6ES5 400-7AA13
Siemens 6ES5 400-7AA13 – 8-Channel 24 V DC Digital Input Module for S5-110
Siemens 6ES5 400-7AA13 is an 8-channel, 24 V DC, galvanically isolated digital input module for S5-110A and S5-110S/B controllers in the SIMATIC S5 family. Within the S5 digital input module range, it uses optocoupler signal transfer, draws 8.5 mA input current and has an ON and OFF delay of 1.5–5 ms.
The module reads switching signals from inductive sensors, photoelectric sensors and mechanical limit switches. Its eight inputs can be represented by the eight bits of one input byte. This model provides standard digital input acquisition; group signalling for interrupt processing is a separate feature of the similarly numbered 401 module.
Input voltage, sensor interface and delay
The nominal input voltage is 24 V DC. Siemens specifies −35 to +4.5 V for logic 0 and +13 to +35 V for logic 1; the intervening region is undefined. For positive switching field connections, consider the difference between PNP and NPN sensors and establish the return connection between the 24 V power supply and input circuit according to the wiring diagram.
Input current at logic 1 is 8.5 mA, and Siemens lists DC BERO proximity switches as connectable devices. Both the OFF-to-ON and ON-to-OFF delays are 1.5–5 ms. This is a digital input module; it does not measure an analog signal magnitude. Pulse applications must account for the input delay and CPU scan time together.
The manufacturer specifies 100% total load capability at 1.2 times the nominal voltage, referred to the sum of all input currents. Do not transfer the loading conditions of the different-voltage 405 modules to this version. Galvanic isolation separates the field and control sides, while correct reference connections and cable checks remain necessary.
Mounting rack, socket and mechanical arrangement
S5-110 I/O modules snap onto the appropriate S5 mounting rack and socket arrangement, establishing the mechanical and electrical connection. The manual lists dimensions of 166 × 40 × 150 mm, in height × width × depth order. Approximate weight is 0.39 kg. In a SIMATIC S5 installation, inspect socket contacts and retention as carefully as the module itself.
Addressing: socket coding and input bit
In this family, the module address depends on the socket position and its coded wiring. The manual identifies address 0 for the first I/O position. When checking the S5 PLC addressing arrangement, use the installed socket configuration. For example, eight channels mapped to input byte 3 can be monitored as I3.0–I3.7, or E3.0–E3.7 with German mnemonics. This illustrates the principle and is not a factory address assignment.
Why a lit LED does not prove CPU input acquisition
The green input LED is on the field side of the optocoupler. Siemens notes that it can remain lit with the PLC switched off if field voltage is still present. A lit LED therefore does not establish that the CPU receives the signal. In an S5-110A installation, also check the 6ES5 900-7AD11 CPU and the internal 5 V supply from the 6ES5 930-7AA12 power supply.
If the correct input state is visible in the program but the machine does not respond, inspect the program conditions and output side separately. The 6ES5 410-7AA11 output module, for example, performs a separate load-switching function. An input indicator does not establish that the output circuit or connected load is healthy.
Differences from the 401 and 405 modules
The 6ES5 401-7AA13 also has eight 24 V DC inputs, but adds group signalling and interrupt processing. Its edge selection, four-input groups and special location notes must not be attributed to the 400-7AA13. This distinction matters when replacing hardware in an existing program.
The 6ES5 405-7AB11 is rated for 115 V AC/DC, while the 6ES5 405-7AB21 is rated for 220 V AC/DC. Similar construction and channel count do not make their input voltage ratings interchangeable. Select the 400-7AA13 for 24 V DC field signals.
The address switch and front connection arrangement of U-range modules such as 6ES5 420-4UA11 do not apply to this module. Other compact S5 input cards, including 6ES5 421-8MA12, are not equivalent merely because they also have eight inputs. When purchasing a used digital input module, check the full order number, socket, individual channel tests and the results of reading the inputs through the CPU.
Editor’s note
Begin with the complete label. The 400-7AA13, 401-7AA13 and 405 modules can look deceptively similar. Standard 24 V inputs, interrupt functions and different voltage ratings are separate selection points; appearance alone is not enough.
Do not approve the module from its LEDs alone. These indicators show the field-side signal and can light while the PLC is off. Confirm that the expected input bit changes at the CPU before deciding that the complete signal path works.
Test all eight inputs. Record the channel order together with the program addresses. Apply the same test signal to each channel in turn and check both detection and release, so that a dead or sticking channel is not missed.
Include the socket in the inspection. Loose or oxidised contacts in an ageing system can imitate a module fault. With power isolated, inspect the seating, contacts and rack connections, and photograph the original arrangement before replacement.
Look for shared causes when several inputs disappear together. Check field power, return wiring, the system 5 V supply and CPU state first. Establish test conditions that prevent machine movement, and request the unit’s working or faulty status and exact test coverage before purchase.
OtomasyonAVM resources and PDFs
+ S5 PDF files — shared manual archive
Related topics
+ 401-7AA13 input module with group signalling
+ 930-7AA12 S5-110A power supply
Browse SIMATIC S5
+ Siemens second-hand main page
Siemens and external references
+ Siemens S5-110S/B Operating Instructions — English; 400-7AA13 specification table, printed page 9