6ES5 465-4UA11
Siemens 6ES5 465-4UA11 – 16-Channel Analog Input / 8-Channel Pt100 Module
6ES5 465-4UA11 is a non-isolated analog input module in compact U construction for Siemens SIMATIC S5 U peripheral systems. In suitable S5-135U, S5-150U and S5-155U peripheral configurations, it provides 16 voltage/current inputs or eight Pt100 resistance inputs. The ranges of this S5 analog module depend on its 6ES5 498 range submodules and mode switches. Data can be represented as 13-bit two’s complement or 12 bits plus sign.
The module can acquire signals from suitable pressure sensors, Pt100 temperature sensors and thermocouples using the appropriate millivolt range. Match the analog signal, sensor wiring and range submodule together. Pt100 measurement uses a four-wire circuit distinct from the voltage/current connections.
Selecting the input range
In the 500 mV base setting, 6ES5 498-1AA11 provides a direct connection for ±500 mV and Pt100. The same submodule supports ±50 mV with the 50 mV setting. 498-1AA21 provides ±1 V, 498-1AA31 provides ±10 V and 498-1AA61 provides ±5 V. For voltage/current measurement, each range submodule serves four inputs.
6ES5 498-1AA41 supports ±20 mA. 498-1AA51 is for two-wire transmitters and 498-1AA71 for four-wire transmitters with 4–20 mA signals. Different suitable range submodules may be fitted to four-input groups while retaining the common 500 mV base setting.
The analog current input burden is 25 Ω for ±20 mA and 31.25 Ω for 4–20 mA. Voltage input impedance is 90 kΩ for ±1 V and 50 kΩ for ±5 V and ±10 V. These values include the installed range submodule.
Scanning time and isolation
At the 50 Hz setting, integration takes 20 ms and coding takes 60 ms per measured value. Scanning eight values takes approximately 0.48 seconds; 16 values take approximately 0.96 seconds. At 60 Hz, coding takes 50 ms per value. The analog update interval is separate from the PLC scan time.
Mode switches select 8/16 channels, cyclic/single scanning, 50/60 Hz and data representation. In single scanning, the CPU initiates conversion; the result is valid when the T activity bit clears. A change in measurement mode must also be reflected in the program’s data handling.
The 465-4UA11 has no galvanic isolation. The permissible common-mode difference between sensor references, and between sensors and the module reference, is ±1 V maximum. Assess the grounding arrangement against this limit. Do not assume the same wiring conditions as an isolated module such as 6ES5 460-4UA11.
Power, front connector and Pt100 wiring
The digital section draws typically 150 mA from the system bus at 5 V ±5%. The F+/F− enable input requires 24 V DC and approximately 5 mA. The external 24 V load supply listed in the specification is required for two-wire transmitters. The S5 front connector has 42 positions: F+ is pin 1, F− pin 2 and L+ pin 3. For voltage/current measurement, channel 0 uses 4 (+) and 5 (−).
Pt100 operation uses the eight-channel, four-wire resistance setting. The module supplies a 2.5 mA constant current; connect the current and sensing leads according to the separate Pt100 diagram. The difference between Pt100 and thermocouples also affects software: Pt100 data represents resistance, while a thermocouple’s millivolt signal requires suitable reference-junction compensation and conversion.
The address switch sets the module’s starting address. Each measured value occupies two bytes; 16 inputs require 32 bytes. A channel starts at base address + 2 × channel number. With base address 192, channel 15 is read from bytes 222–223. Match the channel count and address allocation to the existing PLC program.
Scaling, overflow and broken-wire detection
The nominal bipolar range is represented by ±2048 scaled units. For 4–20 mA, 4 mA corresponds to 512 units and 20 mA to 2560 units. Subtract 512 in software if a 0–2048 result is required. Evaluate activity, fault and overflow bits separately from the measurement data in the raw word.
A specific 4UA11 behaviour: in cyclic operation, an overdriven channel sets the overflow bit for all channels because subsequent readings may also be affected. During PLC troubleshooting, investigate an excessive signal on one channel before treating all sensors as faulty.
With suitable settings, broken-wire detection can be used with the 1AA11 direct-connection submodule. The same hardware indication is unavailable with the shunt inputs of 1AA41, 1AA51 and 1AA71; monitor the lower limit of a 4–20 mA signal in software. The removable enable jumper and test-current disabling connection documented for 6ES5 465-4UA12 must not automatically be applied to the 4UA11.
Editor’s note
Identify the card together with its range submodules. The 465-4UA11 label alone does not establish a ±10 V or 4–20 mA input range. Record each group’s 498 code and the positions of both mode-switch banks.
Measure reference differences first. This module is non-isolated. For signals arriving from separate panels, check common-mode voltage; a correct differential signal alone does not demonstrate compliance with the ±1 V reference limit.
Allow for the 0.96-second scan. With 16 channels at 50 Hz, tracking a rapidly changing signal may be limited. Observe the actual analog update interval as well as the PLC scan time.
Interpret zero readings with their status bits. One overdriven channel can affect overflow indications across the card. Broken-wire detection may return a zero value together with a fault indication, so the numeric value alone is insufficient.
Test a used card in its intended ranges. Use a suitable calibrator for voltage/current inputs and a resistance source for Pt100 inputs. Check range-submodule contacts, the front connector and individual channel results.
OtomasyonAVM resources and PDFs
+ Browse About Siemens S5 PLC and S5 analog modules for system background and module groups.
+ The OtomasyonAVM S5 PDF archive collects the available system manuals. The exact 465-4UA11 specifications are in the U Periphery manual below.
Related topics
+ 6ES5 465-4UA12 and 6ES5 465-4UA13: different versions in the same series; compare mode settings, enable circuits and project requirements.
+ 6ES5 460-4UA11: an eight-channel analog input module with galvanic isolation.
+ 498-1AA11, 498-1AA31 and 498-1AA51: submodules that establish different measurement ranges.
Browse SIMATIC S5
+ S5 analog modules · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page
Siemens and external references
+ Siemens SIMATIC S5 U Periphery – 6ES5 998-0PC22, Release 01 (English PDF): analog module instructions C79000-B8576-C300-06, §5.4. PDF pages 189–193 / printed pages 5-14–5-18 cover the 465-4UA11 specifications, mode settings, range submodules and connector wiring.
+ Analog input representation and 4–20 mA scaling: §3.2, PDF pages 158–163. 4UA11 overflow behaviour: §1.3.1, PDF page 140.