6ES5 430-6AA11

Siemens 6ES5 430-6AA11 – 32-Input, 24 V DC Digital Input Module

The 6ES5 430-6AA11 is an isolated, rugged A-design (Robustbauform) digital input module with 32 inputs rated for 24 V DC, intended for S5-130A and S5-150A systems in the SIMATIC S5 family. Part of the digital input range, it passes contact and sensor states to the CPU program. Its inputs are arranged as four bytes in the wiring diagram.

The nominal field signal voltage is 24 V DC. Compare the power supply and voltage at the inputs with the cabinet diagram. Do not transfer the adjacent 431-6 card's 24/60 V selection feature to this model: the 430-6AA11 is a 24 V DC input card.

Input levels and sensor wiring

The Siemens ST 53 technical table specifies logic “0” as −33 to +4.5 V or an open input, and logic “1” as +13 to +33 V. Do not treat the gap between these thresholds as a defined logic state. Input current at logic “1” is typically 5 mA.

When connecting limit switches and inductive sensors, check the PNP/NPN output configuration and return wiring as well as voltage. Siemens' contact example applies positive field voltage to the input through the contact. Match sensor wiring to this input arrangement and the existing machine diagram.

Input delay and cable distance

Input delay is typically 3 ms. This is not a guaranteed minimum detectable pulse width or a high-speed counting frequency. Where short events must be detected, assess sensor pulse duration and the PLC scan together.

Maximum cable lengths are 400 m unshielded and 1000 m shielded. Check signal cable routing, shield connections and grounding. Distance alone is insufficient for assessing wiring installed close to motor and drive cables.

Two groups of 16 inputs

The Siemens wiring diagram assigns the first 16 inputs to Byte 0 and Byte 1, and the second 16 inputs to Byte 2 and Byte 3. The first field circuit is labelled 1L+/1L−, and the second 2L+/2L−. Distinguish the four input bytes from the two supply groups.

Check the rack and front connection against the A-design diagram. Isolation does not mean that every input has an independent connection arrangement. If an entire group is missing, inspect its common supply, return and connector connections too.

Addressing and program checks

Byte 0–Byte 3 in the diagram are relative positions within the module. Verify the actual start address in the PLC program against the system configuration. For example, if the start address is IB 64, the four groups use I 64.0–64.7, I 65.0–65.7, I 66.0–66.7 and I 67.0–67.7. This is not a fixed factory address.

During troubleshooting, follow the input bit, program condition and digital output response separately. Check the field circuits of output cards such as the 451-5AA13 or 450-6AA12 independently. Correct input recognition alone does not establish that the entire control chain is working.

Comparing related ordering codes

The 431-6AA11 is a different A-design card with 16 inputs and individual 24/60 V selection. The 432-6AA12 provides 16 inputs for 24 V DC with group signalling. Their channel counts and additional functions must not be treated as identical to those of the 430-6AA11.

The 430-3BA11, 430-4UA12 and 430-7LA12 share the “430” designation, but mechanical design, system suitability and wiring require separate checks. For replacement selection, use the complete 6ES5 430-6AA11 code, revision and front-wiring photographs together. Disconnect system and field supplies before removal or installation.

Editor’s note

Start by looking at the fault pattern. Is one input missing, or have 16 disappeared together? If a whole group is affected, measuring its common supply and return connections is a useful first step.

A lit input indicator is not the end of the check. Make sure you are monitoring the correct address in the program. On older machines, a changed cable label or an incorrect address note can lead to a healthy card being removed unnecessarily.

When requesting a spare, give more than “32-input S5 card.” State the 430-6AA11 code and A design clearly. Matching input counts do not establish matching connectors or systems.

For intermittent missing signals, check the sensor supply and cable too. Where practical, measure the signal at the input terminal. Testing with very short pulses without allowing for the typical 3 ms delay can give misleading results.

Have all 32 inputs of a used card checked in a suitable test setup. Test both connection groups separately; a few working indicators do not prove that the whole card is healthy. Checking the connector and locks beforehand also makes installation easier.

OtomasyonAVM resources and PDFs

+ Our S5-115 PDF page: other S5 system documentation. The technical source for the 430-6AA11 is the S5-130/S5-150 ST 53 catalogue below.

+ S5 digital input modules · S5 cable types · S5 racks

Related topics

+ 431-6AA11 · 432-6AA12 · 430-3BA11 · 430-4UA12 · 430-7LA12

+ PNP and NPN sensors · Grounding · PLC troubleshooting

Browse SIMATIC S5

S5 digital inputs · S5 racks · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

+ Siemens ST 53 / 1985 – S5-130 and S5-150 catalogue, German: specifications, printed p. 8/5 / PDF 91; wiring, p. 8/20 / PDF 106; exact ordering code and supported systems, May 1985 ordering table, p. 9/6 / PDF 124. Third-party archive copy of a Siemens publication.