Delta DVP16SP11TS

Delta DVP16SP11TS is a DVP-S expansion module that adds 8 digital inputs and 8 PNP transistor outputs to a compatible DVP Slim PLC CPU. X0–X7 read 24 V DC field signals. Y0–Y7 are sourcing outputs that supply the positive side of the load. DVP16SP11T has the same point count with NPN outputs, while DVP16SP11R has relay outputs.

Inputs, outputs and power

Inputs. X0–X7 can work in sink or source configurations through the shared S/S terminal. Connect S/S to 0 V for PNP sensors or to +24 V for NPN sensors. Select the common reference for the sensor group. Delta lists an ON threshold above 16.5 V, an OFF threshold below 8 V and a response time of approximately 10 ms.

Outputs. Y0–Y7 are PNP outputs rated for 5–30 V DC. For resistive loads the manual specifies 0.3 A per point and 2 A per common. Eight channels at 0.3 A simultaneously would total 2.4 A and exceed the common limit. Electronic response is approximately 15 µs ON and 25 µs OFF. Program-controlled switching also depends on the PLC scan.

Power. The host expansion bus powers the module electronics. The output stage needs an external 24 V DC supply (−15%/+20%). Connect UP to +24 V and ZP to 0 V. Wire each load between its Y terminal and 0 V. The maximum 15 mA auxiliary consumption listed by Delta is separate from the field load current. Size the DIN rail power supply for the loads as well. The module has removable terminals, fits a 35 mm DIN rail and weighs approximately 74 g.

Sensor selection and output loads

Use an inductive sensor to detect a metal machine part, or a photoelectric sensor to detect packages on a conveyor. Consider a through-beam sensor if both sides are accessible, or a retroreflective sensor when you need wiring on one side. Once the detection method is selected, check PNP versus NPN and the sink/source wiring. If the machine needs a continuous distance reading, use the analog versus digital input distinction to select the module.

Check both the running current and any inrush current of a DC valve or relay coil. For a contactor with an incompatible coil voltage or current rating, use a suitable interface relay. Choose the suppression device recommended for the DC coil. Before using a diode, for example, check its polarity and its effect on valve release time. Protect the output feed with a suitable fuse and route field wiring away from motor cables inside the control panel.

X/Y addressing, software and programming cable

The local X0–X7 and Y0–Y7 terminals receive addresses in the host PLC program according to expansion order. If the CPU uses the X0–X7 and Y0–Y7 blocks and DVP16SP11TS is the first digital expansion, the example ranges are X10–X17 and Y10–Y17. DVP addressing is octal. The module uses standard X/Y bits. Verify the actual addresses online before assigning HMI and SCADA tags.

Open the host project in WPLSoft or a CPU-compatible release of ISPSoft. For ISPSoft, check the COMMGR settings. Connect the programming cable to the CPU. For a suitable 8-pin mini-DIN RS-232 host port, Delta lists UC-PRG020-12A. If the PC has no serial port, verify the driver and COM number for a suitable USB–RS-232 adapter. The host CPU runs the automation logic.

Related modules

For fewer points, DVP08SP11TS provides 4 inputs and 4 PNP outputs. Output-only models include DVP08SN11TS with PNP outputs, DVP08SN11T with NPN outputs, and DVP08SN11R and DVP06SN11R with relays. For reading sensors or adding inputs only, see DVP08SM11N, DVP16SM11N and DVP32SM11N. DVP08SM10N is an AC-input model and DVP08ST11N uses DIP switches.

Editor’s Note

Start with the full label. The TS suffix identifies the PNP output version. Check the existing load return before replacing a T module with a TS.

If the Y LED is on but the load stays off, measure UP to ZP under load. Then check the Y terminal and the load’s 0 V return.

If several sensors stop responding together, check their S/S common and 24 V field supply. If the input LED responds but the program bit stays fixed, monitor the actual X address.

After output damage, check the coil, wiring for shorts and suppression device before fitting a replacement. Start with a suitable 24 V test load disconnected from the machine.

For a used unit, ask for label and terminal photos. Test all eight inputs and eight outputs with a compatible CPU. Check the voltage under load as well as the output LED.

PDF manuals and technical documents

See the Delta DVP PLC files page and open section 7.4.17 of the DVP Series Module Manual. In the 6 January 2026 edition, the wiring diagram is on PDF page 145, printed page 7-21. The electrical ratings are on PDF pages 126–127.