6ES5 243-1AA12

Siemens 6ES5 243-1AA12 — Fully Configured IP 243 Analog Processing Module

The Siemens 6ES5 243-1AA12 is a fully configured IP 243 analog processing module for SIMATIC S5. It includes eight analog inputs served by one 12-bit A/D converter, two 12-bit D/A converters and one 8-bit D/A converter. Within the S5 analog module range, it combines measurement, analog command generation and hardware signal processing.

The module also contains 8 digital inputs, 8 digital outputs, 4 analog conditioning circuits, 2 difference amplifiers and 2 comparators. When assessing the I/O arrangement, distinguish the analog inputs, the three D/A converters and the AO1–AO5 physical analog output paths. Internal jumpers determine how these paths are connected.

Analog input ranges and conversion speed

The A/D converter accepts ±5 V, ±10 V or 0–10 V, selected by hardware jumpers. An eight-channel multiplexer feeds the converter; conversion takes 35 µs maximum per channel. Channel selection and PLC instruction execution are additional. The analog signal range, jumper settings and program scaling must agree.

Three D/A converters and five output paths

For D/A conversion, DAC1 and DAC2 provide 12-bit-class ±10 V outputs; DAC3 provides an 8-bit 0–10 V output. DAC1/2 use 11 bits plus sign. AO1–AO5 are not five independent D/A converters. Jumpers can route converter signals, difference-amplifier outputs or conditioned analog signals to these paths.

The X29 and X32 soldering bases establish the internal analog connections. Full configuration includes four conditioning circuits, two difference amplifiers for P-control functions and two comparators. As with other S5 function modules, matching the order number is only part of the replacement: application-specific jumpers and adjustments must also match.

Digital channels, supply and connections

The eight digital inputs accept nominal 24 V DC signals. The eight digital outputs are described for driving indicator elements, with limits of 200 mA per channel and 600 mA total. Do not assume short-circuit-proof operation or automatically apply the BASP behaviour of standard S5 output modules.

The external supply is 24 V DC, with a permitted range of 20–30 V DC. Field wiring uses a 43-way front connector. Check the S5 cables and connectors, analog common reference and grounding arrangement together: the analog and digital circuits are not galvanically isolated. Maximum shielded analog cable length is 20 m.

FB 160 / FB 161 and addressing

FB 160 (PER:ANL) reads the analog module; FB 161 (PER:ANS) writes it. Use the CPU-appropriate block version in the PLC program. During troubleshooting, check the selected ADC channel, range setting and internal signal routing alongside the block call.

The module occupies an 8-byte address area. Relative to the base address, DAC1 is at +0, DAC2 at +2 and DAC3 at +4. Write DAC1/2 as words; a byte write is sufficient for DAC3. ADC channel selection uses +7, while conversion triggering and result access use +6. These offsets are not front connector pin numbers.

System compatibility and IP 243 variants

The IP 243 family is used in S5-115U/H, S5-135U and S5-155U/H systems with a suitable rack and slot arrangement. S5-115U installation requires an adapter casing. Check the manual’s slot table for interrupt-line availability and expansion-unit conditions as well as the CPU family.

The 6ES5 243-1AA11 and 6ES5 243-1AA13 are other fully configured versions. Compare the 1AA12 suffix, hardware release and existing routing with the replacement. An IP 243 label does not establish that its application settings are ready to use.

The 243-1AB11 and 243-1AB12 belong to the partial-configuration group without D/A converters. The 243-1AC11 is the version without an A/D converter. These partial versions do not provide every function of the fully configured 1AA12.

Editor’s note

The label is a useful starting point, but ask for close-up photographs of X29/X32 and the adjustment components when buying a used analog module. A card prepared for a previous machine can behave differently in your installation even when its order number matches.

If there is no output, check which DAC the program writes to, then follow that signal to the physical AO terminal. The software channel and the external terminal are different things. Establishing that link often makes the fault much easier to find.

Leave the trimmers alone until their present settings have been recorded. Start with a known reference voltage and take measurements. An altered offset or gain can make a healthy ADC appear to read incorrectly.

Give DAC3 particular attention: it is not preset to a defined value at power-up and can hold an arbitrary value until the program writes it. Set the initial command in the program and measure it before connecting the load. Also verify the correct route through the DAC3 output buffer.

Record the wiring, jumpers, address setting and program before removal. Check a replacement with a known input first, then test the outputs one at a time. Keeping each change separate makes the result easier to interpret; a steady, step-by-step check saves time here.

OtomasyonAVM resources and PDFs

+ About Siemens S5 PLCs and S5 analog modules — our system overview and analog module pages.

+ Siemens S5 PDF files — our manual archive. The IP 243 family manual’s hardware, jumper-routing and FB 160/FB 161 sections are linked in the Siemens references below.

Related topics

+ 243-1AA11 and 243-1AA13 — other fully configured IP 243 versions.

+ 243-1AB12 and 243-1AC11 — partial versions with different hardware coverage.

Browse SIMATIC S5

+ S5 analog modules · S5 function modules · SIMATIC S5 · Siemens second-hand equipment

Siemens and external references

+ Siemens IP 243 Equipment Manual, English — 2-2: full 1AA and partial 1AB/1AC hardware comparison

+ Same manual — 3-3–3-9: input ranges, ADC, DAC1/2/3 and physical analog outputs

+ Same manual — Chapter 5: front connector, X29/X32 jumpers and address setting

+ Same manual — Chapter 6: supply, digital channels, analog specifications and permitted slots

+ Same manual — Chapter 7: FB 160 / FB 161 and direct peripheral access