6ES5 252-3AA11
Siemens 6ES5 252-3AA11 IP 252 closed-loop control module
Siemens 6ES5 252-3AA11 is an IP 252 closed-loop control module for the SIMATIC S5 PLC family. Its onboard processor compares the setpoint with feedback and calculates the control output. Siemens shows this exact order number in a DC motor speed-control example.
OtomasyonAVM PDF archive
+ Siemens SIMATIC S5 manuals and PDF archive
Siemens application example for the 3AA11
The SIMATIC S5 example uses an S5-115U PLC with a CR 700-2 rack, a 6ES5 942-7UA11 CPU 942 and the 6ES5 951-7LD11 from the S5 power supply range. The IP 252 is fitted with a 6ES5 374-0AA11 DR/SR memory submodule. It takes speed feedback from an analog tachogenerator and sends a reference to the DC drive’s current controller. The PLC uses the digital inputs and digital outputs for machine sequencing.
Signals, connectors and sampling
The IP 252 specifications list 8 analog inputs and 8 analog outputs, with a nominal range of ±10 V. A terminal box connects the signals to the 25-pin X6 socket. Check the machine drawing when identifying S5 connection cables and any separate S5 analog modules.
X4 accepts an incremental speed sensor. The specifications list a 5 V encoder supply and a maximum input frequency of 200 kHz. The IP 242A counter is a separate module in the hardware inventory. X5 connects the programmer, and X3 holds the memory submodule. COM REG handles controller configuration and parameters.
The module can run up to eight control loops within its processor load limit. 4 ms is the shortest sampling interval. Siemens specifies one drive or standard control loop at this interval to stay within the processor limit.
Rack and revision checks
The IP 252 requires an adapter casing in the S5-115U. The hardware section describes direct mounting in suitable S5-135U and S5-150U racks. The S5-135U central controller and S5-135U/155U central controller pages help identify rack labels. Match S5 rack interfaces and expansion units against the machine’s hardware list.
A service list identifies the 6ES5 252-3AA13 as the successor to the 3AA11. Before a swap, compare the hardware revision, memory submodule and COM REG project. The IP 244 temperature controller, IP 245 proportional valve controller, IP 245 servo valve controller and IP 262 K-type and S-type modules serve different control tasks.
Editor’s note
1. Ask for separate photos of the 3AA11 label and the memory submodule in X3. For an S5-115U installation, confirm whether the adapter casing is included.
2. Before removing the module, back up the COM REG loop structure, parameters, sampling intervals and analog channel assignments.
3. If the DC drive reference is off, compare the X6 feedback channel and COM REG scaling with the wiring diagram. Check which variables are assigned to M1/M2.
4. If FAULT stays on after startup, read the fault log with the programmer. If it flashes briefly during RUN, check sampling intervals and processor load.
5. During a controlled bench test, check COM REG access via X5 and the X6 input and output channels used by the project. Record the results against both module labels.
Buying or selling a used module
For a quote, share photos of both labels, the quantity and the operating condition. Confirm the price and bench-test arrangements with the quote. To sell an IP 252, email otomasyonavm@gmail.com.
Related topics
+ IP 252 control module 6ES5 252-3AA13
+ CR 700-2 rack example — 6ES5 700-2LA11
+ SIMATIC S5 analog input and output modules
Second-hand Siemens
External references
+ Siemens IP 252 and COM REG, English, release 03, pp. 2-3–2-10 and 3-5