connector

Browse SIMATIC S5

+ SIMATIC S5 digital output modules · SIMATIC S5 · Used Siemens automation equipment

Siemens and external references

+ Siemens ST 50 Catalog, 498-1AB11 and 458-4UA ordering table (PDF)

+ SIMATIC S5-135U/155U System Manual, 458-4UA12 contact ratings (PDF) · RC circuit and output groups · External suppression for AC and DC inductive loads