Delta AH08AD-5A
Delta AH08AD-5A – 8-Channel Analog Input Module
The Delta AH08AD-5A is an 8-channel, 16-bit analog input module for Delta AH500 PLC systems. Among Delta AH analog modules, this version lets you configure each channel for voltage or current. It has a removable terminal block and a specified A/D conversion time of 150 µs per channel.
The same module can read a 4–20 mA pressure transmitter and a 0–10 V position sensor. Set the signal type and measurement range for each connected device. For limit switches and on/off status signals, see Delta AH digital modules.
Measurement Ranges and Input Impedance
Voltage inputs. 0–5 V, 1–5 V, ±5 V, 0–10 V and ±10 V. The specified voltage input impedance is above 1 MΩ.
Current inputs. 0–20 mA, 4–20 mA and ±20 mA. Current input impedance is 250 Ω. Include this 250 Ω load in the loop voltage calculation when selecting a two-wire transmitter.
Terminal Wiring and Module Power
For a voltage input, connect the signal between Vn+ and VIn−. For a current input, fit a jumper between Vn+ and In+ on the same channel as shown in Delta’s diagram. Connect the current signal to In+ and the return to VIn−. The letter n denotes the channel number from 0 to 7.
The AH08AD-5A receives module power from the backplane. Delta’s wiring note for this model leaves UP/ZP without an external 24 V DC connection. Wire the supply for a two-wire transmitter’s current loop separately according to the transmitter’s diagram. Route shielded signal cables away from power wiring and terminate the shield at SG as shown by Delta.
When installing the module, check the rack layout for the AH expansion modules and the capacity of the AH power supply.
ISPSoft Channel Setup and D Addresses
Use HWCONFIG in ISPSoft to add the module to its physical slot. Set each channel’s voltage or current mode, input range, and averaging or scaling as required. See Delta COMMGR for the PC-to-PLC connection setup.
Each channel’s floating-point measurement occupies two 16-bit D registers, for 16 registers across all eight channels. For example, if the project assigns D0 as the start address, CH0 uses D0–D1 and CH7 uses D14–D15. Check the actual range in the Input Device Range field in HWCONFIG.
5A, 5B and 5C Variants
The AH08AD-5A supports both voltage and current on a per-channel basis. The AH08AD-5B is the eight-channel voltage input model and the AH08AD-5C is the eight-channel current input model. For a four-channel installation, see the AH04AD-5A. Check the complete order code and terminal layout when selecting a replacement.
Manuals and PDF Downloads
AH500 Module Manual – AH08AD-5A wiring diagram · English, December 25, 2020. Printed page 2-17 shows the current-input jumper and the UP/ZP power note. Section 2.4 covers ISPSoft configuration.
AH500 Hardware & Operation Manual – analog input specifications · English, April 12, 2023. Printed pages 2-54–2-55 cover input ranges, hardware resolution, input impedance and conversion time.
Editor’s Note
When buying used, read the full AH08AD-5A code on the label. Check that the removable terminal block and latch are included.
Before removing the old module, photograph the Vn+ / In+ jumpers on the current-input channels and save the channel settings from ISPSoft.
On the bench, apply a known voltage to one channel and a known current from a calibrator to another. Check each reading in the corresponding D-register pair.
For a 4–20 mA channel, test 4 mA, 12 mA and 20 mA separately. This checks both the selected measurement range and the scaling to engineering units.
If readings fluctuate, check the cable route, shield termination and signal return first. Allow for a slower response when increasing the averaging setting.