6ES5 752-0AA62
Siemens 6ES5 752-0AA62 — CPU 928B/948 SINEC L1 Interface Submodule
The Siemens 6ES5 752-0AA62 is a SINEC L1 interface submodule for the second interface (SI2) of the CPU 928B and CPU 948 in SIMATIC S5 systems. It uses a 20 mA current loop at a fixed 9600 bit/s, with a 15-pin female D-sub connector.
This member of the S5 interface module range fits inside the CPU’s interface receptacle. It provides the CPU’s SINEC L1 connection rather than occupying a rack slot as a separate S5 communications processor.
CPU compatibility and hardware revision
The Siemens system manual specifies CPU 928B support from 6ES5 928-3UB12 onwards. Check the complete CPU number and installed interface hardware when assessing a 928-3UB12 or 928-3UB21. The earlier 928-3UB11 must not be included solely because it carries the CPU 928B name.
The CPU 948 is also supported. For installations using a 948-3UA13 or 948-3UA23, check SI2’s existing function and program parameters. Installing the submodule does not by itself configure SINEC L1 communication.
SINEC L1 network, CP 530 and BT 777
The CPU can operate as a slave station on a SINEC L1 network through this interface. A CP 530 acts as network master; designs may use processors such as the CP 530-7LA11 or CP 530-3LA11. A BT 777 bus terminal provides the level conversion between the CPU interface and the network.
The manual also describes a point-to-point connection with one master and one slave. In this specific arrangement, the CPU can be master; the fixed station numbers are 0 for the master and 1 for the slave. A purpose-wired connecting cable can link the two devices without BT 777 terminals. This arrangement differs from a multi-station LAN connection.
Connector, cable and current loop
The receiver connections are pin 9 (+RxD) and pin 2 (−RxD); the transmitter connections are pin 6 (+TxD) and pin 7 (−TxD). Pins 11 and 13 are 20 mA current-source connections. Select the S5 cable and connector from the Siemens circuit diagram, including the required current-loop arrangement.
Check cable shielding, metal connector housings and grounding together. Do not treat this interface as electrically equivalent to RS-232, RS-422 or RS-485. A matching connector shape or pin count does not establish signal compatibility.
DX2 parameters and data exchange
SI2’s SINEC L1 parameters are assigned in DX2. Transmit and receive mailboxes are defined in DB/DX areas; the SCB send coordination byte and RCB receive coordination byte control data exchange. Their addresses and station parameters must match the application in the PLC program.
Without DX2, the second interface is initialized as a programmer port. On the CPU 928B, DX2 parameters are adopted following a cold restart. During communications troubleshooting, check DX2, mailbox definitions and the CPU-specific startup conditions before replacing the submodule.
Differences from other 752 submodules
The 752-0AA12 is a general 20 mA TTY interface, the 752-0AA23 belongs to the V.24/RS-232 range, and the 752-0AA43 provides an RS-422/RS-485 interface. Similar connectors or board layouts do not establish that these versions can replace the 0AA62’s SINEC L1 function.
The 752-0AA53 is a PG submodule for the CPU 928B/948. The 752-0LA62 is the SINEC L1 version for the CPU 945. Check both the 0AA62 versus 0LA62 suffix and the CPU family when selecting a replacement.
Editor’s note
Start with the label, then look at the connector. A clear photograph of the 752-0AA62 number alongside the complete CPU number is much more useful than a general description such as “S5 interface card”. It helps establish what the machine actually needs.
If communication has stopped, give the existing installation a fair check before condemning the card. Inspect the BT 777, connecting cable and connector contacts in turn. Compare the cable wiring with the diagram before trying a similar-looking PG or communications lead.
Photograph the jumper positions before removing the submodule. Record the CPU’s rack position, SI2 connection and original condition. Switch off power and follow the manual’s removal procedure. Keeping these details makes the replacement easier to assess later.
Include DX2 in the backup. An incorrect station number or mailbox address can prevent useful data exchange even with healthy hardware. Checking the hardware and program together usually achieves more than repeatedly changing the same component.
When buying a used card, ask for a test involving actual SINEC L1 data exchange where possible. Recognition inside a CPU alone is a limited check. Sharing the full CPU number, existing card photographs and connection arrangement at the outset helps identify a suitable replacement.
OtomasyonAVM resources and PDFs
+ About Siemens S5 PLCs · S5 interface modules · S5 communications modules
+ Siemens S5 PDF files — our manual archive. The relevant Siemens system and communications manuals are linked at the bottom of this page.
Related topics
+ BT 777 bus terminal · CP 530-7LA11 · CPU 928B 3UB12 · CPU 948
+ 752-0AA53 PG submodule · 752-0LA62 CPU 945 SINEC L1 submodule
Browse SIMATIC S5
+ S5 interface modules · S5 communications modules · S5 cables and connectors · SIMATIC S5 · Siemens second-hand equipment
Siemens and external references
+ Same manual — A-4: 6ES5 752-0AA62 ordering code
+ Siemens CPU 928B/CPU 948 Communication — Chapter 7: SINEC L1 connections, DX2, SCB and RCB