6ES5 318-8MB12

Siemens 6ES5 318-8MB12 — ET 200U IM 318-B Slave Interface Module

The Siemens 6ES5 318-8MB12 is the IM 318-B slave interface for an ET 200U distributed I/O station, using SIMATIC S5 modules within the ET 200 family. It supports DP Siemens and DP Standard (PROFIBUS-DP / DP-Norm). DIP switch 8 selects the protocol; the supply is 24 V DC.

A station can accommodate up to 32 suitable S5-100U I/O modules, with a maximum address space of 32 input bytes and 32 output bytes. This head module in the S5 interface range transfers the installed modules’ data to the master. The I/O cards determine the station’s channel count.

Selecting DP Siemens or DP Standard

On the 318-8MB12, switch 8 ON selects DP Standard; OFF selects DP Siemens. The first seven switches set the station address in binary. For example, address 52 uses the weights 4 + 16 + 32. Check addressing and protocol selection separately.

For DP Standard operation with an IM 308-B master, the Siemens manual specifies COM ET 200 V4.0 or later and IM 308-B revision level 5 or software V4.0. Match the complete interface number and selected protocol in the PLC configuration, as well as the station address.

I/O modules, bus units and address space

Record the connection type, wiring arrangement and hardware revision of bases such as the 700-8MA11 bus unit and 700-8MA22 bus unit. Capacity for 32 modules does not mean every combination fits within the station’s 32-byte address space in each direction.

Compare the full order numbers and slot sequence of cards such as the 482-8MA13 digital I/O module, 464-8ME11 analog input module and 470-8MA12 analog output module with the project. Check permitted positions, data lengths and address identifiers separately for analog and function modules.

Supply and electrical specifications

The nominal supply is 24 V DC, with a permitted range of 20–30 V DC. The manual lists 150 mA maximum internal consumption and 800 mA maximum with the I/O bus fully loaded. Size a supply such as the PS 931-8MD11 for the interface and installed modules together.

The interface provides 9 V for the internal I/O bus. This is not a general field supply for sensors and loads; check the field cards’ L+/M supplies separately. Module weight is approximately 360 g, with dimensions of 45 × 162 × 125 mm.

PROFIBUS wiring and diagnostics

On the PROFIBUS connection, check duplicate addresses, termination and shielding together. Inspect the PROFIBUS connector and grounding arrangement before condemning the interface. Pay particular attention to termination at the ends of the segment.

The front panel has RUN, BUS-FAULT and IM-FAULT indicators. During troubleshooting, record which indicators remain lit or flash. Alongside the usual PROFIBUS checks, compare the master’s configured module sequence with the actual station layout.

Differences from other IM 318 versions

The 318-8MB11 uses DP Siemens; its switch 8 does not perform the same protocol-selection function as the MB12. Also verify the complete revision and configuration when considering the 318-8MB13. Do not assume MB11, MB12 and MB13 are interchangeable from their appearance.

The 318-8MC12 belongs to the IM 318-C DP/FMS range. The 318-8MA12 is a different version associated with ET 100U applications. Identify the 6ES5 318-8MB12 as an ET 200U IM 318-B and preserve the MB/MC/MA suffix distinction.

Editor’s note

Start with the label, then check switch 8. A healthy card cannot communicate correctly when the wrong protocol is selected. Keep a photograph of the old unit’s address and switch settings beside you when fitting a replacement.

A BUS-FAULT indication is a reason to investigate before buying another card. Check that the master is running, the address is correct and the connector and termination are sound. A poor contact elsewhere on the line can make a healthy interface look faulty.

Photograph the module sequence before removing anything. Moving an analog module or choosing a different configured length can shift the data mapping. A station photograph beside the configuration screen makes these differences much easier to spot.

A RUN indication is a useful starting point. For used equipment, ask where possible for actual input reading and output writing through the master. Measure the interface and field supplies separately: communication can be healthy while a load lacks its supply.

Before changing masters, retain the COM ET 200 project, complete module numbers and address map. Verify the required device-description file and I/O sequence before proceeding. A few clear records at the start can save hours during commissioning.

OtomasyonAVM resources and PDFs

+ Siemens ET 200 manuals · About Siemens ET 200 · S5 interface modules

+ The relevant ET 200U manufacturer-manual sections for protocol selection, addressing, supply and indicators are linked at the bottom of this page.

Related topics

+ 318-8MB11 · ;">318-8MB13 · 318-8MC12 · IM 308-B master · PROFIBUS connectors

Browse SIMATIC S5

+ Siemens ET 200 · S5 interface modules · SIMATIC S5 · ET 200 manuals · Siemens second-hand equipment

Siemens and external references

+ Siemens ET 200U Manual — 1-3: station structure, 32-module and 32/32-byte limits

+ Same manual — 5-21–5-22: station address and 318-8MB12 protocol switch

+ Same manual — 8-3–8-5: IM 318-B specifications and dimensions

+ Siemens ET 200U manual — DP Siemens / DP-Norm distinction and IM 308-B revision requirements (German)