Delta DOP-A
Delta DOP-A is a legacy touchscreen operator-panel family programmed with Screen Editor / ScrEdit. Its displays include blue STN, grey FSTN, colour STN and TFT. Standard 5.7-inch models and the A80THTD1/A10THTD1 do not have identical serial-channel and USB hardware. Record the complete code, including W and the final 1, together with the project and rear connections.
Do not assign DOP-AE expansion support to DOP-A. Ethernet, digital I/O and printer modules listed for AE are not established as compatible with A by similar housings or software. DOP-AS is also a separate hardware group.
5.7-inch models and white housings
DOP-A57BSTD: 5.7-inch STN, eight shades of blue, 320 × 240 pixels. The nominal cutout is 172.4 × 132.4 mm and the overall dimensions are 184.1 × 144.1 × 47 mm. It uses CCFL backlighting and is not a colour TFT.
DOP-A57GSTD: 5.7-inch FSTN, 16 grey shades, 320 × 240 pixels, with a 172.4 × 132.4 mm cutout. Its grey FSTN display differs from the BSTD blue STN and CSTD colour STN.
DOP-A57CSTD: 5.7-inch colour STN, 256 colours, 320 × 240 pixels; 172.4 × 132.4 mm cutout. Backlighting is CCFL. Do not describe it as a 65,536-colour TFT; check palette and alarm readability during migration.
DOP-A57BSTD-W, DOP-A57GSTD-W and DOP-A57CSTD-W are the corresponding white-case variants. The catalogue identifies the unsuffixed case as grey. W does not specify Ethernet or a communication option. Do not generate W codes for other screen sizes by analogy.
The 5.7-inch DOP-A group has four user-defined keys and one system key. The 2008 catalogue specifies 4 MB Flash: 1 MB system / 3 MB user, 16 MB SDRAM and 256 KB backup memory for A. Do not copy the AE column’s 512 KB rating to A57.
8-inch and 10.4-inch TFT models
DOP-A80THTD1: 8-inch TFT, 65,536 colours, 640 × 480. HQ10 specifies a 231.4 × 166.4 mm cutout, 243.1 × 178.1 × 52.4 mm overall dimensions, six user keys + one system key and 14 W panel consumption. USB Host and Client 1.1 are provided; this A model supports three serial channels.
DOP-A10THTD1: 10.4-inch TFT, 65,536 colours, 640 × 480. HQ10 gives a 285.2 × 210.2 mm cutout, 297.1 × 222.1 × 51.1 mm overall dimensions, seven user keys + one system key and 15 W panel consumption. It has USB Host/Client and three serial channels. Keep the final 1 in the code.
HQ10 lists 8 MB total Flash: 2 MB system / 6 MB user, 32 MB SDRAM and 512 KB backup memory for these two models. The 2008 catalogue instead divides Flash into 1 MB system / 7 MB user; its A10 backup-memory entry also differs. Check the document issue and hardware revision before promising usable memory. These TFT panels also use CCFL backlighting.
Additional historical model records
DOP-A75CSTD: the early DOP-A specification lists a 7.5-inch, 256-colour STN, 640 × 480 display. The April 2007 ScrEdit manual lists the exact code with six user-defined keys. Do not transfer the A80THTD1 TFT, cutout, USB or three-channel specification to this older code; use its own drawing and label for replacement.
DOP-A10TCTD: the 2007 ScrEdit table specifies a 10.4-inch TFT, 256 colours, 640 × 480. It lists seven user keys; drawing A-9 gives a 285.2 × 210.2 mm cutout. TCTD and THTD1 are different display/revision codes. Do not copy the later A10THTD1 colour depth, USB Host and COM scope to TCTD.
DOP-A80THTD also appears, without the final 1, as an 8-inch standard model in Delta’s May 2008 Hannover bulletin. This spelling has not been normalised to A80THTD1. The bulletin alone does not establish complete hardware or firmware equivalence. The reviewed documents provide eight main codes and three additional historical code records; their issue dates are not the whole family’s production start or end dates.
Two serial channels versus three
Standard A57 models have COM1 RS-232 and COM2 RS-232/RS-422/RS-485. The two-channel scope follows the standard A connection table. A COM3 row in a combined A/AE catalogue column does not establish a third channel on every A57.
HQ10 separately covers COM1 and shared COM2/COM3 for A80THTD1 and A10THTD1. COM1 is RS-232; COM2/3 have RS-232, RS-422 or RS-485 modes. Three channels do not mean three independent DB9 connectors. Pin functions depend on the selected single/dual-channel mode.
For these two larger models, the HQ10 dual RS-232 table assigns COM2: pin 2 RXD, pin 3 TXD; COM3: pin 7 TXD, pin 8 RXD; pin 5 GND. In single-channel mode, pins 7/8 serve RTS/CTS. This arrangement cannot add an independent channel to standard A57 COM2. Check connector orientation, mode, PLC driver, speed, parity and address when selecting programming and HMC cables and communication accessories.
Screen Editor, transfers and storage media
The 2007 manufacturer manual and HQ10 identify the Screen Editor / ScrEdit 1.05 generation. Record the installed editor, project target and panel OS/firmware. Installing current DOPSoft or DIAScreen does not itself establish download support for old DOP-A hardware. Source projects, uploaded panel backups and recipe/data backups are distinct items.
USB Client supports PC transfers; USB Host serves supported storage/printer functions. Do not assign the larger models’ Host hardware to all A57 panels. The 2008 catalogue marks SM cards in the 5.7-inch group; HQ10 marks SM and expansion support for AE in the larger-model table. SM is not SD/SDHC; inspect the actual slot and revision.
Delta Türkiye’s historical DOP-A transfer reply identifies the USB Commode setting under System/Setting and firmware as relevant to USB access; RS-232 transfers require the panel to wait on the correct Download Port. This 2018 service reply does not guarantee current Windows compatibility. Use the official Delta download centre and manufacturer support; test conversion on a project copy.
Power, mounting and expansion limits
The reviewed English documents specify 24 V DC, −10% / +15%, or 21.6–27.6 V DC. The A80/A10 14/15 W figures in HQ10 cover the panel only. Include peripherals and cable voltage drop when choosing shared HMI power supplies. Do not apply a higher upper tolerance from the older Russian translation to every model.
Nominal cutouts are not bezel dimensions. Use the model drawing’s tolerances, panel thickness, gasket and rear terminal/cable clearance when reviewing mounting and power connections. The documented 0–50 °C operating range and IP65/NEMA4 front-face protection do not make rear connectors waterproof. Back up the project and required data before servicing the CR2032 3 V battery.
AE products under Ethernet expansion modules, digital I/O expansion and HMI modules and accessories are not generic adapters for missing DOP-A ports. Remote I/O modules also require the appropriate controller/network structure. Establish compatibility from the exact model’s manufacturer instruction.
Editor’s note
Start with a complete label photograph and a working-project backup. Keep A and AE, TCTD and THTD1, and the white-case W suffix distinct. Do not complete a model number from appearance.
Separate power, contrast, CCFL lamp and backlight-driver faults on a dim screen. TFT does not mean LED backlighting. CCFL circuits carry high voltage; isolate power and use suitable service methods.
Establish whether the unit has two or three COM channels. Do not wire standard A57 pins 7/8 using the larger model’s dual-channel diagram. Check the cable without power; a matching DB9 connector does not establish matching pin functions.
Test the touchscreen corners as well as the centre, every physical user key and SYS. Check alarm and state readability when moving a colour project to blue or grey displays.
Have a recovery path before battery or firmware service. Confirm which editor opens the project, where recipes reside and how to restore them. Test USB Host, Client and SM-card roles separately.
A used panel powering up on a bench is only part of the test. Check the used serial channel, PLC addressing, recipes and alarms under controlled conditions. Compare cutouts and macro behaviour during migration.
Related HMI families and documents
Review screens, cables and projects together when moving to DOP-B, DOP-W or DOP-100. DOP-H07 and DOP-107H are handheld HMIs; HMC07 and HMC08 are separate platforms with motion-control functions.
TP text panels, TP04P and TP70P have their own software and control structures. Select HMI starter kits by the exact panel and required connections.
Use Delta HMI PDF files and Delta PLC and HMI manuals to select documents. Return to Delta HMI families or browse available used Delta products.
Manufacturer documents and external references
The 2008 DOP/TP catalogue covers displays/memory on PDF p.10 and case codes on p.14. The 30 April 2007 ScrEdit manual provides key counts on p.70, specifications on pp.294–297 and drawings on pp.299–302. The early DOP-A technical manual also identifies the A75CSTD display; download availability for this older file may vary.
The 12 July 2010 HQ10 guide — includes Turkish separates COM arrangements on PDF p.7 and specifies A80THTD1/A10THTD1 on pp.13–14. The 2007 connection manual provides the standard DOP-A table on p.1. These are third-party-hosted manufacturer documents.
Delta’s May 2008 HMI bulletin confirms the A80THTD spelling; Delta Türkiye’s DOP-A transfer reply addresses older firmware/transfer differences. Historical documents are not current software-support commitments for every hardware revision.