6ES5 464-8MA21 is a SIMATIC S5 analog input module with four ±50 mV inputs and linearization plus internal cold-junction compensation for J, K and L thermocouples. It is documented for S5-100U, S5-90U, S5-95U, ET 100U and ET 200U equipment in the Siemens S5 family.

The module converts the millivolt signal from a thermocouple into a digital value for the PLC. With Type J or Type K thermocouples, match the sensor, extension cable and compensation arrangement. When using the module’s internal linearization on several channels, use the same thermocouple type on all those channels.

Measuring ranges and sensor selection

The linearized ranges are J: −200 to +1200 °C, K: −200 to +1369 °C and L: −199 to +900 °C, in 1 °C steps. Check the actual probe rating separately from the module’s thermocouple type range. The curves follow IEC 584 for J/K and DIN 43710 for L; match the thermocouple standard and cable identification.

A Pt100 cannot be connected directly to this module. Pt100 and thermocouple measurements use different principles. For a Pt100 installation, consider a suitable resistance thermometer module such as 6ES5 464-8MF21. The shape of a probe does not identify its electrical output.

Wiring, extension cable and isolation

Input terminals are CH0: 3+/4−, CH1: 5+/6−, CH2: 7+/8− and CH3: 9+/10−. Terminals 1+/2− belong to the compensation arrangement. Match the numbers on the S5 terminal base and connector to the Siemens diagram; do not connect an external supply to these terminals.

With internal compensation, the reference junction is at the module front. For remote connections, use suitable thermocouple extension or compensating cable rather than an arbitrary copper extension. Siemens specifies a maximum 50 m shielded cable. The temperature sensor, polarity and intermediate connections all form part of the measurement circuit.

The inputs are galvanically isolated from ground, but the channels are not isolated from each other. The permitted potential difference between inputs is ±1 V maximum. Check the sensor’s electrical arrangement and grounding before connecting points at different potentials to one module.

Operating switches and PLC data

The eight-position switch group assigns 8 to 50/60 Hz, 7–6 to 1/2/4 channels, 5 to wire-break indication, 4–3 to linearization and 2–1 to temperature compensation. Match linearization and compensation to the selected J/K/L type. Integration time is 20 ms at 50 Hz or approximately 16.6 ms at 60 Hz; this is not the complete module update time.

Values use 12 bits plus sign, in left-justified two’s-complement format. In the PLC program, distinguish raw millivolt scaling from linearized temperature scaling. During troubleshooting, inspect the input word, sign and wire-break/overflow status together.

Related order codes and used-module checks

6ES5 464-8MA11 also belongs to the ±50 mV class; account separately for the MA21’s internal linearization and compensation. 464-8MB11 ±1 V and 464-8MC11 ±10 V have different voltage ranges.

464-8MD11 ±20 mA and 464-8ME11 4–20 mA are current-input versions. Before ordering, compare the complete order number, label photograph, switch positions and channel test results. A similar housing or order code does not establish replacement compatibility.

Editor’s note

If the temperature looks wrong, give the basics a careful check before condemning the module. Confirm whether the probe is J or K, then compare that with the switch settings. The wrong type selection can make a healthy card look faulty.

If someone has extended the thermocouple wiring with copper cable, start there. Moving the junction changes the compensation arrangement. Understand the cable run before judging the card.

If all four channels drift by a similar amount, inspect shared settings and the reference junction first. If just one channel misbehaves, start with its probe and terminals. This is a useful diagnostic approach, rather than proof of a particular fault.

For a used module, one plausible room-temperature reading is only a starting point. Ask for several test points on the channels you will use, with a suitable thermocouple simulator, and check wire-break indication. Record the operating mode used for the test.

Before removing a card from an older S5 installation, photograph its switches and wiring. Comparing the replacement with that record and the manual is much easier than trying to reconstruct the original arrangement afterward.

OtomasyonAVM resources and PDFs

+ S5 analog modules and background information on Siemens S5 PLCs.

+ S5 PDF archive — system manuals and wiring documents. For the MA21, see S5-100U printed pages 11-8–11-9 and 14-40–14-41. The manufacturer manuals linked below are in English.

Related topics

+ How thermocouples work · Pt100 versus thermocouple · Thermocouple standards.

+ 464-8MA11 ±50 mV · 464-8MF11 Pt100 · 464-8MF21 Pt100 with linearization.

Browse SIMATIC S5

+ S5 analog modules · S5 modular I/O group · SIMATIC S5 · Siemens S5 PLC.

Siemens and external references

+ Siemens S5-100U System Manual, EWA 4NEB 812 6120-02b — switch settings on 11-8–11-9; wiring and specifications on 14-40–14-41.

+ Siemens S5-90U/S5-95U System Manual, EWA 4NEB 812 6115-02b — MA21 wiring, compensation and thermocouple options on 15-46–15-54.

+ Siemens ET 100U Manual, EWA 4NEB 812 6040-02a — 464-8MA21 wiring and specifications on 2-38–2-39.

+ Siemens ET 200U Manual, EWA 4NEB 812 6087-02b — analog processing and MA21 operating settings in chapter 7.