6ES5 431-8MD11

Siemens 6ES5 431-8MD11 – 8-Channel 230 V AC/DC Digital Input Module

6ES5 431-8MD11 is an 8-channel, 230 V AC/DC digital input module in the Siemens SIMATIC S5 family. This S5 input module has optocoupler-based galvanic isolation arranged as one group of eight inputs (1 × 8). The channels are not individually isolated and use a shared N reference.

Siemens lists this model for SIMATIC S5 S5-90U, S5-95U, S5-100U, ET 100U and ET 200U systems. It transfers the status of 230 V control circuits, contactor auxiliary contacts and relay contacts to the PLC. Match the S5 system architecture, bus unit and station address assignment together.

Voltage class and signal thresholds

Rated input voltage is 230 V AC/DC; the UC designation indicates AC and DC operation. AC signal frequency is 47–63 Hz. The specified ranges are 0–95 V for logic 0 and 195–253 V for logic 1. Voltages above 95 V and below 195 V must not be used as a defined logic state.

Typical on-state input current is 16 mA at 230 V AC and 1.8 mA at 230 V DC. Select a relay contact or sensor output for the actual AC/DC supply type. A 24 V DC sensor output does not reach this model's on-state threshold.

Input delay and 2-wire sensors

Typical input delay is 10 ms for a 0→1 transition and 20 ms for a 1→0 transition. Assess module delay together with CPU scan time for short pulses. The 47–63 Hz value describes AC signal frequency and must not be interpreted as a high-speed counting specification.

2-wire BERO proximity switches can be connected; the manual specifies 5 mA sensor residual current. Check voltage class, off-state leakage and the actual voltage at the input together.

Isolation and field wiring

Optocoupler isolation separates the eight-input group from the system side. Follow the shared N connection in the machine diagram. On suitable bus units such as 6ES5 700-8MA11, terminal arrangement and mechanical coding must match the module type.

Inspect S5 connection parts, connection contacts and terminal tightness. Maximum unshielded field-cable length is 100 m. Assess cable routing, electromagnetic interference, earthing and circuit fuse protection together.

Internal consumption and ambient temperature

The module draws typically 32 mA from the system's +9 V supply. Typical power loss is 3.6 W, and weight is approximately 260 g. In power supply and PLC supply calculations, distinguish internal consumption from current in the 230 V field-input circuits.

The S5-100U manual specifies a module ambient range of 0–60 °C for horizontal mounting and 0–40 °C for vertical mounting. When checking the S5 mounting arrangement and slot layout, also observe the overall temperature limits of the installed station.

Addressing and input checks

The eight channels provide one byte of digital input data. The address follows the installed slot and the station's address assignment. In the ET 100U manual, the module's address designation is 8DI; apply that designation in the ET 100U context.

Compare the CPU project and input addresses in the PLC program against the installed hardware. For example, if the station assigns this module byte 4 (04h), its channels are I4.0–I4.7; German notation uses E. During troubleshooting, compare field voltage, channel LED and the program's input state.

Related modules and used-equipment checks

6ES5 431-8MC11 is an 8-channel 115 V AC/DC input module, and 6ES5 431-8MA11 is an 8-channel 24 V DC model. 6ES5 430-8MD11 has 4 inputs at 230 V AC/DC, while 6ES5 433-8MA11 has 8 inputs at 5–24 V DC. Verify voltage thresholds, channel count and wiring before selecting a replacement.

On used Siemens equipment, inspect the label, bus contacts, terminal areas and signs of overheating. Test every channel in both on and off states at the appropriate voltage.

Editor’s note

Start by confirming the 8MD11 order code and 230 V input class. An 8MC11 or 8MA11 may look similar, but its voltage rating is different. Compare the labels before fitting the spare and begin with the right part.

If all inputs disappear together, give the board a fair check first. Inspect the shared N line, field supply and bus unit. A fault in a common connection can affect every channel in this single-group arrangement.

If an LED stays on with the contact open, measure sensor leakage and the actual input voltage. With 2-wire sensors in particular, a connected cable alone tells you little; use the signal thresholds to guide the diagnosis.

Do not assume terminal numbers correspond directly to input bits. Follow the channel-to-terminal markings on the front label. Check the bus unit's coding too; if the module will not seat, find the cause instead of forcing it.

With a used board, test all eight channels rather than stopping after a few LEDs light up. Have 230 V testing performed by qualified personnel using a protected setup. Isolate field and system power before removal and photograph the connections; those small records make fitting the spare easier.

OtomasyonAVM resources and PDFs

Start with the OtomasyonAVM Siemens S5 PDF archive, About Siemens S5 and S5 digital input modules.

The technical table appears on printed page 14-24, PDF page 374, of Siemens S5-100U, 6ES5 998-0UB23 / EWA 4NEB 812 6120-02b. The ET 100U manual covers the same model on printed page 2-22, PDF page 36.

Related topics

+ 6ES5 431-8MC11 · 6ES5 431-8MA11 · 6ES5 430-8MD11 · 6ES5 433-8MA11.

+ 6ES5 700-8MA11 bus unit · PLC troubleshooting · Electromagnetic interference.

Browse SIMATIC S5

Siemens S5 home · S5 digital input modules · S5 PDF archive · Used Siemens equipment

Siemens and external references

+ Siemens S5-100U system manual – English PDF: 6ES5 431-8MD11 ratings, temperature limits and connection diagram.

+ Siemens ET 100U manual – English PDF: 8DI address designation, technical table and bus-unit connections.