Delta DVP24XP200R

Delta DVP24XP200R – 16 Digital Inputs and 8 Relay Outputs

Delta DVP24XP200R is a mixed digital expansion module for DVP-ES2 and DVP-EX2 systems. It has a 100–240 V AC supply, 16 digital inputs and 8 relay outputs, providing 24 I/O points. The host PLC executes the application program and controls the module through the expansion connection.

Typical applications include collecting limit switch, inductive sensor and photoelectric sensor signals while switching suitable loads through relay contacts. See Delta DVP ES2/EX2 modules for the product family and Delta DVP PLC files for document selection.

Power supply and specifications

Module supply: 100–240 V AC, 50/60 Hz, connected to L and N. The instruction sheet specifies 20 VA consumption and a 24 V DC / 100 mA auxiliary output for this model group. +24V and 24G are auxiliary output terminals. For sensor demand exceeding this budget, select a suitable external 24 V DC power supply.

Digital inputs: 16 channels, 24 V DC, approximately 5 mA/channel, with sinking or sourcing wiring. The ON threshold is >15 V DC and the OFF threshold is <5 V DC. Response times are 10 ms ±10% for OFF-to-ON and 15 ms ±10% for ON-to-OFF. For fast encoder signals, use appropriately rated CPU inputs or a dedicated counter module.

Relay outputs: 8 channels, rated for 10–250 V AC or 5–30 V DC. Resistive load limits are 2 A/output and 5 A total per common. Y0–Y7 share C0; eight simultaneous 2 A loads would exceed its limit. Relay response is approximately 10 ms and the specified switching frequency is at most 1 Hz. These outputs are unsuitable for fast pulse generation.

Installation: 35 mm DIN rail or screw mounting, removable terminal blocks, approximately 300 g and an operating temperature of 0–55 °C. Allow ventilation and maintenance access. Plan protective earthing and load-circuit fusing together.

Input and output wiring

The input terminals are S/S, X0–X7 and X10–X17. Octal numbering omits X8 and X9. For a PNP sensor, connect S/S to 0 V; for an NPN sensor, connect S/S to +24 V. Match sensor power and signal references to the selected diagram. Keep mains voltage away from the 24 V DC inputs and leave NC terminals unconnected.

C0 is the common feed for the relay contacts. Complete the circuit through the load supply, C0, selected Y output and load return. Evaluate contactor coil inrush and inductive duty as well as steady current. Consider a correctly oriented suppression diode for DC coils and suitable RC/varistor protection for AC loads. A resistive-load current rating cannot be applied unchanged to every load type.

Addressing, software and programming cable

DVP24XP200R does not receive a separate application program. Its input and output addresses depend on the CPU and preceding modules. When it is the first digital expansion module on a DVP32ES200R, the ES2 numbering rule gives X20–X37 for its 16 inputs and Y20–Y27 for its 8 outputs. This is an application of the manufacturer's addressing rule; check the actual arrangement before reusing the example.

Supported ES2/EX2 host CPUs can be programmed with WPLSoft or ISPSoft. Match the software version and CPU selection to the existing project, then check the new addresses in the ladder program. For an ISPSoft connection, configure the appropriate channel in COMMGR. The expansion module has no programming USB or serial port.

For the ES2/EX2 CPU's COM1 RS-232 port, UC-PRG020-12A provides a USB programming connection. Where the computer has a physical RS-232 port, UC-MS020-01A is an option. Connect the cable to the host CPU. Install the manufacturer's USB cable driver, check the COM number in Windows Device Manager and select the same port in the software. For other host families, verify software and cable support in the CPU manual.

Related models and differences

DVP24XP200T provides the same 16-input/8-output arrangement with transistor outputs and different load wiring. DVP32XP200R offers 16 inputs/16 relay outputs, while DVP32XP200T offers 16 inputs/16 transistor outputs. DVP24XN200R has 24 relay outputs only; DVP16XM211N has 16 digital inputs only. These are comparison models, not guaranteed replacements. Recheck supply, CPU support, addresses, common terminals and loads.

Editor's Note

Read the complete 200R suffix first. Compare terminal diagrams before transferring wiring from an older XP00/XP11 module or a transistor-output version.

Inspect loose terminals, oxidation, soot and heat damage before energizing. Isolate mains and load supplies and verify absence of voltage with a suitable multimeter. Pay particular attention to discoloration around C0.

Test inputs individually with a controlled 24 V DC source. Check both the input LED and the correct X address in the CPU. If the LED responds but the program does not, examine addressing, S/S wiring and the expansion connection first.

An illuminated output LED does not prove that the relay contact is healthy. Test each channel with a small, suitable fused load and check the voltage drop across the closed contact. An intermittent contact can pass an unloaded continuity test.

Add up all currents passing through C0. Suppress coil transients, review frequently switched loads and avoid arbitrary insulation testing across electronic circuits. Back up the CPU program and photograph the original wiring and addresses before replacement.

Related topics and navigation

Delta PLC · Delta DVP PLC series · DVP expansion modules · How relays work · Delta DVP PLC PDF files · Second-hand Delta equipment

External references

Delta DVP-ES2 DIDO Instruction Sheet — 21 February 2024; English/Chinese, 19 PDF pages. Delta DVP Series Module Manual — source file dated 20240226; internal revision dated 30 November 2023; English, 559 pages; model wiring on printed page 2-16. Delta PLC/HMI Cable Selection Guide — 15 August 2019; English, 175 PDF pages; ES2/EX2 connection on page 1-3 and USB cable on page 1-81.