6ES5 470-7LA11
Siemens 6ES5 470-7LA11 — 8-Channel Analog Output Module
6ES5 470-7LA11 is an 8-channel analog output module providing ±10 V and 0–20 mA for S5-115U systems in the Siemens SIMATIC S5 family. The exact order number is also documented in the Siemens S5-115H manual. This S5 analog module converts PLC output commands into voltage or current signals for field equipment.
Its analog signal can provide a speed reference to a compatible variable frequency drive or a setpoint to an analog controller. Check the receiving device’s input type, configured range and reference connection together.
Signal ranges and load
The module performs digital-to-analog conversion to drive the receiving equipment’s analog input. Voltage outputs require at least 3.3 kΩ; current outputs permit a total load of up to 300 Ω.
The 0–20 mA range starts at zero current. When connecting equipment configured for 0–10 V or 4–20 mA, check its input settings and the program’s lower limit. Changing the wiring alone does not establish the correct scaling.
Supply and common reference
The external supply is 24 V DC, with an allowable range of 20–30 V DC including ripple. Check the S5 power supply and the DC power supply feeding the field outputs separately. A running CPU does not confirm that the analog supply is healthy.
The output group is galvanically isolated; all eight channels share MANA. Review the grounding arrangement and the receiving device’s reference. The individual channels do not have independent isolation from one another.
Connector and voltage sensing
A 46-pin front connector is used. Channel 0: 3 = QV0, 4 = S+0, 5 = S−0, 6 = QI0. During S5 cable and connector checks, identify the output and sensing terminals separately. Use the complete manual diagram for the remaining channels.
S+ and S− are voltage sensing terminals. For unused voltage channels and channels used only for current output, Siemens Figure 7-13 requires S+–QV and S−–MANA jumpers. Isolate the system supply before changing connections.
Programming and output checks
The specified conversion time is 1 ms; nominal output corresponds to 1024 units. In PLC programming, distinguish this scale from the raw peripheral word format. Verify I/O module addressing against the installed CPU, rack and project.
For PLC troubleshooting, compare the commanded value, the module’s measured output and the value reported by the receiver. In a drive PID application, establish that this signal path works before adjusting the control parameters.
Editor’s note
Read the LA, LB or LC suffix carefully. 6ES5 470-7LB11 provides voltage outputs; 6ES5 470-7LC11 uses 1–5 V / 4–20 mA ranges. The 470 family number alone does not identify the signal range.
When considering 6ES5 470-7LA12 or 6ES5 470-7LA13 as a replacement, compare the front connector, active channels, jumpers and program. Similar nominal ranges alone are insufficient to approve a substitution.
A single channel measurement is insufficient when assessing a used module. Record low, midpoint and high commands for every channel required by the application, including negative output in voltage mode. Understanding the S5 system helps separate a module problem from a program or installation issue.
Measure voltage between QV and MANA. For current checks, connect the meter in series with a suitable load; do not place an ammeter across a voltage output. Repeat a successful bench check with the actual receiving equipment.
Before buying, request a readable order label, connector photographs and channel test results. Describe the intended analog signal application. One unloaded reading does not establish performance with your receiver and wiring.
OtomasyonAVM resources and PDFs
+ About Siemens S5 PLC — system structure and operating context.
+ SIMATIC S5 analog modules — models and signal options.
+ Siemens S5-115 PDF archive — manuals and technical documents.
+ Same manual — voltage/current wiring and unused-channel jumpers, Figure 7-13.
Related topics
+ 6ES5 470-7LB11 — eight ±10 V voltage outputs.
+ 6ES5 470-7LC11 — 1–5 V and 4–20 mA output ranges.
+ 0–10 V and 4–20 mA — matching signal ranges.
Browse SIMATIC S5
+ Siemens second-hand equipment