6ES5 243-1AA13

Siemens 6ES5 243-1AA13 – IP 243-3 Fully Equipped Analog Module

6ES5 243-1AA13 is the fully equipped IP 243-3 analog processing module in the Siemens SIMATIC S5 family. Used in S5-135U and S5-155U/H systems, it combines an eight-channel 12-bit A/D converter, two 12-bit and one 8-bit D/A converters, eight digital inputs and eight digital outputs. Within the S5 analog module range, its A/D conversion time is 35 µs maximum per channel.

The IP 243-3 acquires, preprocesses, compares and routes analog signals. The relationship between each analog input and the output functions depends on both the soldered routing connections on the board and the application program.

Reading the eight analog inputs

Jumpers select ±5 V, ±10 V or 0–10 V voltage input ranges; input resistance is approximately 1 MΩ. For 0–10 V output sensors, check the range and common reference. A multiplexer selects the eight channels sequentially: 35 µs is one conversion time and excludes channel-selection and command-processing time.

Understanding the analog outputs

The analog I/O arrangement includes two 12-bit, ±10 V D/A converters and one 8-bit, 0–10 V D/A converter. A separate analog output amplifier is used according to the routing configuration. D/A outputs require a load resistance of at least 2 kΩ; confirm the receiving device’s voltage or current interface before connection.

Signal conditioning and comparison

The module includes four analog conditioning circuits, two difference amplifiers and two comparators. Conditioning gain is 0.5–5 with a −2 to +2 V zero-offset range; difference-amplifier gain is 1.1–20. The board’s routing connections determine how these functions connect to the inputs and outputs.

Digital inputs and outputs

Eight digital inputs and eight digital outputs operate at 24 V DC. Keep the roles of analog and digital inputs separate during diagnosis. Check output loading and protection requirements in the manual. For comparator interrupts, review the CPU, rack and interrupt wiring of the PLC system together.

Addressing, conversion commands and FB 160/161

The IP 243 occupies an 8-byte address area. For direct access, write the channel selection at base address +7, start conversion by writing at +6, then read the result from the peripheral word at +6. Preserve the LOG and STROBE bits when writing the channel-selection byte.

FB 160 (PER:ANL) reads analog/digital inputs and comparator states; FB 161 (PER:ANS) writes analog/digital outputs. Match the CPU-specific block version, base address, channel selection and normalization settings to the existing application.

Supply, connector and common reference

The external supply is 24 V DC, with a permissible range of 20–30 V DC. The catalog lists 600 mA from the internal 5 V supply and 270 mA from the external 24 V supply at no load. There is no galvanic isolation. Check grounding, common references, the S5 system rack and the 43-contact K front connector.

1AA, 1AB and 1AC versions

6ES5 243-1AA11 and 6ES5 243-1AA12 are other versions in the fully equipped 1AA group. Before selecting a replacement for 1AA13, compare the full code, hardware version, routing configuration and program requirements.

6ES5 243-1AB12 is a partially equipped type without D/A converters; 6ES5 243-1AC11 is a partially equipped type without an A/D converter. The IP 243 family name alone does not establish suitability as a replacement for the fully equipped module.

When considering analog input cards such as 6ES5 460-4UA11 or 6ES5 465-4UA11, account separately for the IP 243’s routing, comparator and output functions. Matching signal ranges do not establish matching functionality.

For a used analog module, request photographs of its routing connections, input/output test results and connector condition. Independently measure the signal from any analog output sensor used during testing to establish a reliable reference.

Editor’s note

Start by identifying the board. Confirm the 1AA13 label, then photograph the old module’s front, rear and routing connections. A few clear pictures can save a great deal of uncertainty during replacement.

Leave the soldered links alone until their purpose is clear. The module may have been configured for a different machine. A working IP 243 can still behave unexpectedly when its routing does not match your application.

Check the basics before reaching for a trimpot. Verify the reference voltage, selected range and program scaling first. Record existing adjustments before changing them; otherwise a straightforward diagnosis can become much harder.

A fast converter still needs the right access sequence. Starting conversion before selecting the channel, or changing LOG/STROBE unintentionally, can look like a hardware fault. Follow the program accesses carefully before condemning the board.

Test the outputs as carefully as the inputs. One correct measurement does not establish that the whole module is sound. Check D/A outputs with suitable loads, then test the comparator and digital functions actually used by the machine.

OtomasyonAVM resources and PDFs

+ About Siemens S5 PLCs – system and maintenance information

+ SIMATIC S5 analog modules

+ Shared S5 PDF archive – manuals and files page

Related topics

+ How analog inputs and outputs work

+ Analog voltage signals

+ Grounding and common references

Browse SIMATIC S5

+ S5 analog modules

+ SIMATIC S5 system pages

+ Siemens S5 PLC main page

+ Used Siemens products and model pages

Siemens and external references

+ Siemens IP 243, 6ES5 998-0KF21 – full/partial configurations and functions (English)

+ Siemens IP 243 – FB 160/FB 161 and direct addressing, section 7 (English)

+ Siemens ST 50, 1998 – exact 6ES5 243-1AA13 order code, IP 243-3, pages 4/59–4/60 (English)