6ES5 452-8MR11

Siemens 6ES5 452-8MR11 — 4-Channel Relay Output Module

The Siemens 6ES5 452-8MR11 is a 4-relay-contact digital output module for 30 V DC/230 V AC load circuits in the SIMATIC S5 family. It is specified for S5-90U, S5-95U, S5-100U, ET 100U and ET 200U systems. This S5 digital output module applies commands from the PLC central controller or an ET 200 remote I/O station through relay contacts.

Each output forms a separate galvanically isolated group. The manual specifies optocoupler isolation and varistor contact protection. When assessing a relay output, distinguish the switched load circuit from the module's relay supply.

AC and DC load limits

Resistive loads: maximum 5 A at 250 V AC or 2.5 A at 30 V DC. Inductive loads: maximum 1.5 A at 250 V AC or 0.5 A at 30 V DC. The manual's 5 A continuous-current rating does not establish a 5 A switching allowance for every load.

For loads such as contactor coils, check the coil's AC/DC type together with its switching current. This also applies to Siemens contactors; select the load using more than its nameplate power or the contact's 5 A rating.

Relay supply and bus unit

The L+/M relay supply is 24 V DC, with a permissible range of 20–30 V DC. This supply is separate from the 30 V DC or 230 V AC circuit switched by the contacts. Check it independently even when a PLC command is present.

The module plugs into a suitable bus unit. The screw-terminal 6ES5 700-8MA11 is one bus-unit example used in this system. Check cables and terminal connections against the existing slot arrangement and the manual's wiring diagram.

Channel count and switching frequency

In the PLC input/output configuration, treat this model as a 4-output module. The manual specifies a maximum switching frequency of 10 Hz. Account for mechanical contact life and load type; this figure does not authorize continuous rapid switching with every load.

Fault finding and installation

During PLC debugging, check the program command, 24 V relay supply and load circuit separately. When using a multimeter to check contact behaviour, also confirm that the load actually switches on and off. Inspect the load-circuit fuse, grounding and cable routing; noise immunity depends on the installation as well as the module.

Replace the module with PLC power, the relay supply and every load circuit passing through the contacts disconnected. Switching off the PLC alone does not establish that separately powered contact circuits are de-energized.

Differences from related models

The 6ES5 451-8MR12 is a different module with 8 relay outputs. The 6ES5 451-8MA11 uses DC semiconductor outputs, while the 6ES5 450-8MD11 uses AC semiconductor outputs. Compare channel count, output type and terminal arrangement before considering a replacement.

Editor's note

Start with the full order number: this board has four relay outputs. A similar name or appearance to the 451-8MR12 does not give it eight channels.

A relay click is useful, but it does not establish healthy contacts on its own. Switching all four channels with a suitable load gives a much better picture.

Take care with the 5 A figure when selecting a DC coil. AC/DC and resistive/inductive limits are different; the right load choice starts with those distinctions.

If the command is present but a relay stays quiet, first check the 24 V supply at L+/M. Confusing contact voltage with relay supply voltage can lead to replacing a sound board.

Keep photographs of the old label and terminal wiring, together with the test result. Stored with the S5 system information, these small records make the next service easier.

OtomasyonAVM resources and PDFs

+ Start with the OtomasyonAVM S5 PDF archive.

+ Exact-model wiring and load ratings appear in S5-100U System Manual, 14-35 and ET 100U Manual, 2-33. Check the complete order number in each page heading.

Related topics

+ 451-8MR12 relay output module · 451-8MA11 DC output module · 450-8MD11 AC output module.

+ 700-8MA11 bus unit · What is a relay? · What is an optocoupler?.

Browse SIMATIC S5

+ S5 digital output modules · Siemens S5 main page · Siemens ET 200.

+ Used Siemens automation equipment.

Siemens and external references

+ Siemens S5-100U System Manual — EWA 4NEB 812 6120-02b: page 14-35, PDF page 385; four outputs, load ratings, L+ supply and terminal diagram. English.

+ Siemens ET 100U Manual — EWA 4NEB 812 6040-02a: page 2-33, PDF page 47; exact-model relay output table. English.

+ Siemens 6ES5 452-8MR11 data sheet — June 29, 2020: supported systems and four relay contact outputs. An externally hosted copy of the German manufacturer document.