6ES5 535-3LB12
6ES5 535-3LB12 Siemens SIMATIC S5 CP 535 SINEC H1 Communications Processor
The Siemens 6ES5 535-3LB12 is a CP 535 communications processor that connects a SIMATIC S5 PLC to a SINEC H1 network. The classic H1 triax network runs at 10 Mbit/s. The 3LB12 order number excludes the 15 V module. In the CP 535 rack configurations documented for the S5-135U, S5-150U and S5-155U, a submodule fitted to the rack power supply delivers 15 V to the CP slot.
In service, the CP 535 exchanges PLC status and process data with other SINEC H1 stations. Handling blocks such as SEND and RECEIVE move data between the CPU and the CP. The CP handles the network transfer using the connection parameters assigned to each job.
How does it connect to SINEC H1?
Classic SINEC H1 is based on IEEE 802.3 Ethernet. A drop cable runs from the CP network interface to a SINEC H1 transceiver on the 50 Ω triax backbone. The card has a separate PG interface for configuration. When tracing S5 cables in the cabinet, use the cable labels to distinguish the network drop from the PG connection.
The backbone uses N-type coaxial connectors and terminators at the segment ends. Where the installation uses a SINEC H1 repeater, check the stations on either side separately to isolate the affected segment.
SINEC H1 ISO transport connections use the remote station’s Ethernet address and local and remote TSAPs. When selecting a gateway or adding a station, verify the protocol carried over Ethernet separately from the physical connection.
Which rack and 15 V supply does it need?
Use the system’s slot assignment table to check the CP position and backplane supply in the S5 rack. Siemens specifies that the CP 535 occupies two slots in the S5-155U central rack. On a configuration such as the 6ES5 188-3UA22 central rack, record the CP position along with the rack order number.
The S5-150U central rack manual specifies 6ES5 956-0AA11 to supply 15 V to the CP slots. The EG 185U expansion rack’s spare parts table lists 6ES5 956-0AA12. Match the submodule to the full order numbers of the installed rack and power supply.
The 6ES5 955-3LF12 and 6ES5 955-3NF11 rack power supplies have different input requirements. The 5 V / 40 A nameplate rating refers to the main rack output. Confirm the fitted submodule and rack wiring separately for the 15 V supply at the CP slot.
Which COM 535 settings should be recorded?
COM 535 defines the CP’s Ethernet address, the CPU-side interface number, the job number ANR and the local and remote TSAPs for each connection. Compare the job numbers in the CP with the handling block calls in the PLC program.
The CP can store its connection parameters on a RAM or EPROM memory submodule. When replacing the card, retain the COM 535 parameter set and the CP memory submodule order number along with the CPU program backup.
How do the similar order numbers differ?
The 6ES5 535-3LB11 is also a SINEC H1 CP 535. The 6ES5 535-3MA12 is the order number supplied with a 15 V module and appears separately in Siemens’ S5-115U slot assignment tables. For a replacement, match the 3LB12 suffix, the rack configuration and the memory submodule.
The CP 530 6ES5 530-7LA12 serves SINEC L1, while the CP 544 6ES5 544-3UA11 handles point-to-point serial communications. If the equipment list also includes a CP 544B 6ES5 544-3UB11, label the front connection and order number for each card before removal.
Editor’s note
Before removing the card, photograph the 6ES5 535-3LB12 nameplate, the rack slot and the front cable connections. If a quote specifies only CP 535, confirm the suffix and whether the 15 V module is included.
Before trying a spare, use the rack service documentation to check the 15 V submodule in the power supply and the backplane feed to the CP slot.
Back up the working card’s COM 535 settings. Compare the Ethernet address, interface number, job numbers and TSAP pairs when commissioning the replacement.
If several H1 stations drop out together, start with the shared network segment. If the fault affects only this station, start at the drop cable and transceiver and work back toward the CP slot.
After replacement, test the send and receive jobs separately with a working peer. Check the job status in the PLC program and confirm that the peer station’s data updates.
OtomasyonAVM resources and PDFs
See the Siemens SIMATIC S5 PLC guide for the system family and the S5 communications modules page for other processors in the range.
OtomasyonAVM SIMATIC S5 PDF archive
Related topics
Compare CP 535 variants. 6ES5 535-3LB11 · 6ES5 535-3MA12
SINEC H1 network and rack supply. SINEC H1 755 transceiver · 15 V submodule for CP 535
Browse SIMATIC S5
Used Siemens SIMATIC S5 equipment › SIMATIC S5 › S5 communications modules
Siemens documentation and external references
Siemens 6ES5 535-3LB12 data sheet · Order number without the 15 V module
Siemens SINEC H1 Triaxial Network manual · 10 Mbit/s network, cables and transceiver connections
SIMATIC S5-135U system manual · 15 V supply to the CP slots
SIMATIC S5-150U central rack manual · 6ES5 956-0AA11 supply submodule, German PDF
SIMATIC S5-155U system manual · 15 V supply and CP slot layout
SIMATIC S5 EG 185U expansion rack manual · 15 V submodule spare parts entry
SIMATIC S5-115U system manual · CP 535-3MA12 slot assignment tables
COM 535 configuration example in the Siemens CP 552 manual · Section 2.3.5, Ethernet address, ANR and TSAP