6ES5 470-7LB11

Siemens SIMATIC S5 6ES5 470-7LB11 · 8 × ±10 V Analog Output Module

The Siemens 6ES5 470-7LB11 is an eight-channel ±10 V analog output module for S5-115U and S5-115H systems in the SIMATIC S5 family. The output group is galvanically isolated. All eight channels share a common MANA reference. Siemens specifies a minimum load resistance of 3.3 kΩ per channel, a 1 ms conversion time and an external 24 V DC supply.

The module converts PLC values to a voltage for an indicator or a drive reference input. In Siemens’ CPU 945 example, a 460-7LA12 input module reads the tank level and the 470-7LB11 sends 0–10 V to the indicator. This uses the positive half of the voltage range. In a PID loop, match the output range to the receiving device’s input setting.

46-pin front connector and voltage outputs

On the S5 front connector, connect the external supply across 1 (L+) and 47 (L−). The permitted range is 20–30 V DC, including ripple. The 6ES5 490-7LB21 is a 46-pin screw-terminal connector. The similarly numbered 6ES5 490-7LB11 has 24 pins.

Channel 0 uses 3 (QV0), 4 (S+0) and 5 (S−0). Channel 7 uses 43 (QV7), 44 (S+7) and 45 (S−7). The MANA terminals are 13 and 37. Connect QV and S+ to the positive side of the load, and MANA and S− to the negative side. S+ and S− sense the voltage at the load. Check the relationship between MANA and cabinet ground against the wiring diagram.

Siemens specifies two links at the front connector for each unused voltage channel. Fit QV to S+ and S− to MANA. Terminate the sense leads of active channels at the load. Record the existing links before changing the module.

STEP 5 output word and scaling

Each channel receives one word for its analog output signal. −1024, 0 and +1024 units produce −10 V, 0 V and +10 V respectively. The corresponding bit patterns for a direct output word write are C000h, 0000h and 4000h. In the Siemens S5-115H example with a 460-7LA11 input module, the program scales the analog input and output separately and uses FB 251 for the output.

7LB12 and related 470 modules

The Siemens 470-7LB12 drawing shows QV, S+, S− and MANA on the same pins. Its rated range is ±10 V, its minimum load resistance is 3.3 kΩ, and its conversion time is 1 ms. For a replacement, match the full order number, the fitted front connector and the output addresses in the program.

The 470-7LA11 and 470-7LA12 provide ±10 V / 0–20 mA. The 470-7LC11, 470-7LC12 and 470-7LC13 provide 1–5 V / 4–20 mA. Use the plant’s signal type to distinguish the 7LA, 7LB and 7LC variants when selecting a spare.

Editor’s note

Before ordering, photograph the 470-7LB11 nameplate and the front connector. The 470 module and 490 connector can have similar suffixes.

Isolate the supply before removing the connector. Mark QV, S+, S− and MANA, including the links on unused channels.

If several channels lose output together, start with the supply across terminals 1 and 47 and the MANA connections. Then check the PLC output words.

If one channel reads low under load, check the receiving input resistance against the 3.3 kΩ minimum. Confirm that S+ and S− reach the load terminals.

For a used module, ask for voltage readings on all eight channels under load with the machine in a safe test condition. Record the test load, command value and measured voltage together.

OtomasyonAVM resources and PDFs

+ SIMATIC S5 analog modules · SIMATIC S5-115U CPUs and racks

+ OtomasyonAVM SIMATIC S5 PDF archive

+ SIMATIC S5-115H system manual · 470-7LB11 terminals and specifications, pp. 17-47–17-48

Related topics

+ 6ES5 470-7LB12 · 8 × ±10 V · 6ES5 470-7LA12 · ±10 V / 0–20 mA

+ 6ES5 470-7LC12 · 1–5 V / 4–20 mA · 6ES5 490-7LB21 · 46-pin front connector

S5 navigation

+ S5-115U CPU and rack family · S5 analog modules · SIMATIC S5

External references

+ Siemens S5-115H system manual · 470-7LB11 specifications, p. 17-48

+ Siemens S5-115H system manual · 7LB wiring and unused-channel links, Figure 7-13

+ Siemens S5-115U system manual · 470-7LB12 front connector and specifications, pp. 15-54–15-55

+ Siemens S5-115U CPU 945 manual · 470-7LB11 application with 0–10 V output, p. 10-75