6ES5 755-2CA11

Siemens 6ES5 755-2CA11 – ET 200C and DP/ASi Link Bus Terminating Resistor

Siemens 6ES5 755-2CA11 is a screw-on terminating resistor for the PROFIBUS-DP bus cable in ET 200C and DP/ASi Link installations. It fits the appropriate station's or T connector's 12-pin bus connection. Within the Siemens ET200 range and its distributed I/O arrangement, it provides the electrical termination required at the ends of a PROFIBUS cable section.

The part is used on the PROFIBUS side of documented couplers such as the 6ES7 156-0AA00-0XA0 DP/ASi Link. It should not be confused with a sensor connection on the AS-i network. The ET 200C manual specifies dimensions of Ø26 × 40 mm and a weight of approximately 70 g.

Where does it fit on the network?

Both ends of the bus cable must be terminated. In an ET 200C installation, the resistor screws onto the bus connection of a digital or analog station, or onto the 6ES5 762-2CT11 T connector. The 6ES5 762-2CS11 used for supply distribution has a different purpose. When selecting ET200 connection components, identify the cable end, supply point and station connection separately.

The last device physically located on the machine is not necessarily the electrical end of the bus cable. Trace the cable route and T connections. Review the ET200 terminal arrangement, cables and connectors and PROFIBUS connectors together to establish where termination is actually required.

12-pin connection and compatibility

6ES5 755-2CA11 is an accessory for the documented ET 200C/DP-ASi connection arrangement. Do not assume compatibility with every circular socket found among ET200 network connections or other ET200 network interfaces. When reviewing ET200 accessories, match the complete order number, contact count, mechanical coding and equipment wiring diagram.

Protection rating and installation conditions

The Siemens ET 200C and DP/ASi Link manuals specify IP66/IP67 for this terminating resistor under their installation conditions. Assess IP protection ratings and IP67 together with correct mating and seal condition. The ET 200C manual requires unused connections to be closed with suitable caps; transparent transport caps do not provide IP66/IP67 protection.

Blanking caps, Ethernet terminators and addressing

A blanking cap does not perform the electrical function of a bus terminating resistor. The similarly numbered 6ES5 755-3AA11 is a different terminator for Industrial Ethernet. When ordering, use the complete 755-2CA11 code and network type rather than relying on the description “755-series terminator.”

This component is not a network station and receives no slave address, I/O channel assignment or user program. When investigating PROFIBUS problems, consider an unterminated cable end, termination at the wrong point, cable damage and connection faults together. Removing the final station or extending the cable calls for a fresh check of the termination position.

Editor's note

Do not dismiss this small component as an ordinary metal cap. Missing termination may cause stations to disappear intermittently, although it is not the cause of every bus fault. During PLC troubleshooting, compare the fault record with the cable route and both ends of the network.

Trace the cable before moving parts. Fitting a terminator to every unused socket is not the correct approach. Sketching which T-connector branch continues the line and where the bus actually ends can save an unnecessary hardware replacement.

For a used unit, inspect threads, contact surfaces and sealing parts. Do not force damaged threads onto the mating socket. If dirt, corrosion or water marks are present, external cleaning alone is insufficient; check connection performance in a suitable test arrangement.

A resistance reading between two arbitrary contacts is not a complete health check. The correct pin arrangement and manufacturer wiring diagram are essential to interpreting a measurement. A similar resistance used on another network is not enough to establish interchangeability.

If faults appear when a drive starts, inspect more than the terminator. Check shield continuity, the grounding arrangement and the routing of bus and power cables. Correct termination cannot remove every effect of poor wiring.

Confirm whether the purchase includes one component or a set. The requirement for termination at both cable ends does not mean that every sale includes two units. Correct quantity and placement matter alongside the correct part number.

OtomasyonAVM resources and PDFs

Start with About Siemens ET200, ET200 connection modules and Siemens ET200 user manuals.

+ OtomasyonAVM ET 200C system manual, Edition 03, English: §3.12, printed page 3-22, covers application and connection. §13.5, PDF page 278 / printed page 13-8, provides dimensions and weight.

Related topics

+ 6ES5 762-2CT11: T connector for ET 200C and DP/ASi Link.

+ 6ES5 762-2CS11: Connector serving the different function of ET 200C supply connection.

+ 6ES7 156-0AA00-0XA0: DP/ASi Link coupler.

+ 6ES5 755-3AA11: Industrial Ethernet terminator; not a replacement for the 2CA11.

Browse related equipment

Siemens ET200 · ET200 accessories · ET200 connection modules · ET200 manuals · Used Siemens equipment

Siemens and external references

+ Siemens ET 200C Distributed I/O Station — EWA 4NEB 812 6119-02b, English: §3.12, §4.1 and §13.5; exact model, mounting, protection conditions and mechanical data.

+ Siemens DP/ASi Link Manual — EWA 4NEB 710 6055-02b, English: §4.4.5, printed page 4-21; third-party archive copy of the manufacturer document.