6ES5 498-1AA31
Siemens SIMATIC S5 6ES5 498-1AA31 ±10 V Four-Channel Measuring Range Submodule
The Siemens 6ES5 498-1AA31 is a four-channel voltage-divider range submodule for SIMATIC S5 analog input modules. On the 460-4UA13 and 465-4UA12, Siemens specifies a ±10 V measuring range in 500 mV base mode. On the 460-4UA13, this range uses ×1 gain. One submodule sets the range for a group of four inputs on the host module.
Use this range for an analog voltage signal from a device or transducer with a −10 to +10 V output. A 0 to 10 V signal uses the positive half of the range. The 498-1AA61 is the ±5 V option, and the 498-1AA41 is the ±20 mA option. For 4 to 20 mA, Siemens lists the 498-1AA51 for two-wire and 498-1AA71 for four-wire transducers separately.
Compatible 460 and 465 modules
The S5-135U and S5-155U system manual lists eight voltage or current inputs and two range submodules on the 460-4UA13. The 465-4UA12 accepts four range submodules for 16 voltage or current inputs. The Siemens U Periphery manual also lists the 1AA31 for the earlier 460-4UA11, 460-4UA12 and 465-4UA11. The ST 50 table also gives this range for the 465-4UA13.
The ST 50 catalog also lists the 498 range submodules for the 460-7LA13 and 465-7LA13 in the S5-115U family. It covers the 460-7LA13 under S5-115U/H/F and the 465-7LA13 under S5-115U/H. Verify the full host-module order number and channel group before replacement.
How base mode and gain affect the range
In 500 mV base mode, a 460-4UA13 can measure ±500 mV on one group of four inputs with a 498-1AA11 and ±10 V on the other group with a 1AA31. The 498-1AA21 gives ±1 V in the same base mode. The two channel groups can use different range cards. Check the host module’s base mode and gain settings against its own table.
For the 460-4UA13, Siemens also lists ±1 V in 50 mV mode at ×1 gain and ±2.5 V in 500 mV mode at ×4 gain. The S5-115F manual notes the higher measurement error with the 50 mV combination. Confirm 500 mV mode and ×1 gain for ±10 V measurement.
Wiring and STEP 5 scaling
Connect the voltage signal to the channel’s M+ and M− terminals as shown in the host module’s wiring diagram. Select the S5 connector and wiring for the installed module. Siemens specifies 50 kΩ input resistance with the card fitted on the ±10 V range of the 460-4UA13 and 465-4UA12.
Siemens expresses the rated range of these analog inputs as ±2048 measurement units. In STEP 5, extract the sign and status bits according to the host module manual before scaling the measurement to engineering units.
Editor’s note
Record the 498-1AA31 label together with the host module’s order number. The 1AA61 looks similar and uses a different voltage range.
Isolate the supply before removal. Photograph the four-channel group, base mode and gain settings.
After replacement, use a known voltage to check the direction and scale of the reading. If a small input produces a larger reading than expected, check the 50/500 mV and gain settings first.
On a 465-4UA12 with mixed Pt100 and voltage inputs, consult the wiring diagram for that arrangement. Siemens Figure 9-24 says to leave wire-break signaling disabled for the CH4–CH7 group when it is fitted with a 1AA31.
For a used submodule, ask for a voltage reading test on all four channels. Record the host module and the range used for the test.
OtomasyonAVM resources and PDFs
+ SIMATIC S5 analog modules · SIMATIC S5 CPUs and racks
+ SIMATIC S5 PDF archive · S5-115U manuals
Related topics
+ 6ES5 460-4UA13 analog input · 6ES5 465-4UA12 analog input
+ 6ES5 498-1AA21 ±1 V range submodule · 6ES5 498-1AA61 ±5 V range submodule
S5 navigation
+ S5 analog modules · SIMATIC S5 · Siemens S5 PLC
External references
+ Siemens S5-135U/155U system manual · 460-4UA13 ranges and gain
+ Siemens S5-135U/155U system manual · 465-4UA12 technical specifications
+ Siemens U Periphery manual · 460-4UA11 range submodules
+ Siemens ST 50 catalog · S5-115U/H/F analog input ordering data