6ES5 252-3AA13
Siemens 6ES5 252-3AA13 SIMATIC S5 IP 252 closed-loop control module
OtomasyonAVM Siemens S5 PDF archive
The 6ES5 252-3AA13 is the IP 252 closed-loop control board in the SIMATIC S5 special module family. It compares a measured value with its setpoint and generates a command to reduce the difference. It can run up to eight control loops, depending on the configuration. Siemens lists a minimum sampling time of 4 ms. The number of available loops depends on the sampling time and the control functions selected.
Analog I/O and encoder connections
X6 carries 8 analog inputs and 8 analog outputs through a 25-pin D-sub connector. The nominal analog signal range is ±10 V for both inputs and outputs. X4 is the 15-pin input for an incremental encoder or digital tachogenerator. X5 is the programming device interface and X3 is the memory submodule receptacle. Select the S5 cables using the signal type and terminal-box drawing.
In a speed loop, for example, the IP 252 compares tachogenerator feedback with the speed setpoint and produces an analog command. Trace the digital permissive inputs and the digital outputs to the drive on the cabinet drawing. They help establish when the PLC program enables the loop.
Rack, memory and COM REG
The Siemens manual specifies an adapter casing for the S5-115U and describes installation in the S5-135U and S5-150U. The product note for the exact order number calls for careful alignment of the double-width module in the S5-155U guides. Check the installed rack, expansion unit and power supply codes. Match the controller structure and parameters to the COM REG backup and identify the installed memory submodule from the X3 label.
Direct speed-data exchange with the IP 240 is a specific S5-115U configuration documented by Siemens. It requires 3AA13 revision A04 or later, the 6ES5 374-0AB11 memory submodule, COM REG A05 or later or COM REG GRAPHIC, and the appropriate PS 7A/15A configuration. If a CPU 944 is fitted, check its revision against section 9.1 of the IP 240 manual.
Match the full order number and hardware revision when selecting a spare. Use the product-specific records and wiring documentation for the 6ES5 252-3AA11, IP 262 K and IP 262 S.
1. Back up loop settings before removal. Save the STEP 5 project and COM REG configuration. Record the full board code, revision, X3 memory code and interface number. Have a qualified technician isolate power before labelling the connectors.
2. If one loop drifts, start at X6. Compare the actual value shown in COM REG with the signal at the X6 terminal box and the expected scaling. If the measurement is correct, check the loop input mapping, setpoint and output limits.
3. If FAULT stays on, read the module diagnostics. After the power-on self-test, check the IP 252 RUN/STOP and FAULT indicators. If FAULT persists, have a qualified technician read the diagnostics through X5. Put the connected actuator in a safe state before testing outputs.
4. Compare interface numbers when several IP 252 modules are fitted. For revision 6 and later, Siemens warns that duplicate interface numbers in the same rack can cause a bus conflict. Match the numbers to the existing STEP 5 and COM REG project.
5. If IP 240 speed feedback is missing, verify the hardware and software chain. Check the 3AA13 revision, 374-0AB11 memory code, COM REG version and S5-115U power supply requirement together. Then verify that the actual speed from the IP 240 is read by the IP 252.
6. When buying used, confirm which parts are included. Request a photo of the full 3AA13 code and revision. Confirm whether the X6 terminal box and X3 memory submodule are included. Ask for a test record showing an analog input reading and a controlled change on the corresponding output.
To offer an IP 252 for sale, send the full order number, revision, quantity, condition, label photo and asking price. Include the memory submodule and terminal-box details if available. Contact otomasyonavm@gmail.com.
Related topics
Second-hand Siemens navigation
External references
+ Siemens 6ES5 252-3AA13 product information and revision notes, EWA 4NEB 811 0628-10 (DE)
+ Siemens IP 252 and COM REG, electrical specifications §2.1.5.3 (EN)
+ Siemens IP 252 and COM REG manual, release 03 (DE)
+ Siemens IP 240 manual, speed-data exchange with IP 252 §9.1 (EN)