Delta DVP-F422
Delta DVP-F422 – RS-422 serial communication function card
Delta DVP-F422 provides four-wire RS-422 serial communication for DVP-EH2 and DVP-EH3 CPUs. It connects a supported operator panel or serial peripheral. The PLC port number depends on the CPU generation. See DVP function cards and DVP expansion modules for related hardware.
Port assignment on EH2 and EH3
On EH2, the DVP-F422 takes over COM2 as RS-422. Inserting it disables the CPU’s built-in COM2 RS-485 function. If an existing drive or device network uses COM2, account for that connection before fitting the card.
On EH3, the card operates as COM3. Delta documents master and slave operation on that CPU. Check the PLC port selection in the HMI project and the communication configuration in the PLC program. Verify compatibility against the full host CPU model code.
RS-422 terminals and the DOP-A connection
The card terminals are marked TX+, TX−, RX+, RX− and GND. Connect the transmit pair to the other device’s receive pair and the receive pair to its transmit pair. Keep + and − polarity consistent within each pair. Follow both devices’ diagrams for the GND connection.
In Delta’s DOP-A COM2, MODE 2 (RS-422) example, the card connects to the panel’s DB9 as follows. TX+ → pin 2, TX− → pin 1, RX+ → pin 3, RX− → pin 4. This pinout applies to the illustrated DOP-A port. Use the specific diagram for other panels. Related pages include DOP-A, DOP-B and DVP communication cables.
Programming software and cable
The program is downloaded to the host CPU. Use a version of WPLSoft or ISPSoft that supports the EH2/EH3 CPU. In ISPSoft, configure the connection profile through COMMGR. The host’s COM1 RS-232 port can be used for a PC backup connection. Select the UC-PRG020-12A USB-to-RS-232 cable and its driver according to the CPU’s connection diagram. See DVP programming cables for other options.
Match the protocol, baud rate, data bits, parity and stop bits on the HMI and PLC. Check the station address if the selected driver uses one. RS-422 defines the electrical interface. The device projects determine the communication protocol.
Related topics
Compare DVP-F232 for RS-232, DVP-F485 for RS-485 and DVP-FEN01 for Ethernet. The same card group also includes analog and motion options described on the DVP-F2AD, DVP-F2DA and DVP-FPMC pages.
Editor’s Note
When buying a used card, ask for a photo showing the full model code and terminal block. Damaged locks, bent connector pins and corroded terminals can cause intermittent faults.
On a working EH2 installation, record the devices on the built-in COM2 port and back up the PLC program before fitting the card. If RS-485 stops after installation, check the port reassignment first.
Isolate power and handle the card with static protection. Begin with a short cable you know works and a single panel.
If the connection times out, check the port number, panel mode and TX/RX pairs first. Reversing either pair can stop communication even with matching settings.
Start by reading a known PLC address from the HMI. Once reads are stable, test a write to a safe test address if the application allows it.