6ES5 401-7AA13
6ES5 401-7AA13 – SIMATIC S5-110A/S 8-Channel 24 V DC Digital Input Module with Group Signal
Siemens 6ES5 401-7AA13 is an 8-channel, 24 V DC digital input module with optocoupler isolation and a group-signal function for S5-110A and S5-110S systems. Within the S5 digital input module range, its distinguishing feature is sending a group signal to the CPU when an input changes state. This Siemens S5 module supports applications requiring event notification in addition to reading input states.
It reads signals from pushbuttons, limit switches, compatible sensors and contactor auxiliary contacts. For group-signal selection, the eight inputs are divided into two groups: 0–3 and 4–7. Preserve this event-signalling function when selecting a replacement.
Input voltage and electrical ratings
Rated input voltage is 24 V DC. Specified levels are −35 to +4.5 V for logic 0 and +13 to +35 V for logic 1. Input current at logic 1 is 8.5 mA. Check the power supply and NPN/PNP output configuration against these thresholds and the module’s wiring arrangement.
The Siemens table lists compatibility with DC BERO proximity switches. When connecting an inductive sensor or photocell, assess the off-state voltage and active-state loading together. A sensor’s own indicator alone does not establish correct switching at the module.
Group signal and edge selection
The two switches at the rear each control a group of four inputs. According to the S5-110A manual, viewed from the rear, the left position selects a falling edge and the right position a rising edge. The selected 1→0 or 0→1 change in the group is signalled to the CPU.
Match this setting to the PLC program’s event-handling arrangement. During troubleshooting, monitor more than the input bit: check whether the selected edge produces a group signal and how the CPU responds.
Input delay
For the 24 V DC inputs, delay is 1.5–5 ms for both 0→1 and 1→0 transitions. The group-signal feature does not turn the module into a high-speed pulse counter. Assess pulse timing and contact bounce separately.
Isolation, wiring and LED behaviour
Optocouplers transfer the field signals to the system’s internal signal level. The four-input grouping used for event selection does not, by itself, establish a galvanic isolation grouping. Match field references and the grounding arrangement to the installed circuit diagram.
The green input LEDs are on the field side of the optocouplers. The S5-110A manual explains that they can remain illuminated with the PLC switched off if field voltage remains applied. An illuminated LED therefore does not prove that the CPU is running or reading the input.
S5-110A versus S5-110S placement
The S5-110A manual permits the 401 module in any suitable input position on the mounting rack, like the other input modules. The S5-110S manual specifies locations 0, 16, 32 or 48 for the group-signalling 24 V module. Keep these system-specific conditions separate.
In the S5-110S, addressing depends on I/O socket position and bus coding. Compare the SIMATIC S5 project’s address list with the physical connector arrangement. Two input modules must not share an input address; input and digital output module address spaces are considered separately.
Mounting and cable routing
The module snaps onto a socket on the S5-110 I/O mounting rack. Inspect S5 cables and connection hardware, socket contacts and the mounting-rack arrangement together during replacement. Approximate weight is 0.39 kg.
Permissible signal-cable length depends on whether cables are run together or separately and on adjacent-circuit voltage. Use the appropriate S5-110A or S5-110S table for the installed system and actual route rather than applying one length limit to every installation.
Differences from related modules
6ES5 400-7AA13 also provides eight 24 V DC inputs, but replacement selection must preserve the 401’s group-signal function. Working input LEDs do not establish that this additional function is present and enabled.
6ES5 405-7AB11 and 6ES5 405-7AB21 are 405 input modules for different voltage classes. Similar housings do not make them replacements for the 24 V DC 401; match the full order code to the field signal.
Editor’s note
Check both the 401-7AA13 label and the group-signal function when buying this S5 module. Eight working inputs are only part of the test. If the machine uses event notification, a standard 400 input module will not provide the same behaviour.
Before removal, photograph the two rear group switches. Left and right are described when viewing the module from behind. Turning the module around while checking it is an easy way to confuse rising- and falling-edge settings.
An input LED can remain on with the PLC switched off. That may simply mean the field supply is still present. Check the field signal and CPU side separately rather than treating the light as evidence that the processor is reading inputs.
Establish whether the controller is an 110A or 110S before moving the module. In particular, check the 110S location requirement of 0/16/32/48. A spare working in another machine does not establish that the present mounting position is correct.
For a used Siemens module, request tests of all eight channels in both logic states and both groups on their selected edges. Previous internal modifications may have suppressed group signalling. Isolate power before replacement; a small switch setting can explain the difference between working inputs and a working machine.
OtomasyonAVM resources and PDFs
+ S5 digital input modules · S5 cables and connection hardware · S5 mounting racks.
+ Siemens S5 shared PDF archive. Relevant documents are S5-110A Operating Instructions, GWA 4NEB 807 0690-02, and S5-110S/B Operating Instructions, GWA 4NEB 807 2121-02; both are in English.
Related topics
+ 400-7AA13 · 405-7AB11 · 405-7AB21 · 410-7AA11 digital output module.
+ NPN versus PNP · PLC troubleshooting · PLC programming.
Browse SIMATIC S5
S5 digital inputs · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page.
Siemens and external references
+ Siemens SIMATIC S5-110A Operating Instructions, GWA 4NEB 807 0690-02, 6ES5 998-0AA22, Issue 1, English. Printed 1.6 / PDF 10: 401 group signalling and placement; 1.12 / PDF 16: exact 401-7AA13 specification table; §3.2, printed 3.1 / PDF 28: rear-switch directions and LED behaviour.