Delta AH16AN01R-5A

Delta AH16AN01R-5A – 16-Point Relay Output Module

The Delta AH16AN01R-5A is a 16-point digital relay output module for the Delta AH500 PLC rack. Its relay contacts switch the external load supply connected to their common terminal. Field wiring connects through a removable screw terminal block. See Delta AH digital modules for other output types.

Contact voltage and load current

Delta’s model wiring diagram lists 24 V DC / 240 V AC contact ratings. For resistive loads, the limits are 2 A per output and 5 A per common. Add the currents of outputs that operate at the same time. Four loads drawing 1.5 A each, for example, draw 6 A through their shared common even though each output is within its individual limit. For valve and contactor coils, check inrush current and Delta’s contact life curve. Review the AH rack power supply and the field load supply separately.

COM0–COM3 terminal groups

COM0 serves outputs 0–3, COM1 serves outputs 4–7, COM2 serves outputs 8–11, and COM3 serves outputs 12–15. If four field outputs stop working together, first check whether they share the same common terminal.

ISPSoft and output addressing

Use HWCONFIG in ISPSoft to verify the rack, slot and starting Y address. The module occupies 16 output bits. The manual shows the range as Yn.0–Yn.15. Match each terminal channel to its output address in the project. See AH expansion modules for rack planning, Delta PLC software for engineering tools and What is a PLC? for basic terminology.

Wiring diagram and PDF archive

AH16AN01R-5A wiring diagram – AH500 Hardware and Operation Manual (EN) · PDF page 206, section 4.7.5. The diagram also appears in the AH500 section of the Delta PLC technical catalogue. See Delta AH PLC PDF files for other series documents.

Editor's Note

When buying a used module, check the AH16AN01R-5A label and the 16AN01R marking on the front.

Make sure the removable terminal block is included. Look for discoloration, melting or loose screws around the common terminals.

On the bench, use a suitable low-voltage test load to check all four COM groups and each output in turn.

When a channel LED lights, check that the contact actually closes at the field terminal. A worn contact can work intermittently.

Record the Y addresses and COM groups before replacing the module. Compare the outputs with the field labels before returning the machine to service.