Delta DVP12SC11T PLC – DVP-SC CPU with High-Speed Counting and Pulse Outputs

The Delta DVP12SC11T is a 24 V DC PLC CPU in the Delta DVP-SC series. It has 8 digital inputs, 4 NPN transistor outputs and 7,920 program steps. X10 and X11 support high-speed counting, and Y10 and Y11 can be assigned to positioning. Typical uses include measuring length with an encoder, counting parts and commanding a pulse-input drive.

Encoder inputs and counting limits

The CPU accepts 20.4–28.8 V DC and consumes up to 4 W. Its inputs are X0–X5 and X10–X11. Wire the S/S common to match the 24 V DC sensor output. When selecting an incremental encoder, check its supply and output signal type. Choose an input interface suitable for the PNP or NPN sensor wiring or the differential encoder output.

C243 on X10 and C245 on X11 can count single-phase signals at up to 100 kHz per input. Delta specifies a 130 kHz combined high-speed counting bandwidth for X10 and X11. The limit for C255 using A/B two-phase counting is 35 kHz. To check an encoder, calculate per-phase frequency as PPR × rpm ÷ 60 and verify the selected counter mode. See PLC high-speed counters for the counting principles.

Pulse outputs and positioning

Y0 and Y1 are general-purpose outputs. Y10 and Y11 are the high-speed pulse outputs, with up to 100 kHz on one channel under suitable conditions. For two-axis synchronous pulses with firmware V1.2 and V1.4, Delta specifies a 60 kHz maximum on Y10 and a 40 kHz maximum on Y11, with Y11 running below Y10. The output commons are C0, C1, C2 and C3, respectively. Check the drive input circuit and high-speed output load rating before testing.

The SC programming manual uses DDRVI for relative positioning, DDRVA for absolute positioning and DZRN for homing. For a servo or stepper motor drive, match the instruction’s output assignments to the drive’s pulse mode. See PLC high-speed pulse outputs for the signal selection principles.

Programming software and cable

Use WPLSoft or a version of ISPSoft that supports the SC target, and select SC as the CPU type. The programming connection uses COM1 RS-232. Delta lists the DVPACAB2A30 cable with a PC-side DB9 and a PLC-side 8-pin mini-DIN. The instruction sheet also lists the DVPACAB230. For a USB-equipped PC, use a suitable USB-to-RS-232 adapter and select its Windows COM port in WPLSoft or in COMMGR for ISPSoft.

COM2 RS-485 supports Modbus serial communications with field devices. Record the actual station address, baud rate, parity and ASCII/RTU mode when maintaining an existing machine. See Delta DVP programming cables and the range of compatible DVP expansion modules for connection and I/O options.

Editor’s Note

Before buying a used unit, check the DVP12SC11T label, firmware revision, COM1 socket and power terminals.

Back up the program, retained registers and communications settings before removing the CPU or servicing its battery. Follow the SC instruction sheet for battery service.

Use a suitable signal source of known frequency to test X10 and X11. In A/B mode, reverse the encoder and verify that the count reverses too.

Check the fast outputs with an oscilloscope while drive motion is disabled. Test one channel first, then test Y10 and Y11 together if the machine uses both.

Before changing CPU models, compare the X10/X11 and Y10/Y11 assignments, counter instructions and drive interface against the existing project.