Delta DVP08XP211T

Delta DVP08XP211T – 4 Input / 4 NPN Transistor Output Expansion Module

Delta DVP08XP211T adds 4 digital inputs and 4 NPN transistor outputs to DVP-ES2 and DVP-EX2 PLC systems. The host CPU supplies 24 V DC to the module electronics through the expansion bus. The output stage requires an external 24 V DC supply at UP and ZP. Show both power paths in the panel drawing.

Typical applications include additional sensors, indicators and DC control points on conveyors and packaging machinery. Delta’s ordering table also lists this code for ES3, ES3-TEC and EX3 families. Check expansion support and the power budget in the selected CPU hardware manual.

Inputs, outputs and terminals

Inputs X0–X3 accept 24 V DC at approximately 5 mA per channel with 4.7 kΩ input impedance. The ON threshold is >15 V and the OFF threshold is <5 V. Response is 10 ms OFF→ON and 15 ms ON→OFF (±10%). Match the common connection to the circuit when wiring an inductive sensor, photoelectric sensor or limit switch. For a PNP sensor, connect S/S to 0 V. For an NPN sensor, connect S/S to +24 V.

Outputs Y0–Y3 are NPN sinking. Section 2.5.5 of the 2024 and 2026 Module Manuals specifies 5–30 V DC and resistive load limits of 0.3 A per output and 1.2 A per common. The electrical table specifies ≤100 Hz, approximately 50 µs turn-on and 200 µs turn-off. The older DIDO sheet shows different values of 0.5 A per output and 1 kHz. This page follows the model-specific limits and electrical table in the current module manual.

Output power connects to UP at +24 V and ZP at 0 V. The specified tolerance is −15% / +20% and the module draws up to 5 mA from this connection. Calculate load current separately. In the manufacturer’s 24 V DC example, the load goes between the positive supply and the corresponding Y terminal. Leave the unused NC terminal open.

Mounting dimensions include 45 mm width and 90 mm body height. The module weighs approximately 107 g, has removable terminals and mounts to a 35 mm DIN rail or panel plate. Use the full dimensional drawing on printed page 2-5 for panel layout and clearance.

Programming, cable and X/Y addresses

PLC programming takes place in the ES2/EX2 host using WPLSoft or ISPSoft, depending on CPU support. The host ladder program uses the points as X and Y devices. X0–X3 and Y0–Y3 printed on the module are local channel labels. Verify actual addresses in the CPU I/O map and check expansion order. DVP X/Y addresses use octal numbering.

For USB access to a standard ES2/EX2 CPU, use UC-PRG020-12A on the CPU’s COM1 RS-232 port. A PC with a serial port can use UC-MS020-01A. In ISPSoft, select the connection and COM port through COMMGR. For other CPU families, choose the programming cable from the selected CPU documentation.

Related topics

Check the selected CPU’s high-speed inputs and pulse outputs for encoder counting and servo or stepper motor positioning. Select a suitable analog or temperature module for analog signals and Pt100 measurements. The host CPU and any network module determine industrial communication support, including RS-485, Modbus RTU and Ethernet.

Follow the manufacturer’s load protection diagram when driving coils. If an interposing relay drives the load, verify its coil current. Select the panel fuses, protective grounding and emergency stop arrangement according to the machine electrical design.

Related Delta modules

DVP08XP211R provides 4 inputs and 4 relay outputs. DVP08XN211T provides 8 NPN outputs, while DVP08XM211N provides 8 digital inputs. DVP16XP211T offers 8 inputs and 8 NPN outputs. For a new panel design, Derell PLCs and smart relays are also available as standalone control options.

Editor’s Note

When inspecting a used unit, check for the 211T suffix and the UP/ZP markings. The 211R uses a different terminal layout.

If inputs work but all four outputs fail to switch, check the 24 V DC across UP and ZP with the load connected.

Test each Y channel with a suitable current-limited DC load. Observe both the output LED and the load response.

If an X LED changes but the expected program bit stays still, verify the module order, device address and expansion connector.

Check both the individual channel current and the shared common current. Account for inductive loads and inrush separately.

Isolate supplies before removal or installation. Clear any test forces before commissioning.

PDF documents

Start with our Delta DVP PLC files page. The wiring diagram is in the DVP Series Module Manual, section 2.5.5, PDF page 45 of the 2026 edition. Use the shared programming and cable guides for CPU software and COM1 wiring.

DVP08XP211T · ES2/EX2 modules · DVP expansion modules · DVP PLC series · Used Delta PLCs · Delta Automation

External references

Delta DVP Series Module Manual (2026) · Delta DVP series catalogue · Delta PLC/HMI Cable Selection Guide