6ES5 470-8MC12
Siemens 6ES5 470-8MC12 SIMATIC S5 Analog Output Module, 2 × 4–20 mA
The Siemens 6ES5 470-8MC12 is a 470-series analog output module for S5-90U, S5-95U, S5-100U, ET 100U and ET 200U in the SIMATIC S5 family. Both channels output 4–20 mA and are galvanically isolated from each other and from ground. The maximum resistive load is 300 Ω per channel, and the nominal external supply is 24 V DC.
The module sends a setpoint to a valve positioner, a drive’s current input or another control device. The lower end of the PLC command corresponds to 4 mA and the upper end to 20 mA. The related 470-8MB12 outputs ±20 mA. When choosing a spare, check the signal range and program scaling along with the channel count.
Which S5 systems support it?
Siemens documents local use with S5-90U, S5-95U and S5-100U. For an S5-100U installation with a CPU 100, CPU 102 or CPU 103, check the module slot and output address in the system manual. The Siemens ST 50 catalog also lists the 8MC12 for S5-95F.
For distributed I/O with interfaces such as the ET 100U IM 318 or ET 200U IM 318-B, check the station configuration. In the ET 200U table, the module occupies two output words, four bytes in total. The manual identifies it as 2AQ, with numeric code 021 for DP Siemens or 097 for DP Standard.
How are the supply and current outputs wired?
The Siemens wiring diagram shows the supply on terminals 1 (L+) and 2 (M). Connect the two-wire load for channel 0 to 4 (QI) and 6 (MANA), and the load for channel 1 to 8 (QI) and 10 (MANA). Check the terminal type against the base unit order number. The 700-8MA11 screw-terminal base, 700-8MA22 crimp-terminal base and 700-8FA11 bus unit have separate order numbers.
The external supply range is 20–30 V DC, including ripple. The receiver input and any series elements must stay within the 300 Ω resistive load limit for each channel. The ET 200U manual specifies a capacitive load below 100 nF, including the cable. Allow for the PLC scan and any station communication time separately from the module’s 0.15 ms conversion time.
How does STEP 5 represent 4, 12 and 20 mA?
The module uses left-justified two’s complement. Within the nominal range, 0, 512 and 1024 measurement units correspond to 4, 12 and 20 mA, respectively. With the four low bits set to zero, the corresponding output words are 0000h, 2000h and 4000h. When tracing the scaling block, distinguish its measurement units from the encoded output word.
How do the related order numbers differ?
The 470-8MC11 also has two 4–20 mA outputs. The ET 200U table specifies 0.10 ms for the 8MC11 and 0.15 ms for the 8MC12. Voltage-output models include the 470-8MA12 at ±10 V and the 470-8MD12 at 1–5 V.
For process feedback, the 464-8ME11 4–20 mA analog input is a separate module. The 477-8EC11 Ex analog output and the 470-4UA12 eight-channel analog output have their own system and wiring requirements.
Editor’s note
Before removal, record the 8MC12 suffix, the base unit order number and the station slot. Check the station table if an 8MC11 is being considered as a spare.
If neither output responds, start with the external 24 V DC supply at terminals 1 and 2 and the two output words in the PLC.
If a channel falls short of 20 mA, check the receiver input, series components and cable together. A loop isolator or display added later can increase the total load.
Trace each channel return separately against the diagram. Check for links between the MANA terminals and confirm the cable goes to the intended channel.
With the machine in a safe test state, compare the PLC command and actual receiver reading at 4, 12 and 20 mA.
OtomasyonAVM resources and PDFs
See the Siemens SIMATIC S5 PLC overview and the S5 analog module catalog.
Browse the OtomasyonAVM SIMATIC S5 PDF archive and the Siemens ET 200 manuals directory. The ET 200U manual covering this module is listed in the Siemens references below.
Related topics
Compare the 470-8MC11 with the same signal range, the 470-8MB12 bipolar current output and the 470-8MD12 1–5 V output.
Browse the S5 range
Siemens SIMATIC S5 › S5 analog modules
To sell a Siemens S5 module, email the full order number, quantity, working condition, label photo and asking price to otomasyonavm@gmail.com.
External Siemens references
+ Siemens 6ES5 470-8MC12 data sheet
+ SIMATIC S5-100U system manual, wiring and STEP 5 output value table
+ SIMATIC ET 100U manual, 470-8MC12 wiring and specifications
+ SIMATIC ET 200U manual, 470-8MC12 specifications and address ID