Siemens 6ES5 431-6AA11 – 16-Input, 24/60 V DC Digital Input Module

The 6ES5 431-6AA11 is an isolated, 16-input digital input module in the rugged A design (Robustbauform) for S5-130A and S5-150A systems in the SIMATIC S5 family. Within the digital input range, it supports 24 V DC or 60 V DC signals, selected individually for each input using jumpers on the card. Siemens specifies 24 V as the factory setting.

The card passes contact and sensor states to the CPU program. The 24/60 V designation does not permit either voltage to be applied without checking each channel's configuration. Compare the field supply and individual jumper settings with the machine diagram.

24 V and 60 V input levels

At the 24 V setting: logic “0” is −33 to +4.5 V or an open input; logic “1” is +13 to +33 V. At the 60 V setting: logic “0” is −72 to +9 V or an open input; logic “1” is +26 to +72 V. Do not treat the gap between these thresholds as a defined logic level.

For limit switch and inductive sensor applications, consider the output voltage, PNP/NPN configuration and return wiring together. In particular, do not rely on an occasional indicator response when applying a 24 V sensor signal to a channel configured for 60 V; verify the channel setting.

Input current, delay and cable length

The Siemens ST 53 technical table specifies 5 mA typical input current at logic “1” and a typical input delay of 3 ms. Do not interpret this delay as a guaranteed minimum detectable pulse width or a high-speed counting frequency.

Maximum cable lengths at the 24 V setting are 400 m unshielded and 1000 m shielded. At the 60 V setting, they are 250 m unshielded and 700 m shielded. Assess cable routing, shielding and grounding for the actual cabinet conditions; the catalogue maximum does not guarantee identical noise performance in every installation.

Two input bytes and group connections

The wiring diagram assigns inputs 0–7 to Byte 0 and inputs 8–15 to Byte 1. The two eight-input groups have 1L+/1L− and 2L+/2L− connections. Check the rack and front connection against the A-design diagram; connectors from different S5 mechanical designs are not automatically interchangeable.

Byte 0 and Byte 1 in the diagram are relative positions within the module. Verify the actual input addresses in the PLC program against the system configuration. For example, if the assigned start address is IB 64, the groups use I 64.0–I 64.7 and I 65.0–I 65.7. This is an example, not a fixed factory address.

During troubleshooting, follow input recognition and digital output operation separately. Check the field circuits of output cards such as the 451-5AA13 or 450-6AA12 independently. A machine failing to respond despite a correct input bit does not by itself establish an input-card fault.

Differences from related input cards

The 430-6AA11 is a different A-design card with 32 inputs rated for 24 V DC. The 432-6AA12 provides 16 inputs for 24 V DC and group signalling. Keep these distinct from the 431-6AA11's 16 channels with individual 24/60 V selection.

The 431-3BA11, 431-4UA12 and 431-7LA11 share the “431” designation but require separate mechanical and electrical checks. For replacement selection, use the complete 6ES5 431-6AA11 code, jumper settings and front-wiring photographs together. Disconnect system and field supplies before removal or installation.

Editor’s note

Check the jumpers first on this card. If a replacement channel arrives configured for 60 V, your 24 V signal may not register as expected. A matching model number does not guarantee matching settings.

Photograph the channel settings and wiring before removing the old card. Make a short record of which inputs use 24 V and which use 60 V. Having that information to hand makes installation much easier.

If eight inputs disappear together, check that group's supply and return connections before assuming all eight channels have failed. One loose common connection can make a healthy card look faulty.

For intermittent missing signals, investigate the sensor, cable and pulse duration together. An input with a typical 3 ms delay should not be expected to capture every short pulse. Establish what the application actually requires.

When buying a used card, have all 16 channels checked at the voltage settings you intend to use. One lit input indicator does not prove the entire card is healthy. Inspecting the front connector and jumper condition beforehand can save trouble later.

OtomasyonAVM resources and PDFs

+ Our S5-115 PDF page: other S5 system documentation. The technical source used here for the 431-6AA11 is the S5-130/S5-150 ST 53 catalogue below.

+ S5 digital input modules · S5 cable types · S5 racks

Related topics

+ 430-6AA11 · 432-6AA12 · 431-3BA11 · 431-4UA12 · 431-7LA11

+ PNP and NPN sensors · Limit switches · PLC troubleshooting

Browse SIMATIC S5

S5 digital inputs · S5 racks · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

+ Siemens ST 53 / 1985 – S5-130 and S5-150 catalogue, German: specifications, printed p. 8/5 / PDF 91; wiring, p. 8/20 / PDF 106; exact ordering code and supported systems, May 1985 ordering table, p. 9/6 / PDF 124. Third-party archive copy of a Siemens publication.