Delta DVP08RT-S
Delta DVP08RT-S – 8-channel NTC temperature input module
The Delta DVP08RT-S is a Delta DVP Slim specialty module with eight NTC temperature inputs. It runs on 24 V DC, supports two thermistor curves rated at 10 kΩ at 25 °C, and reports Celsius values in 0.1 °C increments. It sends readings to the PLC and has zero outputs.
Supported thermistors and measurement ranges
An NTC with R25 = 10 kΩ and B25/86 = 3977 K measures from −20 to +100 °C. Its raw Celsius range is −200 to +1000.
An NTC with R25 = 10 kΩ and B25/85 = 3630 K measures from −20 to +150 °C. Delta's catalog identifies the MF58-103 for this curve. The raw Celsius range is −200 to +1500.
The supply range is 20.4–28.8 V DC, power consumption is about 2 W, resolution is 12 bits, and the update time is 200 ms per channel. Full-scale accuracy is 0.5% at 25 °C ambient and 1% over a 0–55 °C ambient range.
PLC compatibility, software and cable
Legacy Delta documents list the DVP08RT-S with the DVP-SS, DVP-SA and DVP-SX CPUs. Check the module position in the right-side expansion chain against your project. Open the compatible PLC project in WPLSoft or use ISPSoft if it supports the CPU and project version. For COM1 on the DVP10SX11R/T, Delta's cable guide lists the UC-PRG020-12A for a USB connection at the PC and the UC-MS020-01A for an RS-232 connection at the PC. Check the exact CPU and port on other models.
In the ladder program, trace the FROM instruction to the module position and destination D register. Verify the project's CR address before writing a setting with TO. In Celsius mode, 253 = 25.3 °C and −75 = −7.5 °C. Use a signed value with one decimal place on the operator display. When the system uses RS-485 Modbus, check the ASCII or RTU mode and station settings against the existing project.
Choosing probes and checking the wiring
When monitoring a cabinet or cooling circuit, select a temperature sensor by its measurement range and B curve. Two 10 kΩ NTC probes can read close to each other at room temperature and diverge as they warm up. Use a matching input module for a Pt100, a type J or a type K thermocouple. Check the probe label to identify the required analog input type.
If readings jump as a motor starts, compare the routing of the sensor leads with the motor and drive cables. Check the voltage at the 24 V DC power supply and at the module. Checking for electromagnetic interference and reviewing grounding can help distinguish a faulty probe from wiring-related errors.
Editor's Note
When buying used, inspect the full model label, side expansion connector and terminals. Corrosion at a terminal can cause intermittent jumps in the reading.
Switch off power and disconnect the probe. Use a multimeter at about 25 °C. If the probe measures near 10 kΩ, test it at a second known temperature.
Connect a known-good probe with the correct curve to each channel in turn. Compare the readings at the same temperature.
If the display reads ten times too high, check the 0.1 °C scale. If the error grows as the probe warms, check its curve first.
When considering the DVP08NTC-S, check its own manual for the terminal layout, thermistor curve and CR mapping.