6ES7 156-0AA00-0XA0
Siemens 6ES7 156-0AA00-0XA0 DP/AS-i Link Module
Siemens 6ES7 156-0AA00-0XA0 connects an AS-Interface (AS-i) field network to PROFIBUS DP. It operates as a PROFIBUS DP slave and an AS-i master, making the input and output data of connected AS-i devices available to the upstream PLC. Its role is to integrate the sensor and actuator network into the machine’s control system.
Applications and field connections
Conveyors, packaging machines, assembly equipment and material handling systems often contain numerous sensors, pushbuttons, position switches and valves. AS-i allows these points to be collected along a common network using suitable field modules. For example, a conventional inductive sensor can connect through a compatible AS-i input module, while an instrument with a built-in AS-i interface can join the network directly.
The Link itself does not provide individual terminals for all these sensor and actuator signals. The connected AS-i devices provide the field I/O. Compared with a conventional arrangement using digital input modules and digital output modules, device addresses and AS-i profiles become an additional part of the selection process.
Device capacity and communication performance
The module supports up to 31 AS-i slaves. This is a device count, not a specification of 31 individual inputs or outputs. The available I/O arrangement depends on the field modules selected. This original model should not be specified as a 62-device AS-i master.
PROFIBUS DP communication supports rates up to 12 Mbit/s. The stated AS-i cycle time is 5 ms with 31 devices. That figure does not include the complete PLC program and DP communication response. When assessing performance, consider PROFIBUS communication and the AS-i cycle separately. Further network background is available on the ET 200 PROFIBUS and PROFINET page.
Separate DP and AS-i power requirements
The DP section requires a nominal 24 V DC supply, with a permitted input range of 20–30 V DC. Siemens lists a current consumption of 100 mA for the DP section and 70 mA for the AS-i section. These figures describe the module’s consumption; they are not an output rating for powering all connected field devices.
The AS-i network also requires a dedicated AS-i supply of approximately 30 V DC with data decoupling. Since communication and power share the same two conductors, an ordinary 24 V supply should not be connected directly as the AS-i bus supply. When choosing the power supply, account for field-device consumption and cable voltage drop. A DIN rail mounting format alone does not establish AS-i compatibility.
Connectors, enclosure and operating conditions
The PROFIBUS DP and 24 V supply connections use two 12-pin circular connection points. AS-i connects through a 4-pin M12 interface. The enclosure measures 205 × 80 × 57 mm and weighs 800 g. Allow additional installation space for the T connector and cable exits.
The die-cast aluminium enclosure provides IP66/IP67 protection when assembled with the correct connectors, covers and seals. The operating temperature specified for 6ES7 156-0AA00-0XA0 is 0 to +60 °C. When examining a used unit, connector threads, seals and covers deserve the same attention as the electronics. The ET 200 connection modules section provides additional background on connection arrangements.
Addressing, configuration and cabling
The PROFIBUS station address can be selected using DIP switches or EEPROM. This address is separate from the addresses of the AS-i devices. Configuration is handled through STEP 7 or COM PROFIBUS, depending on the control system. Check the project’s device arrangement and I/O definitions against the installed equipment; seeing the Link online on PROFIBUS does not establish that every field signal is correctly mapped.
A standard AS-i installation is assessed against a total cable length of 100 m, including branches. Extensions require a separately engineered solution. Cable routing should also account for electromagnetic interference from motor and drive wiring. Recording both the DP address and the AS-i device list makes later maintenance considerably easier.
Diagnostic indicators and maintenance
BF helps identify PROFIBUS-side problems, ASi POWER FAIL indicates an AS-i supply problem, and CONFIG ERROR relates to a difference between the expected and detected field configuration. These indications provide a starting point for checking the relevant network, supply or device group. They should not automatically be interpreted as proof that the Link hardware has failed. Record the LED states and PLC diagnostic information before arranging a replacement.
For the document archive, see Siemens ET 200 manuals. Match the selected DP/AS-i Link document to the complete order number and hardware release; products within the same family do not necessarily share every specification.
Editor’s note: Edition 3 of the Siemens manual covers 6ES7 156-0AA00-0XA0 from hardware release 03 onwards. Release-dependent functions should be checked separately for an earlier unit. The −25 to +60 °C operating range in that manual applies to 6ES7 156-0AA01-0XA0 and subsequent versions.
Related topics
For other parts of the installation, explore the Siemens ET 200 overview, ET 200 additional modules and power distribution modules. These links provide general background; accessory compatibility must be checked for the specific model.