6ES5 242-1AA32

The Siemens 6ES5 242-1AA32 is a SIMATIC S5 IP 242A high-speed counter module with seven independent channels. It processes pulses on the card and transfers the count to the S5 CPU.

Channels 1–5 are 16-bit counters. Their CNT count, STA start and STO stop inputs can be set to 5 V or 24 V. The limit is 480 kHz with the C8–C22 input filter capacitors unpopulated. Channels 1–5 support 19 modes, including frequency and time measurement.

Channels 6–7 are 24-bit up/down counters. They process A/B signals 90° apart from a 5 V RS-422 incremental encoder at up to 500 kHz. They also have an N zero marker and a separate SYN synchronization input.

X3 is the 37-pin Sub-D for channels 1–5. The 9-pin X4 and X5 serve channels 6 and 7 respectively. The 15-pin X6 carries the seven counter outputs and the external 24 V supply. The internal 5 V supply comes through X1.

Wiring, addressing and compatibility

Match the differential A/B/N outputs of the incremental encoder for channel 6 or 7 to the installed S5 cable. Check the relevant wiring table for other signal types used with S5 positioning modules.

Siemens lists CPU 941A/B through 944A/B for S5-115U. Check the full variant on a CPU 943 or CPU 944 label. For S5-135U, the manual specifies CPU 922 firmware 9.0 or later, CPU 928A 3UA12 or later, or CPU 928B. It also lists S5-150U/S and S5-155U with CPU 946 or CPU 947.

Parameters are set over the S5 bus. S3 sets the base address and addressing mode. Page frame addressing is the usual mode. The IP 242A also supports 210-byte linear addressing in S5-115U and S5-155U. FB 178–182 apply to IP 242A. The IP 242B 242-1AA41 uses FB 183/184 with its own firmware and has 32-bit channels 6–7.

The 242-1AA31, 242-1AA13, 242-1AA12 and 242-1AA21 pages cover separate order numbers. Compare the card label, firmware EPROM, S3 and the project function blocks before replacing the module.

If the cabinet also contains an IP 240, IP 281, 385A or 385B, mark which card handles each channel on the cabinet drawings.

Editor’s note

For a used card, ask for photos of the full order number and firmware EPROM label. Check whether the mating connectors for X3–X6 are included.

After isolating power, record the BR3–BR17 jumper positions for channels 1–5. Siemens ships these inputs set to 24 V. Compare the positions with the installed signal level.

If counting works at low speed but pulses are lost at high speed, check the C8–C22 filter positions and the pulse width. The 480 kHz limit applies with the filter capacitors unpopulated.

If channel 6 or 7 counts in the wrong direction, check the A/B phase sequence. If counting is correct but resetting fails, check the N marker and SYN input separately.

If the count changes but the field output fails to respond, check the external 24 V at X6 and the configured output function.

Related topics

+ IP 241 digital position decoder

+ IP 246I positioning

+ IP 266 closed-loop positioning

Used Siemens equipment

+ SIMATIC S5 special modules

+ Siemens SIMATIC S5

+ Used Siemens equipment

If you have this module to sell, email a label photo, quantity and condition to otomasyonavm@gmail.com.

OtomasyonAVM PDF archive

+ Siemens SIMATIC S5 manuals and PDF files

External sources

+ Siemens IP 242A/B manual · 6ES5 998-0KM21 · English

+ Siemens IP 242A/B manual · 6ES5 998-0KM11 · German

+ Siemens ST 50 · IP 242A/B specifications, printed pp. 4/57–4/58