Delta DVP201LC-SL

Delta DVP201LC-SL Single-Channel Load Cell Weighing Module

The Delta DVP201LC-SL is a single-channel load cell module that mounts on the left side of a compatible Delta DVP PLC CPU. It reads four- or six-wire strain-gauge load cells for hopper weighing, batching and filling. Weight measurement depends on the sensor capacity, mounting and calibration of the whole assembly.

Power supply, measurement and wiring

The module requires an external 24 V DC supply (20.4–28.8 V DC). Sensor excitation is 5 V DC, and the analog input range is ±200 mV DC. A 24-bit ADC acquires the signal and the PLC reads a 32-bit weight value. Select a response time from 2.5 to 400 ms. The factory setting is 50 ms. Filter settings and mechanical vibration also affect settling time.

EXC+/EXC− supply excitation, SIG+/SIG− carry the measurement signal and SEN+/SEN− sense the excitation voltage. For a four-wire sensor, link SEN+ to EXC+ and SEN− to EXC− at the module terminals, as shown in Delta’s diagram. Connect the separate sense leads on six-wire sensors. Terminate the shield at SHD and follow the manufacturer’s grounding diagram. Keep the signal cable away from power wiring in the control panel. Check lead functions on the sensor datasheet when wiring the low-level strain gauge signal.

PLC programming, LCSoft and registers

For compatible left-expansion CPUs such as the DVP-SA2 and DVP-SX2, write the PLC program in WPLSoft or in ISPSoft with CPU support. ISPSoft uses COMMGR. The UC-PRG020-12A cable can be used on compatible CPUs with an 8-pin mini-DIN RS‑232 port. To monitor or calibrate the module directly with LCSoft, connect to module RS‑232 COM1 using a serial cable that matches Delta’s pinout. Use a suitable USB-to-RS‑232 adapter if the PC has no serial port. For standalone communications, the module supports ASCII or RTU over RS‑485 Modbus.

The closest left-side special module to the CPU is K100. CR#0 returns model code H5106. CR#2 configures sensor sensitivity, and CR#3 selects response time. Use FROM to read CR#12 (low word) and CR#13 (high word) together as the 32-bit CH1 weight. Use TO to write parameters. CR#6 handles zero and tare commands, and CR#7 selects gross or net weight.

Calibration and filling

Select the sensor capacity and load cell type for the application. Capture zero on the empty platform and a second point with a known reference weight. Delta’s example scales 1 kg to 1000. CR#25–27 control the calibration steps, and CR#33–34 hold the CH1 reference value. Once verified, write H5678 to CR#41 to save the settings to the module. Changing the units or decimal places displayed in LCSoft leaves the PLC’s raw value unchanged.

For production-line weighing, slow the fill as it approaches the target and take the final weight reading once the reading stabilises. Display net and gross weight separately on the HMI. Record the batch weight and measurement status together in SCADA or your production data system. Standalone weight controllers are also available for single weighing stations.

Related models

See the DVP202LC-SL for two weighing channels, or the DVP211LC-SL for one channel with analog output and local digital I/O. The earlier single-channel DVP01LC-SL and dual-channel DVP02LC-SL use 20-bit ADCs. Compare channel count, wiring and register maps before replacing a module.

Editor’s Note

When buying used, ask for photos of the full label, left-side bus connector and sensor terminals.

On a four-wire cell, check the SEN links early. A loose link can make the reading unstable.

Test with a known good load cell at zero, with a reference load, and at zero again. Check that the reading returns when the weight is lifted.

If the reading moves during filling, check the platform for friction and cable drag before increasing the filter setting.

Back up the old settings before swapping the module. Repeat the zero and reference-weight checks on the machine’s own platform after installation.

PDFs and technical documents

Related document index Delta DVP PLC files. In Delta’s 2026 module manual, see PDF page 286 for specifications, 301 onward for control registers, 313 for wiring and 328–332 for calibration. The 2023 instruction sheet includes wiring information in English and Turkish.

DVP201LC-SL main page · DVP Slim load cell modules · DVP expansion modules · DVP PLC series · Delta PLC · Used Delta models · Delta PLC and HMI manuals

Delta AS PLC · Delta AH PLC · Delta TP panels and remote I/O

External references

Delta DVP Series Module Manual (2026) · Delta DVP201/202/211LC-SL Operation Manual (2019) · Delta Load Cell Module Instruction Sheet (2023, TR/EN)