6ES5 470-8MB11
Siemens 6ES5 470-8MB11 SIMATIC S5 Two-Channel ±20 mA Analog Output Module
The Siemens 6ES5 470-8MB11 is a 470 analog output module for SIMATIC S5-100U and ET 100U, with two galvanically isolated ±20 mA current outputs. It uses a 24 V DC load supply and two-wire output connections. Siemens’ ET 200U table lists a 0.10 ms output delay and four bytes of output address space for this order number.
The module converts a digital PLC command into positive or negative analog current. A zero command produces 0 mA. The 470-8MC11 is the 4–20 mA model and produces 4 mA at the same zero code. Match the receiving device’s input range and current-signal scaling to the installed module suffix.
Where do the 24 V DC supply and current outputs connect?
In Siemens’ two-wire diagram, the load supply connects at 1 = L+ (24 V DC) and 2 = M. Channel 0 uses 4 = QI and 6 = MANA. Channel 1 uses 8 = QI and 10 = MANA. Connect each load between its own QI and MANA terminals and leave unused outputs open. Check the terminal numbers on the screw-terminal bus unit or other bus unit fitted to the station.
When troubleshooting an output, account for the receiver input resistance, wiring resistance and any series components. The 300 Ω maximum load in Siemens’ later S5-100U manual applies to the 470-8MB12 table. Verify the 8MB11 load limit against its own hardware documentation.
How are the outputs addressed in S5-100U and ET 200U?
In an S5-100U with a CPU 100, CPU 102 or CPU 103, use the installed station’s slot plan to identify the channel addresses. In ET 200U, check the configuration selected for the IM 318-B SINEC L2-DP or IM 318-B DP Standard arrangement. Siemens lists the module as 2AQ. The decimal identifier is 021 for DP Siemens or 097 for DP Standard, with four bytes of address space in either table.
Each channel uses one output word in the STEP 5 program. Siemens’ bipolar table maps −1024 to −20 mA, 0 to 0 mA and +1024 to +20 mA. The value is left-justified in the output word in two’s complement form. With the lowest four bits set to zero, the endpoints are KH C000 and KH 4000. Check whether the existing program already formats the word this way.
How do the related 470 and 464 modules differ?
The 8MB11 and 8MB12 both have two ±20 mA outputs. The ET 200U table gives delays of 0.10 ms and 0.15 ms, respectively. The 470-8MA11 and 470-8MA12 are ±10 V versions, the 470-8MC12 is 4–20 mA, and the 470-8MD11 and 470-8MD12 are 1–5 V versions. The 464-8MD11 and 464-8ME11 are analog input modules that measure field current.
Editor’s note
Photograph the suffix. The 8MB11 and 8MC11 look similar. When ordering a spare, provide the full code and the current range expected by the receiver.
Record the slot and output words. Before replacement, note both channel addresses, the PLC variables that drive them and the wire numbers at the bus unit.
Check the load supply. If the output is low, check for 24 V DC at terminals 1 and 2, then check the total resistance of the receiver and series components.
Mark each channel return. Record the two MANA terminals separately. Preserve the channel wiring shown on the diagram when fitting the replacement.
Test both polarities. Before reconnecting the field load, use a suitable test load to check each channel at zero, positive and negative commands.
OtomasyonAVM resources and PDFs
+ SIMATIC S5 analog input and output modules · S5-100U CPU 103 product and documentation page
+ OtomasyonAVM SIMATIC S5 PDF archive · Siemens ET 200 manual archive
Related topics
+ 6ES5 470-8MB12 ±20 mA · 6ES5 470-8MC11 4–20 mA · 6ES5 470-8MA11 ±10 V · 6ES5 470-8MD11 1–5 V
If you have a 6ES5 470-8MB11 to sell, send the label photo, quantity and test status to otomasyonavm@gmail.com.
Browse the S5 range
SIMATIC S5 analog modules · Siemens SIMATIC S5
Siemens and external references
+ Siemens 6ES5 470-8MB11 data sheet
+ Siemens ET 200U manual, two-wire output connection and bipolar value table, pp. 7-27–7-28
+ Siemens ET 200U manual, DP Standard address identifiers and output delays · DP Siemens address table
+ Siemens S5-100U Closed-Loop Control manual, analog module ordering table, p. 2-6