6ES5 430-3BA11
6ES5 430-3BA11 – SIMATIC S5 32-Channel 24 V DC Compact K Digital Input Module
Siemens 6ES5 430-3BA11 is a 32-channel, 24 V DC digital input module in the compact K format for the SIMATIC S5-130/150K group. Within the S5 digital input module range, it provides two galvanically isolated groups of 16 inputs. This Siemens S5 module converts field signals into input states that the PLC program can read.
Applications include monitoring pushbuttons, limit switches, compatible sensors and contactor auxiliary contacts. Check both the 3BA11 suffix and the K mechanical format when selecting a spare; a description such as “430, 32 inputs” is insufficient.
Input levels and sensor selection
The specified levels are logic 0: −33 to +4.5 V; logic 1: +13 to +33 V. Do not treat the intervening region as a reliable switching level. Evaluate the 24 V DC power supply and NPN/PNP output configuration against the module’s input reference.
Nominal input current is 8.5 mA ±10%; typical input resistance is 2.8 kΩ. When selecting an inductive sensor or photocell, check its output voltage under load and its off-state leakage current.
Isolation and group references
Isolation is arranged in two groups of 16 inputs; it does not imply independent isolation for every channel. Follow the wiring diagram and distinguish group references from protective grounding. If an entire group is affected, check its common connection and connector contacts first.
Input delay and program monitoring
Input delay is typically 3 ms, with a minimum of 1.4 ms and a maximum of 5 ms. Consider the PLC program and CPU scan time when assessing short pulses. During troubleshooting, monitor the field signal alongside the corresponding program input bit.
Address coding socket and four input bytes
The module address is set through an address coding socket. When replacing a SIMATIC S5 module, record the existing socket configuration and board jumpers. Thirty-two input bits represent four bytes; compare the channel order with the program’s address list.
For example, if the existing configuration starts at byte 20, the four-byte bit range is I20.0–I23.7. This illustrates address tracking; the actual starting address depends on the socket coding and machine configuration. Preserve channel labels when disconnecting S5 cables and connectors.
Compact K construction and supply checks
Consumption from the internal 5 V supply is approximately 150 mA. Keep this separate from the total consumption of field sensors. Check the S5 rack, front connector and control panel layout against the existing K-format hardware.
Comparison with similar order codes
When comparing 6ES5 420-3BA11, check the isolation arrangement; when comparing 6ES5 431-3BA11, check the channel count and input-voltage configuration. Similar order codes do not establish that the same wiring can be used.
For 6ES5 430-4UA11 and 6ES5 430-4UA14, assess the U-format housing, rack and front connection separately. An identical channel count does not establish that either module can directly replace a compact K module.
Editor’s note
Start by reading the complete label on this S5 module: 430-3BA11, compact K. Ask for clear photographs of the label, front connection and both sides of the board. A seller’s shortened description leaves too much room for a mismatch.
Before removal, photograph the address coding socket, jumpers and cable order. A spare with the same order code may arrive configured for another machine. Recording the original setup can save a lengthy search after replacement.
If sixteen inputs disappear together, check the shared connections before condemning the board. Work through the group common, field voltage and connector contacts. One common connection fault can make healthy channels appear defective.
A sensor’s illuminated indicator does not prove that the module receives a valid signal. Measure at the module terminal against the correct group reference, then watch the program input bit. A cable or contact fault may be invisible at the sensor itself.
When buying a used Siemens module, ask for all 32 channels to be tested in both logic states. A few working inputs are insufficient. Isolate power before replacement; understand the existing setup first, then make controlled changes.
OtomasyonAVM resources and PDFs
+ S5 digital input modules · S5 cables and connectors · S5 racks.
+ Siemens S5 shared PDF archive. The exact 430-3BA11 table appears in the German Siemens compact input module operating instructions below, on printed page 7 / compilation page 149.
Related topics
+ 420-3BA11 · 431-3BA11 · 430-4UA11 · 430-4UA14.
+ NPN versus PNP · PLC troubleshooting · S5 digital output modules.
Browse SIMATIC S5
S5 digital inputs · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page.