6ES5 431-8MA11

Siemens 6ES5 431-8MA11 – 8-Channel 24 V DC Isolated Digital Input Module

Siemens 6ES5 431-8MA11 is an eight-channel, 24 V DC digital input module for SIMATIC S5 systems. It is documented in the S5-90U, S5-95U and S5-100U manuals and listed for ET 100U. This S5 digital input module provides optocoupler isolation in one group of eight inputs.

The input ranges are 0–5 V for logic 0 and 13–33 V for logic 1. At 24 V, logic-1 input current is 8.7 mA typical. The manufacturer’s diagram shows L+ applied to the input; assess a relay contact or positive-switching field output against that arrangement. These ratings concern the 24 V DC field circuit of the Siemens S5 system.

Signal thresholds and two-wire sensors

Voltages above 5 V and below 13 V are outside the specified logic-0 and logic-1 ranges. Measure between the input terminal and M. Include the actual terminal voltage in load and wiring calculations, rather than relying on the nominal supply alone.

Two-wire BERO proximity switches can be connected; the specified residual-current limit is 1.5 mA. Check off-state sensor current together with the voltage remaining at the input. Do not assume that this 24 V DC input is suitable for a 5 V logic signal.

Terminal order and common M connection

The diagram assigns terminal 1 to L+ and terminal 2 to M. Input-bit assignments are .0 → 4, .1 → 3, .2 → 6, .3 → 5, .4 → 8, .5 → 7, .6 → 10 and .7 → 9. Match field wiring by both terminal number and bit designation.

The eight channels share M and are not individually isolated from one another. Galvanic isolation does not mean an earthed input. Keep protective grounding distinct from the field M connection. When investigating interference, check the return conductor, shielding and connection contacts together.

Delay, cable length and operating conditions

The S5-100U specification gives typical input delays of 5.5 ms from 0 to 1 and 4.5 ms from 1 to 0. Include CPU scan time when assessing short pulses; this is not a high-speed counter input. The maximum specified unshielded field-cable length is 100 m.

Typical consumption from the internal +9 V CPU rail is 32 mA, typical power loss is 2 W, and approximate weight is 190 g. Distinguish internal module consumption from field-input current in the power-supply calculation. Permitted ambient temperatures are 0–60 °C horizontally and 0–40 °C vertically.

For supply faults, inspect the cabinet fuse and possible field short circuits. This check does not imply that the module contains a user-replaceable input fuse.

Mechanical coding and addressing

The module’s mechanical code is 4. Match the coding element on the S5-100U bus unit to the module; this number is not the input-byte address. For S5-100U digital I/O, the slot determines the byte: for example, slot 3 → I 3.0–I 3.7. German operand notation uses E instead of I.

Compare the PLC program addresses with the physical installation. Inserting a bus unit can change subsequent slot addresses. During troubleshooting, observe the channel indicator and program bit together. In ET 100U, follow the interface addressing arrangement; the module’s address designation is 8DI.

Important differences between similar codes

The 431-8MC11 is a 115 V AC input model and the 431-8MD11 a 230 V AC model. The 433-8MA11 has a different 5–24 V DC input arrangement. The 421-8MA12 is a separate, non-isolated card. Equal channel counts do not establish interchangeability; compare the full code and wiring within the S5 family.

Editor’s note

Read the 8MA11 suffix first. The 8MC11 and 8MD11 do not operate at the same input voltage. Eight channels alone are not enough to identify a suitable replacement.

If an input remains on with the sensor off, check the two-wire sensor’s residual current and input-to-M voltage before condemning the card. A small leakage current can complicate diagnosis, particularly in older installations.

If all eight inputs disappear together, start with L+, M and the terminal contacts. They form one common group, so a shared connection fault can affect every channel. Check that path before replacing a sound card.

If short pulses are missed, remember the 5.5 ms / 4.5 ms input delays and CPU scan time. A successful slow on/off bench test does not establish that fast pulses will be captured.

When buying a used Siemens card, test all eight inputs using the correct terminal order. Confirm that each front indicator and program bit refer to the same channel. Inspect bus contacts, loose terminals and evidence of previous repair too.

OtomasyonAVM resources and PDFs

+ S5 digital input modules · About Siemens S5 PLC

+ Siemens S5 shared PDF archive and operating manuals. For the exact model, use the S5-100U specification on printed page 14-22 / PDF page 372.

Related topics

+ 6ES5 431-8MC11 · 6ES5 431-8MD11: different AC input models.

+ 6ES5 433-8MA11 · 6ES5 421-8MA12: compare signal and isolation arrangements separately.

Browse SIMATIC S5

+ S5 digital input modules · S5-100U bus unit · SIMATIC S5

+ Siemens S5 PLC · Siemens second-hand equipment

Siemens and external references

+ Siemens S5-100U System Manual – English; EWA 4NEB 812 6120-02b, Edition 04. Printed page 14-22 / PDF page 372: exact 431-8MA11 ratings and wiring. Section 6.2 / PDF page 106: digital addressing.

+ Siemens S5-90U/S5-95U System Manual – English; EWA 4NEB 812 6115-02b, Edition 03. Printed page 15-19 / PDF page 383: the same exact module.

+ Siemens ET 100U Distributed I/Os Manual – English; EWA 4NEB 812 6040-02a. Printed page 2-20 / PDF page 34: module support and 8DI designation. Input-delay figures on this page follow the S5-100U manual.