Delta AH10DNET-5A
Delta AH10DNET-5A DeviceNet master / slave communication module
The Delta AH10DNET-5A is a CAN-based DeviceNet communication card for a compatible expansion slot to the right of a Delta AH500 CPU. This AH communications module can operate as a master scanning field devices or as a slave exchanging data with an upstream scanner.
Master and slave data capacity
In master mode, the card reads inputs and sends outputs to devices on its scan list. Delta specifies a maximum of 980 bytes each for inputs and outputs in master mode and 1,000 bytes each in slave mode. Set individual device data lengths and PLC starting addresses in the project.
The AHRTU-DNET-5A is the DeviceNet station head for digital I/O and analog I/O cards in a remote panel. The AH10DNET-5A operates alongside the CPU. When replacing one, check the expansion slot, main rack and rack power supply against the existing system.
DeviceNet wiring and baud rate
On the 5.08 mm removable connector, pin 1 is V− (black), pin 2 is CAN_L (blue), pin 3 is shield, pin 4 is CAN_H (white) and pin 5 is V+ (red). V+ and V− carry the 11–25 V DC DeviceNet network supply.
Use the two rotary switches to set a unique node address from 00 to 63. In DR1 / DR0 order, OFF/OFF selects 125 kbit/s, OFF/ON selects 250 kbit/s and ON/OFF selects 500 kbit/s. ON/ON enables extended rates configured in software. This mode supports up to 1 Mbit/s when every device on the network supports the selected rate. Set addresses and switches with power off.
ISPSoft, DeviceNet Builder and EDS
Use ISPSoft for the AH500 CPU hardware project and DeviceNet Builder for network configuration, operating mode, scan list and data mapping. Delta’s setup example connects the PC to the AH500 CPU over USB. For the master project, select the EDS file for the exact field device and revision. See Delta PLC software for related tools and Delta device description files for file types.
Manuals and PDF files
AH500 Module Manual — English PDF. Chapter 10 covers master and slave setup, extended baud rates, data mapping and a worked network example.
AH500 Hardware and Operation Manual — English PDF. Section 4.11.1 covers wiring, and section 12.3.7 lists module fault codes. See the Delta AH PLC PDF archive for related documents.
Editor’s Note
When buying used, ask for the removable five-pin connector. Inspect the rear backplane socket and both address switches.
Record the MS and NS LEDs together with the seven-segment display. Check for network power at V+ and V− even if the rack is powered.
For 16#A0F0, look for a duplicate or invalid node address. For 16#A0F1, check whether the master scan list is empty.
For intermittent communication, check that every node uses the same rate, verify CAN_H and CAN_L wiring, and check the 121 Ω terminators at both ends of the trunk.
IN0 determines whether the module holds or clears its previous I/O data when a slave disconnects. Compare the setting with the original project and verify the result on a bench setup isolated from the machine.
Related topics
AH10COPM-5A for CANopen, AH10PFBM-5A for PROFIBUS DP master, AH10PFBS-5A for PROFIBUS DP slave and AHRTU-PFBS-5A for PROFIBUS DP remote I/O.
Delta AH PLC series · Delta PLC · Second-hand Delta equipment
External references
Delta AH500 Module Manual · Delta AH500 Hardware and Operation Manual