6ES5 470-4UB13

6ES5 470-4UB13 Siemens S5 – 8-Channel ±10 V Analog Output Module

6ES5 470-4UB13 is a compact U-design analog output module for SIMATIC S5-135U/155U systems, providing eight ±10 V voltage outputs. It converts commands from the Siemens S5 program into analog voltages. The output group is galvanically isolated; the individual channels are not isolated from one another.

Typical duties include sending speed or process setpoints to equipment with a suitable voltage input. The polarity and magnitude of the analog signal must match the receiving device's configuration. In analog control applications, confusing a bipolar ±10 V command with a 0–10 V input can produce an incorrect response.

Output range and model identification

The 4UB13 provides voltage outputs. The ±10 V / 0–20 mA ranges of 6ES5 470-4UA13 and the 1–5 V / 4–20 mA ranges of 6ES5 470-4UC13 do not apply to this model. Moving wires cannot make a voltage-only output suitable for a current-input receiver.

When considering replacement of 6ES5 470-4UB12 or 6ES5 470-4UB11, compare the complete order number, hardware revision and machine documentation. Membership of the same 470 family is insufficient evidence for a direct replacement without checking the installation.

Power supply and front connector

The digital section uses the system bus 5 V supply; the analog section requires external 24 V DC. With PLC input and output modules, successful communication alone does not establish that field power is correct. Evaluate grounding and the analog reference according to their separate functions in the cabinet drawing.

A 42-contact front connector is used. The S5 cable and connector range includes the crimp-type 6ES5 497-4UA12 and the screw-terminal 6ES5 497-4UB31 for a 20 mm mounting width. Check the housing, contacts and rack installation requirements together.

Key terminals are 1: F+, 2: F−, 3: L+, 21: L− and 42: MANA. Channel 0 uses 4: QV0, 5: S+0 and 6: S−0. In this analog I/O circuit, QV is the voltage output, S+/S− are sense connections and MANA is the common analog reference.

The receiver must present a load of at least 3.3 kΩ. S+/S− may sense at the load; where cable drop is negligible, fit S+–QV and S−–MANA links at the connector. These links are also required on unused channels. Consult the manufacturer diagram for the complete channel assignment.

Addressing and numerical representation

During PLC programming, match the address switch to the software's access address. The eight channels occupy 16 bytes. When reviewing the Siemens S5 architecture, do not assume that the rack slot alone determines the module's program address.

Output data uses 12-bit two's complement; nominal values of −1024 / 0 / +1024 units correspond to −10 / 0 / +10 V. Engineering units and the transferred word are different representations: check the STEP 5 word layout and the scaling expected by the selected function block.

Output behavior and troubleshooting

BASP output inhibit does not clear the last analog value. With the enable circuit active, loss of F+/F− power can cause QVZ. During PLC troubleshooting, check addressing, the enable jumper, supplies and measured output separately. CPU STOP is not a guarantee of zero output voltage.

The specified delay from data transfer until the output exceeds 99% of its final value is 5 ms maximum. Investigate electromagnetic interference, cable routing and connection continuity when a signal fluctuates. An EMC filter does not by itself correct a faulty reference connection or a loose contact.

When comparing 6ES5 470-7LB13 or 6ES5 470-8MA12, check more than the ±10 V range. System family, channel count, connector and addressing also matter. These linked models are comparison references, not confirmed direct substitutes.

Editor’s note

Start with the nameplate. Resolve the 4UB13 versus 4UA13/4UC13 distinction before purchase. A connector that physically fits does not establish the correct signal type.

Photograph the links. Record the address switch, enable jumper and S+/S− wiring before removing the original module. Missing connector links can easily be mistaken for an electronic fault.

Test all eight channels. On a controlled bench setup with a suitable load, compare negative, zero and positive commands. One correct channel does not establish the condition of the whole module.

Investigate load-dependent errors. If a voltage is correct unloaded but changes when the receiver is connected, inspect the input load, return conductor and sense wiring. Measure at both ends of the cable.

Verify stopping behavior. Check BASP and enable behavior against the machine's stopping design. For a used module, request channel-by-channel test results as well as clear identification photographs.

OtomasyonAVM resources and PDFs

+ About Siemens S5 PLC: system architecture and legacy installations.

+ S5 analog modules: individual input and output module pages.

+ S5 PDF files: the shared archive for S5 work outside the 90U group.

Related topics

+ 6ES5 470-4UA13: a different model with voltage and current outputs.

+ 6ES5 470-4UC13: the 1–5 V / 4–20 mA version.

+ 6ES5 497-4UB12: a screw-terminal connector option for a 40 mm mounting width.

Browse SIMATIC S5

+ S5 analog modules · S5 cables and connectors

+ SIMATIC S5 · Siemens S5 PLC · Siemens second-hand equipment

Siemens and external references

+ Siemens S5-135U/155U System Manual – English: C79000-G8576-C199-07, section 9.7; wiring, addressing and technical specifications.

+ Siemens ST 50, 1998 – English catalog, archive copy: pages 4/50–4/51, the 470-4U family and complete order numbers.

+ Siemens S5 to S7-1500 migration guide – English: Table 7-7, the 6ES5 470-4UB13 entry; a reference for migration planning.